Installing My 8Kw Vevor Diesel Heater || Part 2

แชร์
ฝัง
  • เผยแพร่เมื่อ 23 พ.ย. 2024

ความคิดเห็น •

  • @BackmansGarage
    @BackmansGarage  11 หลายเดือนก่อน +18

    Please Read! If you would like a follow-up video on this after 1 year of use and some q&a, please like this comment and post if you have any questions that you would like to be answered below. Thanks for watching 👍

  • @PainterD54
    @PainterD54 9 หลายเดือนก่อน +3

    Motorcycle muffler insulation or "packing" as it's called works for wrapping the exhaust in to run it thru the wall. You can actually hold it in your hand with unit running. Another option is to wrap it in motorcycle exhaust wrapping. Both work great!

  • @rednecktek2873
    @rednecktek2873 ปีที่แล้ว +13

    You'll want an AC/DC converter of at least 20a rating to feed that heater. It needs about 13a to start between the pump, fan, and glow plug. Once it's fully lit off it'll drop down to about 3a of draw. Anything less than a 20a power supply will tend to sag the voltage just low enough that it sometimes will give you that alarm, especially if/when the glow plug gets a little dirty. Fortunately a 20a power supply is pretty cheap and bulletproof.

    • @hunkenpunken
      @hunkenpunken ปีที่แล้ว +1

      In the 5kw Maxpeedingrods it says it uses 10amp in startup

    • @rednecktek2873
      @rednecktek2873 ปีที่แล้ว +4

      @@hunkenpunken My shunt says 13.4a on startup at the highest point, so that's what I budget for when running wire and calculating.

    • @inktownfishing4505
      @inktownfishing4505 ปีที่แล้ว +4

      I picked up a 15 amp AC/DC converter on amazon for 30.00 3 years ago and still works fine on my 5-8 kw diesel heater.

    • @pstoneking3418
      @pstoneking3418 10 หลายเดือนก่อน +2

      You should always use a battery to power these units. Very dangerous using a converter because if there is a power failure the unit can't properly shutdown. Whereas if the battery gets low the unit will shutdown properly with a low voltage error.

    • @Nomaswearefull
      @Nomaswearefull 21 วันที่ผ่านมา

      ​@@pstoneking3418no

  • @Uphillfreefall
    @Uphillfreefall ปีที่แล้ว +3

    Please read!!! I just wanted to say as a new user of this heater. I took it to my 4200sq shop, not assuming it would heat the shop but with 3 furnace’s @45 degrees my bill is over $500 so the purpose of this heater is to keep my feet and fingers warm while I am rebuilding lower units and transmissions. I ran a 25’ vent hose to reach the drive stands. Works perfectly @ #2 on setting. Exit chamber is @180-187* . Today i added length to the exhaust (3/4)x 10’ pipe and within 20min the chamber temp climbed to 210* and the fuel pump was pumping faster. And a combustion smell. To me, that’s a rich/lean condition. Try it yourself. To note: the same applies to HVAC units. ( each 45 adds 2’ in line set.) bottom line less length and wide bends on the exhaust is best.

    • @paulwilliams8536
      @paulwilliams8536 ปีที่แล้ว +2

      Shouldn’t have a combustion smell, check your combustion chamber bolts are tight and the gasket isn’t damaged. Seen a few reports of loose combustion chamber bolts
      The pump rate and fan speed are just set to any setting at the factory to get them to run and are usually running rich search TH-cam for vortex he’s done a video on tuning the heater. Get a carbon monoxide detector too

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +2

      Will get it tuned in in time. The smell that I had was from the heatwrap getting settled/hardned.

  • @marcobrian1619
    @marcobrian1619 หลายเดือนก่อน +1

    Iv a 5kw in my shed. been in for 3 winters now.
    IV only got exhaust going out side....
    IV not used de-mid since.
    The air intake keeps air circulation....
    The rest is dry heated air.

  • @laurencemaddy3159
    @laurencemaddy3159 ปีที่แล้ว +5

    I think you will find that the inlet pipe in the bottom is for the combustion chamber only and should be outside.

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      I would agree that it would have been a good idea to do that yes.

