  • Timecodes
    0:00 - Intro
    1:32 - How to go into programming mode
    3:17 - How to program/add points in the SLC
    7:02 - Point programming
    12:10 - Notifier special function programming
    13:27 - How to program NAC sync/coding options
    17:14 - Setting up an agent release NAC
    19:21 - How to change notifier LED polling speed
    21:12 - How to change the system normal message
    22:38 - How to turn off trouble reminder
    23:30 - How to change addressable protocols
    24:04 - Testing the panel and alarms

ความคิดเห็น • 58

  • @Roxxofoxxo
    @Roxxofoxxo  2 ปีที่แล้ว +2

    0:00 - Intro
    1:32 - How to go into programming mode
    3:17 - How to program/add points in the SLC
    7:02 - Point programming
    12:10 - Notifier special function programming
    13:27 - How to program NAC sync/coding options
    17:14 - Setting up an agent release NAC
    19:21 - How to change notifier LED polling speed
    21:12 - How to change the system normal message
    22:38 - How to turn off trouble reminder
    23:30 - How to change addressable protocols
    24:04 - Testing the panel and alarms

    • @dc5rick
      @dc5rick 16 ชั่วโมงที่ผ่านมา

      @Roxxofoxxo Hey I have this same system but I’m having an issue when my main sprinkler valve is closed I get a trouble but when the valve is close the supervisory light should turn on but it’s not any input would be appreciated thank you.

    • @Roxxofoxxo
      @Roxxofoxxo  16 ชั่วโมงที่ผ่านมา

      I'm assuming you know the monitor module address that is connected to the tamper value. You're using the wrong point type for that device, go into programming mode and change the point type from a trouble to a tamper point type

    • @dc5rick
      @dc5rick 15 ชั่วโมงที่ผ่านมา +1

      @@Roxxofoxxo I do have the address I will look at it tomorrow thank you again.

  • @jorgemm1914
    @jorgemm1914 ปีที่แล้ว +3

    Excelente demostración. Felicidades!

  • @thailander5572
    @thailander5572 หลายเดือนก่อน

    there is some reason we need to shutdown this control box. how do we do it? and how to turn it on again when we want to use it ?

  • @timothyfranche2513
    @timothyfranche2513 2 หลายเดือนก่อน

    I cant seems to get to the " change program " menu, even im using the correct password. It just gets back to the home screen. Sometimes it works but most of the time not. 1:32 .
    I know that its not a wrong password since it doesnt shows error it just simply puts me back to home screen.

  • @arturoibarra6944
    @arturoibarra6944 4 หลายเดือนก่อน

    I have a remote annunciator, and i do not know how to program it, could you help me with that

  • @Omegamoney32
    @Omegamoney32 3 หลายเดือนก่อน

    theres Security LED and try connect home security with panel

  • @MrFido9209
    @MrFido9209 7 หลายเดือนก่อน

    We replaced an existing FSP-851 with the newer FSP-951 detector and base. But the panel showed trouble TEST F. What could be the problem...?

    • @EZBANK4L_
      @EZBANK4L_ 6 หลายเดือนก่อน +1

      You have to use the FSP-951IV if not the it won’t accept the new device. New FSP-951 are flash scan protocol the since you were working on an older system which is set up for clip mode protocol, you would have to use a FSP-951IV which is set for both Flash Scan & Clip Mode Protocol.

    • @MrFido9209
      @MrFido9209 6 หลายเดือนก่อน

      @@EZBANK4L_ Thanks. That's exactly what we had to do to resolve this issue...

  • @SergioLopez-sl6zc
    @SergioLopez-sl6zc ปีที่แล้ว

    I have a smoke detector that failed to recall the elevator. So the recall relay isn’t assigned with the smoke. Is it possible to change that through the panel ?

    • @N9ne20
      @N9ne20 ปีที่แล้ว

      Yes, you’ll need the master password. Go into programming and edit the device, you’ll need to add the zone for recall to that detector.

  • @arturoibarra6944
    @arturoibarra6944 ปีที่แล้ว +2

    But, what if i don't have the password

  • @marxbautista9323
    @marxbautista9323 5 หลายเดือนก่อน

    Is there a default passwork to access Basic Programming?

    • @arturoibarra6944
      @arturoibarra6944 4 หลายเดือนก่อน

      y el admin password is 00000

  • @legrandscanlan6336
    @legrandscanlan6336 ปีที่แล้ว

    I try modifying a detector and it wouldn’t let me. For example I tried modifying a detector the address was 1D001 but instead it took me to the 2 detector which is 1D002 I tried, and tried changing ID001 but it just skips to 1D002. Do I have to run auto program again to modify this point????

