Huanyang VFD 2.2kw (pt1/2) - Wiring

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 พ.ย. 2024

ความคิดเห็น •

  • @seldian
    @seldian 4 ปีที่แล้ว +1

    lol i love how casually 'youll melt your wires or burn your house down' was delivered. Thanks for the info!

  • @shammient
    @shammient 8 ปีที่แล้ว +1

    I run one of these on my router. Mach3 controls it just fine, just requires the standard messing around with settings. On/off is just an output from the bob to a relay and speed control is via the 0-10v output.
    I use also us a couple of AC Tech VFD's in the shed and they're very similar.

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Great! Thanks for posting that.

  • @EnlightenedSavage
    @EnlightenedSavage 8 ปีที่แล้ว +1

    Perfect video! Was just about to purchase one. Watching your video will save me a lot of time.

  • @LarrySbrusch
    @LarrySbrusch 4 ปีที่แล้ว

    will the motor on lathe still run without the green, white and black not connected..I have my unit hooked up to 220 volt and have 110 volt on each leg then I test the voltage at lower right side wires and I have 148 volts (each) on all three wires going to the three phase motor..my box is a little different...but looks similar. no brand name on it or instructions..so I am assuming if the wires up top are not connected the lathe will not run..

  • @richardleslie410
    @richardleslie410 3 ปีที่แล้ว +1

    HI Russ, I am running a 110 vac1.5 kw spindle on a 110vac 2.2kw vfd. I have upgraded to a 110 vac, 2.2kw spindle for the larger collet size. I previously had my max current PD142 set to 7 amps which ran fine. I went to increase the amps on my drive and see it only goes to 11 amps. Do you know if this the max for the drive or if it is being limited by another parameter. this is a Haugyang VFD.

    • @russtuff
      @russtuff  3 ปีที่แล้ว

      I just tried it on mine and hit the same limitation. None of the documentation I have says if this is supposed to be the max so I'm not sure.

    • @richardleslie410
      @richardleslie410 3 ปีที่แล้ว

      I wonder since7 amp setting for 1.5kw works well, so maybe the 11 amp setting for 2.2kw is Correct. I guess that I will try and see. Being this is a 3 phase set up on the output side it will be different than computing current from a regular formula. Thank you for you response. Good day to you.

  • @sadbutwedidntstartit
    @sadbutwedidntstartit ปีที่แล้ว

    Question , I have the 120VAC input drive. I've seen videos where it is hooked up to a single phas with a single phase AC motor as the load. They don't mention how thw AC in is wired. I'm trying to figure out where to wire the Neutral wire to. The Line input ( black ) will go to 'R', does the neutral go to 'S' or to the ground terminal on the unit. Thanks

  • @jetkrazee
    @jetkrazee 7 ปีที่แล้ว

    Thanks so much for the excellent tutorial. Hadn't been able to find anywhere that explained about what to do with the neutral wire though I assumed it would be connected to ground but was a bit hesitant. Thanks again! :)

    • @russtuff
      @russtuff  7 ปีที่แล้ว +1

      Great! I'm glad the video helped :)

    • @toolguy6057
      @toolguy6057 7 ปีที่แล้ว

      Neutral is not ground. See my post.

  • @jodyolivent8481
    @jodyolivent8481 8 ปีที่แล้ว +1

    Nice work and great information.
    I went with the Teco L510 on the lathe. I specifically didn't get into any wiring info in my video due to the liability issue. I love haveing my lathe running under 3 phase, variable speed, power. It is so simple to change speeds. Now to get the carriage brackets made.

  • @nathancamplin2735
    @nathancamplin2735 2 ปีที่แล้ว

    Great video mate , im trying to pwr a hoist with vfd but the sparkie wired the neutral back to the single phase input side , should the neutral coming back off the 3 phase side be wired ti ground terminal of the vfd?? Please
    Help i got no output from mine 😞

  • @ejpjr6280
    @ejpjr6280 2 ปีที่แล้ว

    I have this vfd and I want to add a two wire remote switch. I know I have to program some ports and land wires there. Can you tell me the process? Thx

  • @DrunkNewsNetwork1
    @DrunkNewsNetwork1 5 ปีที่แล้ว

    how would you feel about 18 gauge stranded from spindle to the vfD?