  • @GloucesterLGB
    @GloucesterLGB ปีที่แล้ว +1

    I have my CDH against an outside wall in a cottage with sawn-lap board clad in aluminum on the outside, and plywood paneling over drywall on the inside. When I installed it 2 years ago, I faced a quandary as to how to get the exhaust through the wood-frame and wood-surfaced exterior wall. The only examples I found were through a concrete foundation, or a nearby window that had a fire-resistant panel inserted in place of an opened sash.
    Wood normally requires between 4-600°F to ignite, but with prolonged exposure to 150-250°F, it can ignite at as low as 200°F.
    My solution was to put a 4" dia hole through the wall - 7" from inside to outside. I centered a 10" section of 4" solid single-wall aluminum dryer vent pipe in the hole. I then placed a 3" diameter of the same length inside the 4" pipe with just enough spun fiberglass building insulation batting to center it inside the 4" pipe. I have a ~1" hole dead center in a 4" aluminum pipe cap on either end that keeps the CDH exhaust centered in the hollow 3" pipe. This rig keeps the outer surface of the pipe at well below 150°F on the inside with ambient of 75°F in the area around the heater with the pump at 2.8Hz. In fact, the surface of the pipe can be touched and held after 24hrs of continuous operation right where it makes contact on the paneling inside and it will not burn your hand - although it would not be comfortable to maintain skin contact for more than several seconds if the heater pump rate is set at 3.5-5.2Hz for several hours. Outside, only the small protruding 1" actual exhaust pipe even has any heat - even at outside ambients as warm as 50°F, the exterior 4" diameter casing and cap is not even body temperature at the higher heater settings. The set up also insures that the exhaust pipe from the CDH maintains enough heat to prevent any condensation in the exhaust as well.
    Once the temps outside drop below 45°F, I keep the CDH running pretty much continously. It has a 14VDC Meanwell 14VDC 17a output power supply connected with a 800MCA series 27 Marine battery and a 30a solar system instant'lossless switching relay - so that if the power goes out it will stay running on battery without the controller resetting to standby/off mid-operation and causing a meltdown. The only time it gets a shutdown is if I need to leave for more than 30 minutes or more. Then it gets a rest-cycle. So, I have had 2 years to note any protential problems with the exhaust system.

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน

      Thanks for the comment and of all the tips 👍

  • @bkee62
    @bkee62 2 วันที่ผ่านมา

    I really like the thimble insert that you made to go through the wall. however the protective tape you used is really good to protect skin but it will not really do anything as far as insulation goes. I would suggest using a "wool like" insulation I've seen on some other videos

  • @PainterD54
    @PainterD54 10 หลายเดือนก่อน +2

    One more thing you could do to help capture more heat off the unit - run a longer exhaust inside the building before exiting the tube. That will let the hotter length of tubing radiate heat inside before it goes thru the wall. That will be "phaze 4"!

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน +1

      I was thinking about running it through an egr cooler to make hot water for the pressure washer 😃

    • @Richard-nb4iv
      @Richard-nb4iv 10 หลายเดือนก่อน +1

      ​@@BackmansGarageI've seen guys retro fit an old cast iron radiator that is attached to the exhust then outside. It seem pretty efficient at recapturing heat that would have been lost from the exhust. There are some deals on used ones in the classifieds.

  • @hillaryclinton1314
    @hillaryclinton1314 3 หลายเดือนก่อน +1

    All of mine are indoors.. all mounted half way up the wall with 2 to 3 feet of always sloping down exhaust pipe on them before going through the wall. A small fan blows across it to capture that heat. A car battery with float charger (preference) OR a 30a power supply going th rough a ups powers it. Intake air is from indoors, it will not suck all the air out.. unit continually reheats warming indoor air. Exhaust hole is always 3 inch stuffed with house insulation and a heavy purpose bought exhaust flange outside.

    • @BackmansGarage
      @BackmansGarage  3 หลายเดือนก่อน

      Thanks for sharing, i would like to find a better way to use the exhaust pipe heat than i currently have.

  • @martinpanks992
    @martinpanks992 ปีที่แล้ว +3

    If you are ever stuck with the holesaw that is wandering around just go through a pice of thin plywood or strong cardboard and that will steady the bit on the next hole.

  • @JeffJones-k3b
    @JeffJones-k3b 11 หลายเดือนก่อน +2

    to make a saw hole to a larger size. put the existing size inside the desired size.