    • @Roxxofoxxo
      @Roxxofoxxo  ปีที่แล้ว

      What are you trying to modify detector 1 as, or are you trying to add detector 1 to the panel?

    • @legrandscanlan6336
      @legrandscanlan6336 ปีที่แล้ว

      @@Roxxofoxxo I wanted to label it 1D001 - Admin Board room, and it’s zone but it just skips to 1D002 which I already labelled as Admin Sales

    • @arturoibarra6944
      @arturoibarra6944 4 หลายเดือนก่อน

      to add a new device you need to autoprogram, to erase other you doit in modify point.@@legrandscanlan6336

  • @notifierfan6078
    @notifierfan6078 4 หลายเดือนก่อน

    does the 640 use both the 320 and 2-3030 cpu cause ive seen some with the 3030 cpu and the 320 cpu like this one

    • @Roxxofoxxo
      @Roxxofoxxo  4 หลายเดือนก่อน

      It used a cpu similar to the 320, that is basically identical besides some hardware and firmware differences

    • @notifierfan6078
      @notifierfan6078 4 หลายเดือนก่อน

      @@Roxxofoxxooh

  • @calebmorand4604
    @calebmorand4604 2 ปีที่แล้ว +1

    If cross zones activate, will it cause a pre discharge countdown? Thanks!

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      Yes, I am pretty sure

    • @calebmorand4604
      @calebmorand4604 2 ปีที่แล้ว +1

      @@Roxxofoxxo Cool! Thanks!

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      @@calebmorand4604 np

  • @user-zu2uc1sv9i
    @user-zu2uc1sv9i ปีที่แล้ว

    ¿como habilitar software de una nfs2 640 bloqueada?

  • @sebastiaopereiradacruzjuni5545
    @sebastiaopereiradacruzjuni5545 2 ปีที่แล้ว +1

    is there any way to remove this beep from the fault ?

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      Press the acknowledge button

  • @Experemented
    @Experemented 2 ปีที่แล้ว

    yes I will totally need this for totally legit fire alarm stuff hmmm yes

  • @hsn000hsn2
    @hsn000hsn2 11 หลายเดือนก่อน

    How to activate the smoke detector remotely, through the control panel ?

    • @arturoibarra6944
      @arturoibarra6944 4 หลายเดือนก่อน +1

      no can do, but if you want to make the sirens to go, keep pushing drill botton for 2 seconds

  • @colsonjames-wx5hw
    @colsonjames-wx5hw 2 หลายเดือนก่อน

    nfs 320 next plz

  • @mvsmahesh669
    @mvsmahesh669 8 หลายเดือนก่อน

    How to Change Date and Time

  • @m7md034
    @m7md034 ปีที่แล้ว

    When i press auto programming nothing is happening what to do?

    • @Roxxofoxxo
      @Roxxofoxxo  ปีที่แล้ว

      Do you have devices connected to your SLC?

  • @MantenimientoSalvavidas
    @MantenimientoSalvavidas 2 หลายเดือนก่อน

    I need you help..

  • @calebmorand4604
    @calebmorand4604 2 ปีที่แล้ว

    Can you autoprogram a new device if you already have existing programmed detectors or modules on the slc?

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      Yes
      Just use autoprogram

    • @calebmorand4604
      @calebmorand4604 2 ปีที่แล้ว

      @@Roxxofoxxo awesome! Thanks.

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      Np!

    • @Roxxofoxxo
      @Roxxofoxxo  2 ปีที่แล้ว

      @@calebmorand4604 you plan on getting a Notifier onyx?

    • @calebmorand4604
      @calebmorand4604 2 ปีที่แล้ว

      @@Roxxofoxxo yes I do. They seem very nice. Probably a 320 or 640. Do both program the same?

  • @kwanmo5077
    @kwanmo5077 ปีที่แล้ว

    Can you tell me,how to use CBE

    • @mimi2
      @mimi2 ปีที่แล้ว

      Set the module to the zone you wish to control
      Then a output module or a nac to said zone

  • @uniteddrones7626
    @uniteddrones7626 2 ปีที่แล้ว

    Do you have a template of the word meanings like AHJ codes like that and what they are used for… and please don’t abuse ur panel at 14:48 I almost dropped my dinner 🤣🤣

  • @NoahDoane
    @NoahDoane 2 ปีที่แล้ว

    Notifier simp 😤

  • @stzenterprises6155
    @stzenterprises6155 8 หลายเดือนก่อน

    Tea you are terrible