    • @russtuff
      @russtuff  5 ปีที่แล้ว

      Depends on the load. For my motor 16ga seemed like the safest.

  • @CNC4XR7
    @CNC4XR7 8 ปีที่แล้ว +1

    Hi Rus,
    Great video, What Model VFD is it Exactly I know 220V 1hp? I heard you mention the 1 HP three phase motor.
    Be Safe,
    Sam

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Mine is the 2.2KW version, I'm not sure of the exact model number as it isn't listed anywhere on the VFD.

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Added the "2.2kw" to the title. Thanks Sam.

    • @CNC4XR7
      @CNC4XR7 8 ปีที่แล้ว

      Thanks Yeah folks might want to know its a 3HP VFD

  • @CORZER0
    @CORZER0 6 ปีที่แล้ว

    Uniform? Wow, you really are old school! Utah where I'm from (graduated high school y2k). Thanks for the content! Very helpful.

    • @russtuff
      @russtuff  6 ปีที่แล้ว

      Are you saying Uniform is no longer in use, or is it just that it sounds weird hearing phonetics being used? I learned the phonetic alphabet from listening to my old man talk on the radio.
      Go Utah!
      -Romeo Uniform Sierra-

    • @CORZER0
      @CORZER0 6 ปีที่แล้ว

      Uniform is proper. Not sure why or how I got stuck on Utah! Just always been that way. By the way, do you have a physical switch or plug/physical disconnect between your breaker and your vfd? I'm thinking about implementing both, as in: breaker>switch>plug>vfd>motor. In case I want to move my unit around (2x72 belt grinder, 3hp Baldor motor).

  • @jamesandrew1750
    @jamesandrew1750 8 ปีที่แล้ว +1

    Thanks really useful guide & links

  • @bojansar1
    @bojansar1 6 ปีที่แล้ว

    I live in Europe with 220v electricity,Can you give your opinion on grounding the spindle?There are many opinions on the net about it,on how you should solder an additional wire inside the spindle to the body itslef,or not doing anything at all,but the pin number 4 is empty,it is not connected to anything.

    • @russtuff
      @russtuff  6 ปีที่แล้ว

      3 Phase motor signals are balanced, so a ground isn't required to get it running. That said, I would agree that attaching a ground to the spindle body is a good idea just to make sure you're being safe. I didn't realize some spindles don't have a ground lug on them already. Are you using a high-freq 2.2kw spindle? I have one but never wired it up so I'm not sure if it allows for grounding either.

    • @bojansar1
      @bojansar1 6 ปีที่แล้ว

      russtuff Mine is 0.8kw spindle.It has a number 4 pin but when I dissamble it there is no connection to anything

  • @Zerostar369
    @Zerostar369 5 ปีที่แล้ว

    Can I tie the 220v neutral and the motor ground wire to the same lug on the VFD if I dont have a chassis ground? In my case Im going to be mounting the 3hp vfd variant of this to my table saws cabinet.

  • @sp4rksaflyin
    @sp4rksaflyin 2 ปีที่แล้ว

    You want to add 25% for motor start to allow the the voltage spike upon starting. So 3.2 x .25= 4.05 Amps.

  • @plasticbaldy
    @plasticbaldy 8 ปีที่แล้ว

    Currently my 240V power shuts down at the end of repetitive cycles and restarts when I click 'Cycle Start ' on my Mach 3. If I only connect the motor wires and these interrupted 240V power wires will I have to reset the speed etc on this VFD on every cycle ?

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      I'm not sure I understand your question. The VFD can be turned off/on at any time and will not lose its programmed parameters. Disconnecting the main voltage is not going to deprogram it.