  • @Uphillfreefall
    @Uphillfreefall ปีที่แล้ว +2

    Also to add to my last book.. No volt meter needed as well. Basic group 27 battery and a $5 trickle is doing the job for me. And like I said the smell I was getting seems to get higher as the chamber temp increase. It’s a flange seal unit. It’s not water proof per say. Level 2-3 seems best. Hopefully this helps someone.

  • @thisisoff-grid2504
    @thisisoff-grid2504 ปีที่แล้ว +8

    You said you wanted to shut it off because it was too smelly?? Can you please explain what you meant because it is not supposed to smell like diesel at all...

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +5

      The smell was probably the glue and or heat wrap curing under the first few heatcycles. It smelled bad a few more times after this but eventually went away.

  • @chrismo9848
    @chrismo9848 ปีที่แล้ว +2

    These heaters have a built-in "low voltage" protection for being wired in to your RV or Semi sleeper, they actually shut off somewhere around 12.2V or 12.4V so the heater doesn't run your battery down too much and your vehicle can still start in the morning. If you are wiring it permanently, either get an adjustable 12V power supply that you can tweak to 12.6 - 12.8V or get a DC-to-DC step-up converter and tune it to that voltage. That will take care of your E2 error codes. These thing pull a little over 60W (if I remember right) while the glow plug is on when it initially starts up and then drops to like 20W when it's hot enough to run without the glow plug.

  • @rainrabbit9209
    @rainrabbit9209 ปีที่แล้ว +1

    Glad to see venting heat protection - nice job

  • @Ghettochappy
    @Ghettochappy ปีที่แล้ว +5

    I would put it in an isolated box outside and pull the inlet air to the heater from inside the house to prevent condensation and then send it in again thru another pipe. Both should fit through that one big hole you already got in the wall. Bara en ide! Bra video!

    • @PainterD54
      @PainterD54 10 หลายเดือนก่อน

      Both air hoses can be run thru the same opening into the house however, the cold air return (that goes into the back of the unit) should be taking air far away from the hot air coming into the house so the hot air can circulate thru the room before going back out.

    • @michaelllewellyn7215
      @michaelllewellyn7215 หลายเดือนก่อน

      No I think it is more efficient inside as less heat loss and you can play with the controls better I also think if in a small insulated box outside it could all get a bit hot and melt things and have a risk of condensation The noise is a bit of a problem indoors but once it has warmed up the room it runs a lot quieter say on H1 You do get used to it. The unit is very small and takes up very little space
      You do not have to stand in the cold refueling it . That is my thinking

  • @srenfreiesleben1028
    @srenfreiesleben1028 11 หลายเดือนก่อน +2

    Nice to see something from a fellow Scandinavian :) I am working on a diesel heater for our camper at the moment, also from Vevor :)

  • @tonyshipman257
    @tonyshipman257 ปีที่แล้ว +4

    You can ramp it up to heat the space faster and then turn the setting down to maintain the temperature. This will also quiet the unit down with a lower setting.

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      Thanks 👍

    • @hunkenpunken
      @hunkenpunken ปีที่แล้ว

      ​@@BackmansGaragevad var det som "luktade"??

  • @brentmcmahon8188
    @brentmcmahon8188 ปีที่แล้ว +3

    Fuel gelling up and false starts because the fuel won’t start first and you would have to put a quart of gas in 5 gallon of diesel to get to ignite better and you may have to add more gas if it’s super cold and doesn’t want to start. But this me and Iam not telling body to do anything except what manual says .

    • @BackmansGarage
      @BackmansGarage  2 หลายเดือนก่อน

      Im just running it off pure Diesel at the moment. Works alot better than the mixed in with green stuff.

  • @billmorgan6110
    @billmorgan6110 ปีที่แล้ว +5

    Special Trick:
    When drilling using the large hole drill saw:
    Step: (#1)
    Only drill (1/2) way through till only the drill just breaks through the other side.
    Step: (#2)
    From the other side completely drill through wall.
    Step: (#3)
    Instead use a (3") gas heater vent. (Inner Pipe)..
    Step: (#4)
    Use black "wetted" fiberglass motor cycle exhaust tape.

    • @hillaryclinton1314
      @hillaryclinton1314 3 หลายเดือนก่อน

      Standard home fiberglass batting works fine. Mineral wool is even better.

  • @jimibmore
    @jimibmore 11 หลายเดือนก่อน +1

    Nice clean installation. Well done. The only thing I would be aware of is the exhaust ground level with snowfall.

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน +2

      Thanks! It's a good point, not to mention putting anything else in front of the exhaust on the outside. I came close to putting some wheels in front of the exhaust once, but since the exhaust pokes out a bit I realized it probably wasn't such a good idea to put them there.

  • @OverlandSubaru
    @OverlandSubaru 11 หลายเดือนก่อน

    Fridged air does not contain a lot of moisture. Humidity levels in winter are very low.

  • @patricklockerby4308
    @patricklockerby4308 ปีที่แล้ว +3

    Very informative video.
    Looks like you were using an LED power supply. This will restrict the maximum voltage and current to the point that the heater doesn't get enough startup power. (Power in Watts = Volts x Amps.)

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน +1

      Jepp, bad idea with the led power supply. Should hav bought somekind of 12v ups system

  • @dougbas3980
    @dougbas3980 11 หลายเดือนก่อน +1

    I imagine the smell was from the initial heating of new burner parts and should go away after one or two burns. Nice install. You are belt and suspenders with your wall pass thru (LOL). I imagine you moves the condensate drain hole to the bottom before final sealing?

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      Haha thanks. No, i thought since the exhaust temps are so high it will burn off any water near and that will evaporare out of the hole. Its mostly there to prevent somekind of pressure build up from boiling condensation water.

  • @chrisharrell2449
    @chrisharrell2449 ปีที่แล้ว +3

    If you put a return as well as flow, and put heater in a insulated box As a lot of UK home owners are doing to avert the high energy cost her due to the war. there will be no condensation. its the opposite maybe to dry a heat for some! I heat the whole of my ground floor of house on lowest setting using 150 ml per hour just under 7 hours for 1ltr of kerosene in my case as its much cheaper than diesel is in UK

    • @MickeyMishra
      @MickeyMishra ปีที่แล้ว

      Its kind of nuts this thing is still going on almost 8 months later. Now they are planing to use battery powered Tanks and planes to be "green" while turning everything red. Crazy times. But since when has war ever made any sense?
      If there ever was a showcase of humans stupidity, war would rank quite high on the ladder .

  • @jw200
    @jw200 ปีที่แล้ว +3

    You should take the air from outside and feed it to machine with another pipe.
    With current setup you will burn out all of the oxygen and you may pass out.
    Unless you have very good ventilation.

    • @GloucesterLGB
      @GloucesterLGB ปีที่แล้ว

      Simply - NO. There is no more chance that ..."you will burn out all the oxygen and pass out"... than you would risk from running a clothes dryer vented to the outside, a bathroom fan, or a kitchen exhaust hood - all WITHOUT a fresh air intake. If you actually own and operate a CDH, you will note that it actually draws less CFM than any of the aforementioned examples. Even without test equipment, comparing the movement of the exhaust off the 1" dia CDH exhaust that your intake pipe in feeding through the burner, to the amount of air at your dryer vent, should convince you that you are not in danger of creating any vacuum or fresh air starvation.
      While cold-air intakes are an advantage in ICE's, this is a heater - there is no compression benefit from pulling colder/denser air into the combustion chamber as it is a simple burner not a compression cylinder. In this case warmer is better.

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน

      Guess i have good ventilation then 🤷‍♂️

  • @gregorypoulos8596
    @gregorypoulos8596 ปีที่แล้ว +1

    Choice #1 A small AGM with trickle charger Choice #2 House connected to UPS Choice #3 Spare motherboard located in sock drawer...Lol Just Sayin.

    • @rednecktek2873
      @rednecktek2873 ปีที่แล้ว

      You'll want an AC/DC converter of at least 20a rating to feed that heater. It needs about 13a to start between the pump, fan, and glow plug. Once it's fully lit off it'll drop down to about 3a of draw. Anything less than a 20a power supply will tend to sag the voltage just low enough that it sometimes will give you that alarm, especially if/when the glow plug gets a little dirty. Fortunately a 20a power supply is pretty cheap and bulletproof.

  • @Melvinschroeder
    @Melvinschroeder 11 หลายเดือนก่อน

    Could use metal asbestos chimney pipe to go through wall as a liner.