  • @yazicib1
    @yazicib1 6 ปีที่แล้ว

    Thanks for the video. I got a question. I bought a VFD and a spindle (2.2 kw air cooled) but when it arrived i realized i ordered 220V instead of 110V i have in my garage.
    It looks exactly like yours. Do you know if these models have the same hardware and configured differently and i can change some switch and voila itis 110v ? PC power supplies have that switch for example...
    If not, if i exchange the product, changing VFD is enough? Or spindle will meed to be changed too?
    Thanks

    • @russtuff
      @russtuff  6 ปีที่แล้ว

      For the VFD, certain models can either be powered by 110v or 220v. They all look the same, so it's a bit of a hassle figuring out which VFD you have. You will probably have to comb through the manual to find out if yours will run off 110v. Or just wire it up and see what happens :/
      For the spindle, you might be able to run it off 110v but you'll be getting half the power. 2.2KW is calculated on 220v and 10 amps. if you can only supply 110v you'd have 1.1KW at 10 amps. I'm not sure how well the motor will run like that (or if at all).

  • @Paxtraxx
    @Paxtraxx 7 ปีที่แล้ว

    I have one of these drives and I want to control a single phase fan motor (like the kind used for a restaurant kitchen exhaust). Do you have advice on wiring for 110VAC mains and motor?

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      +Gary Packer That shouldn't be a problem, just make sure you program it for 110.

    • @toolguy6057
      @toolguy6057 7 ปีที่แล้ว

      This model is for ~220 Volts, it will not work on 120 volts. If you tried to connect 120V (line & neutral) to any order of RST, it will go up in smoke! You need the model that is made for 120 volts.

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      He's Right, I'm wrong. This model only allows for 170v-240v for 220v power. I could have sworn it allowed for 110v input, but nope.
      Thanks ToolGuy.

  • @gideonopuni964
    @gideonopuni964 8 ปีที่แล้ว

    nice video man. I need a help, did you install any plugin drivers

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Nope. The driver's to run this VFD are built into LinuxCNC.

    • @gideonopuni964
      @gideonopuni964 8 ปีที่แล้ว

      Unfortunately Mach3 doesn't have it. Thanks for the reply

    • @saulm.7100
      @saulm.7100 7 ปีที่แล้ว

      they have drivers for mach3 just search mach3 huanyang plugin

  • @adamgoldberg
    @adamgoldberg 7 ปีที่แล้ว

    Is the manual still available on your Google Drive? The link doesn't really take you anywhere with a PDF easily discovered...

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      Man we keep having trouble with Google Drive. I've moved it to Dropbox, check the new link in the description. The link takes you to a folder with the PDF.

  • @stefanpietzsch8621
    @stefanpietzsch8621 6 ปีที่แล้ว

    great video. I have this same inverter (220V 1~ph in, 220V 3~ph out, ), laying around from another application in the past, but with 3kW rating.
    I now want to use it to drive a 220v 3ph deep well water pump. This pump fills a reservoir and a level switch in this reservoir is turning the pump on and off. Off when it is totally full, and on when the level drops a few feet. So it is basically an ON/OFF operation.
    My question is: where do I connect the level switch to?
    I have the manual, but can not get clear how to connect the on/off level switch to.
    Is it +10V and VI ? Not sure so would appreciate some help with this.

  • @ShahrokhKamyab
    @ShahrokhKamyab 7 ปีที่แล้ว

    Hello and thank you for your video.
    I saw a couple of other videos about this vfd. They had set PD003, 004 and 005 to max (400)
    What do you think ?
    regards
    Shahrokh

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      Frankly I'm not sure why we need these settings at all. I can't say what will happen if you set it to max as I've never tried it. If you're running a high-freq spindle (400hz) then yeah I'd set PD005 at 400. Let me know if you try maxing them out and if you notice anything being affected.

    • @ShahrokhKamyab
      @ShahrokhKamyab 7 ปีที่แล้ว

      Thank you very much for your reply, of course i will.

  • @Th3mast3r69
    @Th3mast3r69 4 ปีที่แล้ว

    Why do you hook up your neutral to the ground on the VFD?