  • @morgaj21
    @morgaj21 ปีที่แล้ว

    Trouble is with these videos is that other people say running the input from inside will increase condensation. Very difficult to get a difinitive method of installation.

  • @dennydewaal137
    @dennydewaal137 ปีที่แล้ว +2

    I have seen a video of someone, running the exhaust tru un old boiler filed whit sand . Creating a sand heat battery.. maybe un idea for you

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      It's probably a good idea if you want to store the heat for long and is probably more suitable if you want to use the diesel heater as your primary source of heat. I'm my case it would use too much space for the time I need to use this.

  • @450rhino1
    @450rhino1 ปีที่แล้ว +2

    That is a good setup as your air going in is already pre heated, not drawing it from outside. Great presentation. TKS.

    • @christopherdaniels4148
      @christopherdaniels4148 9 หลายเดือนก่อน +2

      It's taking heated air from inside the shop, burning it in the combustion chamber then exhausting that air outside. To make up for the air" burned" from inside the shop that means cold air MUST seap into the shop. So it's actually more efficient to use a "cold air intake" that's drawing air from outside, burning it, then exhausting it outside.

  • @GMCLabs
    @GMCLabs 9 หลายเดือนก่อน +1

    Yeah they lie about the power draw on these things. They only use a couple amps once they are running, but on startup it can be 15 to 20 amps. My 12 amp supply wasn't even enough for mine. My solution was to add a 12V 7AH NiCD battery pack. That gives enough extra power to start the thing, as well as act like a UPS if I have a power failure. You don't want to lose power to that while its running, the hot heater core will melt the plastic case if the fan stops running. I also like the NiCD better than a lead acid battery, BC I can keep my PS set to 14V and that will keep the NiCD pack charged without ever over charging it. Running the heater at a slightly higher voltage is better bc the fans run a bit faster. Its also rated to 16 volts so it won't hurt the heater either.

    • @michaelllewellyn7215
      @michaelllewellyn7215 หลายเดือนก่อน

      Yes a battery is a must have as the unit must be able to go into its cool down mode if you should ever have a mains failure as the plastic internals could melt

  • @hunter7181
    @hunter7181 ปีที่แล้ว +7

    Det säkraste är att köra den från ett batteri för om det blir strömlöst under drift så kommer kontrollkortet i den att gå sönder då fläkten stannar.

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว

      Sant, Har faktiskt inte tänkt på det scenariot.

    • @MickeyMishra
      @MickeyMishra ปีที่แล้ว

      Absolutely!

  • @pstoneking3418
    @pstoneking3418 10 หลายเดือนก่อน +1

    People are always trying to use ac-dc converters when they are designed to use batteries, and get all kinds of weird error codes.

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      True, I was thinking about using something called an UPS uninterrupted power supply that uses 220v to make 12v for the heater and that had a battery backup installed in case of a power-out situation.

  • @brentmcmahon8188
    @brentmcmahon8188 ปีที่แล้ว +2

    It sounds like paint and oil burning off when so crank it wide open for a couple hrs out side should cure you smell test .

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว

      Yes, it doesn't smell anymore. I think it was mostly the heat wrap curing that made the smell.

    • @alexanderiturraldeleon6385
      @alexanderiturraldeleon6385 11 หลายเดือนก่อน

      Did the same set up heat wrap smokes and smells. Cure heat wrap running till it stopped smoking and no smell now

  • @ponchoremerize5508
    @ponchoremerize5508 ปีที่แล้ว +1

    You do realize the Fiberglass, I.e. what you said will burn. Are actually used in insulating very hot pipes. Like steam lines in power plants. Former U.S. Army Engineer here.

  • @IVAN-bs5bq
    @IVAN-bs5bq หลายเดือนก่อน

    Yes run off mains without a battery back up and kill the heater if you have a power cut !!

  • @PUBHEAD1
    @PUBHEAD1 ปีที่แล้ว +3

    How hot did the wall feel from the exhaust? I want to install one but need to vent it safely without spending $$$$$ on horizontal ducting

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +4

      Absolutly no problem with the heat :)

    • @PUBHEAD1
      @PUBHEAD1 ปีที่แล้ว +2

      @@BackmansGarage thanks for the reply. Much appreciated 👍

  • @scottweedin7570
    @scottweedin7570 11 หลายเดือนก่อน +1

    Could you put the unit outside , run the air intake and heating line thru the wall so you dont have that noisy unit running inside ?

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน +1

      Could try it for comparison if i get my hands on another unit one day. But for now there are no plans for it.

  • @allexandruprroca6713
    @allexandruprroca6713 10 หลายเดือนก่อน +1

    9:11 and that is how you build yourself a katana!

  • @The-Mandolorian
    @The-Mandolorian 11 หลายเดือนก่อน +1

    Hi, at the end of the video you mentioned there was a bad smell.
    What was that due to?
    Do these heaters cause a smell in the area they are placed?
    Would it be better to put the whole unit outside and duct in the hot air?

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      No it was smelling some during break-in. Not its all right 👍

  • @allt-under-solen
    @allt-under-solen ปีที่แล้ว +5

    De är glödstiftet som drar mycket ström vid glöggning ca 10A vid uppstart på min Vevor 5kW sen drar den ca 40 W på full effekt. I princip kan man montera ett litet batteripack parallellt med nätdelen typ litiumjon 3S 2-3Ah minst 5C bör räcka för uppstart.

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +3

      Grymt bra info 👍

    • @allt-under-solen
      @allt-under-solen ปีที่แล้ว

      @@BackmansGarage Det är ett alternativ till en 10 - 12 A nätdel och "modern" switchade nätdelar brukar stänga av vid överbelastning.

    • @allt-under-solen
      @allt-under-solen ปีที่แล้ว

      Har du lite avgasbandage kvar kan de vara klokt att isolera rörkröken närmast värmaren då bränsleledningen är mycket nära. Kontrollera om de finns vassa plåtkanter där bränsleledningen passerar, räcker långt med en tejp bit. Kontrollpanelen är lätt och flytta om man vill.
      Enkel och vettig installation :)

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      Kan man inte styra lijon batteriet på något sätt så att den bara är aktiv under uppstart? Typ via någon utgång på värmaren kopplat till ett relä lr liknande.

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +2

      Japp, såg lite förbättringsmöjlighter där med. Vill få dit lite avgaspasta på innan bara :)

  • @LilYeshua
    @LilYeshua ปีที่แล้ว

    A glass pack muffler might could do the trick. Aren't those diesel heater's exhaust pipes notorious for splitting open at it's seam?

  • @FixitEasyDIY
    @FixitEasyDIY 11 หลายเดือนก่อน +2

    Nice video ❤❤❤

  • @rexclay2231
    @rexclay2231 ปีที่แล้ว +1

    #2 heating oil same as diesel , but added color

  • @kevinmorris5726
    @kevinmorris5726 ปีที่แล้ว +2

    Computer power supplies work well

  • @JohnSmith-ef6rg
    @JohnSmith-ef6rg ปีที่แล้ว +2

    Great video. For the metal exhaust, what do you call the rims you put on both sides? Would have been great to see how you did that. Thanks!

  • @markackerman9788
    @markackerman9788 9 หลายเดือนก่อน

    I would have to put through the wall higher up because of snowfall

    • @BackmansGarage
      @BackmansGarage  9 หลายเดือนก่อน

      It was convenient since the hole was already partially made. A good thing would be to have a reminder to check the outside before starting tho.

  • @brentmcmahon8188
    @brentmcmahon8188 ปีที่แล้ว

    Central location will warm better not stuck in a corner.

  • @azza1793
    @azza1793 11 หลายเดือนก่อน

    One problem with having the heater inside is the noisy pumps which continuously clicks away

    • @Zzrdemon6633
      @Zzrdemon6633 10 หลายเดือนก่อน +1

      80% of the time I have to wear hearing protection in my shop/garage and the music is always blaring too so the slight noise from the heater is drowned out or inaudible anyway

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      I thought it would be an annonying sound, but the more i habe it on the more I'm starting to like it. 😀

  • @martinpanks992
    @martinpanks992 ปีที่แล้ว +1

    You have a perfect AC unit there! Why the need for a CDH?..

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน +1

      Mostly for very cold and pricey days or when I need alot of heat fast for defrosting etc.

  • @rodkirt9273
    @rodkirt9273 10 หลายเดือนก่อน

    A 2 KW heater will heat a 8 X 8 X 7 foot room even if it has no insulation in the floor , walls or ceiling .