    • @iwens1966
      @iwens1966 4 ปีที่แล้ว +1

      Well, he shouldn’t be. Neutral and ground are not the same. The neutral is the groundED conductor and the green is the groundING conductor. If this VFD is 220v, that neutral doesn’t belong in there.

  • @danieleconty
    @danieleconty 6 ปีที่แล้ว

    really thanks Rus, for you videos and your attention, really appreciate. It is more difficult than i expected, with the help of an eng, i could see that my motherboard use the "phisical com" i mean the real address of a COM for "inner use" so it is too risky triing to use them for something else. One more question, using the HY vfd, i can easily control a three phase usual motor, but it sense too much load for a submersible motor pump. Wich parameter i could try to work on, to set them to "handle" with this type of motor. I know the VFD could do this, because there are a whole series of VFD selled to drive this type of motors. BTW it is just to experience with the VFD , so if you have better things to do, do not worry about it. Again thanks, Daniele

    • @russtuff
      @russtuff  6 ปีที่แล้ว

      +danieleconty I can't find my manual so I'm not sure which setting it is. Have you tried running the pump and the VFD is faulting?

    • @danieleconty
      @danieleconty 6 ปีที่แล้ว

      Thanks, so much Rus, i could not remember just now, what i know: the inverter works fine with standard motors, when i tried it with the submersible type, it acted like if overloaded. SO i think may be it need a "smoother" output voltage.. but not sure on how to do it.

  • @bigcat9139
    @bigcat9139 8 ปีที่แล้ว

    Thank you for posting this. Much clearer and more to the point than other videos I've seen. Not to mention the files you uploaded.
    I have a question: The manual (which as you correctly point out is a bit hard to digest) makes it sound like unplugging or sudden stopping of the flow of power to your device/motor FROM the VFD can damage it. I'm currently using it to power a couple of air compressors, which of course have mechanical relays to maintain a certain pressure. Do you ever use the Huanyang with similar relays/contactors/SSRs? Should I find some kind of work around in order to not damage the VFD?
    One possibility is using the mechanical relay to redirect wall Mains to the control terminals which would then shut off the VFD. But I'm not sure which terminals would work since, as we've said, the manual looks like it was written by a computer.
    Appreciate any additional help you or others can offer, not to mention what you have so far
    Chris

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      I really think the warnings are to keep the device from seeing high inrush current or feedback. I've had a other people say they are running them the way you are and have never had a problem. It may be luck of the draw :/
      I don't have any good ideas on a workaround though. I figure if you haven't burned one up quickly you're probably alright.

  • @lonlygad
    @lonlygad 4 ปีที่แล้ว

    Hello, how can i wire my 1600w 50Hz 220v miter saw in 2.2kw single phase-three phase frequency converter because we use 60Hz in my country and i want to convert the frequency from 60Hz to 50Hz to allow me to use my miter sow safely ? Thank you

    • @russtuff
      @russtuff  4 ปีที่แล้ว

      Many VFDs can be programmed to accept either 60hz or 50hz, but you'd have to go through your manual to find out if it can be done on yours.

  • @chadgdry3938
    @chadgdry3938 8 ปีที่แล้ว

    question: you use Linux CNC but have never used the Mach software. This implies you are good with linux.. not out of the realm of possibilities, is there another reason? Do you think that this is better in some way? is the sampling rate, or the frame rate or something?? I am just looking at these technologies but I don't have the discretionary funds to jump in att. So, why did you pursue this tech tree?

    • @russtuff
      @russtuff  8 ปีที่แล้ว +1

      I've been using LinuxCNC for a few years now. I'm not a developer or programmer, but I've been using it long enought that I'm comfortable with it.
      Frankly, I went with LinuxCNC because it's free, and Mach isn't. I assumed that at some point I would "upgrade" to Mach, but I no longer consider Mach as an upgrade. I know many people using Mach who hate it and want to switch to LinuxCNC. Mach runs on Windows and if you aren't using a SmoothStepper (and even if you are) you may have problems with signals not correctly being sent to your breakout board.
      Linux uses a "real time" kernel which means you don't need a SmothStepper and you get a much more reliable command stream to the breakout board. Also, with a little programming knowledge and a lot of help from the LinuxCNC forum, LinuxCNC is every bit as capable as Mach and is just as easy to use.