  • @chrishilbilly
    @chrishilbilly 10 หลายเดือนก่อน +1

    Next time use a hole saw the size of the hole thither the hole saw the size you want it one inside the other and boom

    • @BackmansGarage
      @BackmansGarage  9 หลายเดือนก่อน

      Yep saw this by another creator, not a bad idea :)

  • @stuartcotterill9475
    @stuartcotterill9475 ปีที่แล้ว +2

    What is that thing called you put on the pipe on each end? I need them badly!!! I use a bean tin for my heater exhaust 🤣

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      On the exhaust pipe or the pipe going through the wall? 🙂 On the exhust pipe i have just welded on a couple of 2mm plates with a 25mm hole drilled in the center 👍

    • @stuartcotterill9475
      @stuartcotterill9475 ปีที่แล้ว +1

      @@BackmansGarage sorry, the pipe going through the wall?

  • @spanishconmigo122
    @spanishconmigo122 9 หลายเดือนก่อน +1

    I need to remove the plate on this heater to change the glow plug. Can you help?

    • @BackmansGarage
      @BackmansGarage  9 หลายเดือนก่อน

      Can probaby fit that in when doing the 1 year recap of the heater that will be made soon.

    • @spanishconmigo122
      @spanishconmigo122 9 หลายเดือนก่อน

      @@BackmansGarage We got it popped off and replaced. I feel so proud about that

  • @Danguy351
    @Danguy351 11 หลายเดือนก่อน

    I was wondering if you could pls share a link or purchase info for the flange that you mounted on either side. Didn't have any luck at the local home Depot

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      www.vvsochbad.se/vaggstos-oe-100-mm-1017048?gclid=Cj0KCQiA2KitBhCIARIsAPPMEhIHrzko3S4mAP7fK9LUneF2EYGILpEF8rrBrgMoMSGorc8M_dyiRy8aAoUxEALw_wcB
      I used something lile thisone but it was at Byggmax (local hardware store)

  • @ClownWhisper
    @ClownWhisper ปีที่แล้ว +1

    What brand did you buy it I just wandered in the room in the middle of your video mine you can hardly hear it run you hear little tick tick tick tick tick and that's it and a little fan noise but hardly nothing

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน

      Its from vevor, but i think most of these ebesprächer knockoffs come from the same place.

  • @jeffvanderveen2890
    @jeffvanderveen2890 11 หลายเดือนก่อน

    How come you didn't run yhe exhaust into a heat exchanger , then out the wall . Heat exchanger also gets warm and keeps garage warm .

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน

      Maybe if this was a more permanent solution, but for now, its just auxillary heat for when i need the little extra. However, i like tha idea of heating water for the high pressure washer in the future, but i would probably use a dedicated diesel water heater for that. But maybe i will cosider adding a heat exchanger (egr cooler type) to use some of the exhausted heat as well.

  • @CliffE-k3j
    @CliffE-k3j หลายเดือนก่อน +1

    Kollade du temperaturen runt utloppet i väggen,blev det som du hade tänkt med isoleringen?

    • @BackmansGarage
      @BackmansGarage  หลายเดือนก่อน +1

      Känns tryggt, men inget mätt så direkt. Kommer en uppföljare på denna snart 👌

    • @CliffE-k3j
      @CliffE-k3j หลายเดือนก่อน

      @@BackmansGarage Jag snodde din avgasinstallation på ett liknade sätt, dock har jag inga gipsväggar med isolering utan endast tjocka träväggar utan isolering. Men det verkar funka! Tack för en kanonvideo och jag ser fram mot en uppföljning.

  • @josephbowles4995
    @josephbowles4995 ปีที่แล้ว

    He’s a Happy Hole cutter lol !😊

  • @donbot5000
    @donbot5000 11 หลายเดือนก่อน +1

    use a piece of plywood with same size hole as a guide next time.

  • @viggalvens
    @viggalvens หลายเดือนก่อน +1

    Nyfiken. Lukt, vad var det för lukt?
    Väntar på att min ska komma med posten 😊

    • @BackmansGarage
      @BackmansGarage  หลายเดือนก่อน

      Det va nog bara lite gammelt bös som va från fabrik. Den brände in sig efter ett par ggr och nu luktar det inte mera 👍 Still going strong efter dessa år iaf. Tips är dock att köra på blankdiesel.

  • @chrisb5839
    @chrisb5839 11 หลายเดือนก่อน

    If you get an exhaust leak between the unit and the wall, the room will fill with carbon monoxide.

  • @fanatickornfreak
    @fanatickornfreak ปีที่แล้ว +2

    Think i recognise that hole saw haha

  • @bluefloyd6058
    @bluefloyd6058 10 หลายเดือนก่อน

    Suppose it snows and blocks your low lying exhaust!!

  • @lillydog0905
    @lillydog0905 10 หลายเดือนก่อน

    It's drawing to many watts because of the glow plug

  • @cdoublejj
    @cdoublejj 11 หลายเดือนก่อน

    i would consider a longer pipe outside, i could see that blowing back in if you have the door cracked. i hear they are considering banning these because don't get he corbonmonoxide far enough away.

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน

      I would highly recommend using a carbon monoxide alarm as soon as you are heating with anything that will produce carbon monoxide.

  • @machine7767
    @machine7767 ปีที่แล้ว +1

    So it took, 3 hours to heat your work space? How big is the work space? What was the outside temp?

    • @rednecktek2873
      @rednecktek2873 ปีที่แล้ว +2

      9:27pm is 21:27, it was up to temp at 22:12 so about 45 minutes and NOT on full tilt.

    • @BackmansGarage
      @BackmansGarage  2 หลายเดือนก่อน +1

      space is about 27sqm 2.35m to ceiling.

  • @russellesimonetta9071
    @russellesimonetta9071 11 หลายเดือนก่อน

    Minus 20?? Diesel turns into slush when it gets super cold like 0.

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      It's winterdiesel during the cold season here in Sweden. I think its good down to around -32 celcius

  • @Martin-tb4oo
    @Martin-tb4oo ปีที่แล้ว +1

    What was smelly?

    • @BackmansGarage
      @BackmansGarage  2 หลายเดือนก่อน

      De vara bara något bös från när den va nystartad. Det brännde bort efter ett par timmars körtid.

  • @ClownWhisper
    @ClownWhisper ปีที่แล้ว +2

    Smelly? You literally could not be able to smell anything there's something wrong with it that one because again I can't hear mine run hardly at all it sounds like a tiny fan running and I can't smell a damn thing not a damn thing

    • @BackmansGarage
      @BackmansGarage  11 หลายเดือนก่อน +1

      It was the heat wrap hardeing 👍

  • @xatazch
    @xatazch ปีที่แล้ว

    Vad var det för lukt som du pratade om i videon? är det diesel eller rök?

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      Förmodligen ifrån härdningen av avgasbandaget. Luktar ingenting längre i alla fall :)

  • @miikis86
    @miikis86 ปีที่แล้ว +2

    Dina händer börjar också klia av bergullet som är isolering i din vägg. Ps. De brinner inte. =D

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +2

      Sant, värsta va att jag hade tatt av och på mig jackan flera ggr så nu när det klia hela veckan 😄
      Gött att det inte är så brandfarligt då iaf 👍

  • @abecoulter8550
    @abecoulter8550 ปีที่แล้ว +1

    thats not 8KW

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +1

      Technically no. It's just the "8kw" model I guess. False advertising from 🇨🇳 like always 😄

    • @abecoulter8550
      @abecoulter8550 ปีที่แล้ว

      @@BackmansGarage maybe if you were to use Jet A1

  • @pauls466
    @pauls466 ปีที่แล้ว

    It is NOT a 8 kw . Not even close.

  • @Dn8484out
    @Dn8484out ปีที่แล้ว +1

    To much work for the average person

    • @baileyhatfield4273
      @baileyhatfield4273 11 หลายเดือนก่อน

      The heater costs like 150 to 200 canadian dollars. So. It's fairly cheap for what it is. Depends on the application

    • @BackmansGarage
      @BackmansGarage  10 หลายเดือนก่อน

      Yes

  • @daddyeeoo
    @daddyeeoo ปีที่แล้ว +1

    Shouldn't need the muffler. Just maybe a screen to keep the bugs out when not in use.

    • @BackmansGarage
      @BackmansGarage  ปีที่แล้ว +3

      Im having some condenstation issues when not i use, the exhaust becomes a "vent" 😄

  • @raymondj8768
    @raymondj8768 ปีที่แล้ว

    Dude n old computer brick would put enough power out if u have one !!!