    • @gordonfrank
      @gordonfrank 7 ปีที่แล้ว

      I started with Mach3 and went to LinuxCNC and am glad I did. There's a little learning curve but like Russ said there's plenty of forum help.

  • @Tribusion
    @Tribusion 8 ปีที่แล้ว

    hey man, I have a VFD like this for a milling machine (only mine is 1.5kW) do you have anything that could be like a schematic for what wires go where? I didnt understand the video (not your bad, but i suck at english when it comes to electrostuff) so it would be great if you had a link or something
    Beside that, very good video :)

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      I do not know where you can find a schematic, but the manual says what each connection does.

    • @ΧαραλαμποςΠαπαγρηγορακης
      @ΧαραλαμποςΠαπαγρηγορακης 6 ปีที่แล้ว

      Very good video. Is there any way that I can find wiring diagram for inverter SAMCO -Q?I don't have any wiring diagrams for external analog control for example.A three phase motor is connected it's OK But I want to have any wiring diagram or user manual. Thanks

  • @darktermi1993
    @darktermi1993 6 ปีที่แล้ว

    How do i turn off the vfd? Or just pull out the power cord?

    • @russtuff
      @russtuff  6 ปีที่แล้ว

      I have mine wired to a relay and I kill power to the relay to turn it off. I'm not sure if there is a way to turn it all the way off without just cutting power.

  • @beanxlj
    @beanxlj 7 ปีที่แล้ว

    very good tutorial. so no coding needed? no HAL or any edit? just wire it up and everything should work in Linuxcnc? that's pretty magic

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      +xue roger I think there is a call for it in one of the HAL files. I'll take a look and post an update if needed.

    • @beanxlj
      @beanxlj 7 ปีที่แล้ว

      russtuff thanks for reply. I have the added the code. But the hy_comm signal is always false. I've switched couple rs485, but no luck

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      Any more luck?

    • @beanxlj
      @beanxlj 7 ปีที่แล้ว

      russtuff thanks for checking back. it turns out I forgot to set the address, I think it's the 163 needs to be 1. now everything works.

  • @capnhooks1
    @capnhooks1 7 ปีที่แล้ว

    How would you install an external potensiometer what terminals and what parameters thanks

    • @russtuff
      @russtuff  7 ปีที่แล้ว

      Sorry, I'm not sure as I never got to that part. You may be able to find another video online discussing it, or you might have to consult the manual. If you get it working, make a video and let me know!

  • @davidconnerley3846
    @davidconnerley3846 2 ปีที่แล้ว

    What monitor are you using?

  • @henrybartlett1986
    @henrybartlett1986 ปีที่แล้ว

    Nice one.

  • @andywah9413
    @andywah9413 8 ปีที่แล้ว

    Wondering what kind of mother board that is

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Where motherboard?

    • @andywah9413
      @andywah9413 8 ปีที่แล้ว

      breakout board that has parallel port

    • @russtuff
      @russtuff  8 ปีที่แล้ว +1

      andy wah C11 from CNC4PC. I talk about it in some other videos.

  • @ZONAEDINSON
    @ZONAEDINSON 6 ปีที่แล้ว

    amigo usted tiene conctado fase en R y neutro en S

  • @davidsorkin
    @davidsorkin ปีที่แล้ว

    Hit thumbs down by mistake, nice video, thanks

  • @imthexman
    @imthexman 3 ปีที่แล้ว

    Skip to 4:36 to see the actual wiring

  • @browncoconutable
    @browncoconutable 8 ปีที่แล้ว

    the reason 12awg is so commonly used even though it's overkill is for compliance with the national electrical code.

    • @russtuff
      @russtuff  8 ปีที่แล้ว

      Right. I did about 20 versions of this video before settling on this take, and in most of the previous versions I covered national code. In the end, I decided I didn't want to get into it. Thanks for watching.