What would electricity look like without following NEC (National Electrical Code) standards?

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 539

  • @zenronaut
    @zenronaut 4 หลายเดือนก่อน +190

    As a Canadian Electrician, i love the cleanliness of the install and how easy I would be to repair these installs however I can say that the main reason we avoid this method of installation is that each plug and light having its own dedicated path to the circuit breaker panel is extremely expensive.
    The smallest breakers we can use in a residential installation is 15Amps as required by the NEC / CEC as such the wires we pull minimum size must be 14 AWG.
    However this allows us to create MWBC (Multi-Wire branch circuits) or Edison Circuits which massively saves on the required amount of copper.
    Also our building standards are much different, Our high-rise buildings tend to only have concrete walls between units, all interior walls are either wood frame or steel frame which allows us to run wire behind drywall (before its installed) and the ceilings would have a small gap above them for wires and plumbing to be ran before drywall would also be installed.
    Both methods have their reasons for existing and both have their drawbacks.
    All that conduit looks like it takes some time to install + the time to pull each individual circuit where in north America I can wire a small 6 office floor in a few days. but it can be a pain to add or renovate, especially if the client wants to avoid damaging the drywall for new installations.

    • @steveurbach3093
      @steveurbach3093 4 หลายเดือนก่อน +5

      I understand we now can use a 10A breaker (and smaller wire) here in the US.

    • @phuturephunk
      @phuturephunk 4 หลายเดือนก่อน +6

      @@steveurbach3093 It may be allowed (I'm not sure on that) but you wouldn't really want to because with the exception of maybe an isolated circuit that only hanndles LED lighting, it's gonna blow the minute anyone puts any real amps through it. The reason most small appliances in the US cap out at 1800 watts is because that will pull about 12.5 Amps at 120 volts. You try putting a standard 1800 watt microwave on a 10 amp circuit and you're blowing it every time.

    • @PXSHaman
      @PXSHaman 3 หลายเดือนก่อน

      As an American Electrician. None of this shit is allowed. Piss off. Everything this guy does is wrong.

    • @Ale55andr082
      @Ale55andr082 3 หลายเดือนก่อน +4

      "the main reason we avoid this method of installation is that each plug and light having its own dedicated path to the circuit breaker panel is extremely expensive."
      wrong reason...

    • @zenronaut
      @zenronaut 3 หลายเดือนก่อน +1

      Care to elaborate then?
      If each receptical required its own path to the panel, it would be extremely Exspencive.
      To CEC code, a 14AWG wire with a 15A breaker can feed a maximum of 12 recepticals, if I remeber correctly and a 20A circuit with 12 AWG can feed 16.
      If every receptical required it's own feed that's not going to be cheap in material costs. considering most NA houses have 1 circuit Per room feeding both lights and recepticals.

  • @jrbay1
    @jrbay1 3 หลายเดือนก่อน +48

    Master electrician, 40 years, really don’t see anything wrong, work was executed in a workmen like manner, regardless of lack of NEC ; codes & technical specifications worldwide are very similar and based on NEC. Grounding, Wire protection, flame spread, physical protection of conductors, only problem I saw was with damaging that beam.

    • @danngehdochzunetto
      @danngehdochzunetto 3 หลายเดือนก่อน +3

      "codes & technical specifications worldwide ... based on NEC" - No. Not in Europe. Not in Russia. Not in countries that were former colonies of European countries.

    • @xaerothehero
      @xaerothehero 3 หลายเดือนก่อน +1

      "Master" electrician XD There's no such thing

    • @tsfankrk
      @tsfankrk 3 หลายเดือนก่อน

      @@xaerothehero in Poland we have MAASTER ELECTRICIAN

    • @johncford3957
      @johncford3957 2 หลายเดือนก่อน +1

      @@xaerothehero Yes there is here in Canada, in this province they are also able to inspect and pass their work.

  • @ChristianWagner888
    @ChristianWagner888 4 หลายเดือนก่อน +20

    It’s closer to IEC standards, especially the circuit breaker box. Conduit is commonly used in many countries, for example Australia. Less common in Europe due to the additional cost. As long as the wire gauges and circuit breakers are of the correct size, I do not see how the installation in the video would violate the NEC or any IEC based electrical code.
    There are various details that may be required in some countries such as the sizing of junction boxes or exclusive use of UL listed components, but in general this electrician is delivering a system that is commendable and looks safe as well as easy to maintain.

  • @irvingbaptiste2559
    @irvingbaptiste2559 2 หลายเดือนก่อน +4

    I have been an electrician for close to 28 years, different doesn't mean bad, I learned the British system first and now I work at the NEC,
    I worked with the Chinese wiring low-income houses in the Caribbean, in some ways, their system is better, and in other ways, ours is best. it's like comparing apples to oranges. Your conduit work and your panel dressing' ability are simply beautiful & we love it. I love the idea of a separate
    conduit for each fixture, it makes repair and replacement so simple.
    ss

  • @TupahTupah1
    @TupahTupah1 4 หลายเดือนก่อน +63

    As an European Engineer we avoid this because it's cheaper and faster to lay down the cables on a tray

    • @kainvonakenbak7966
      @kainvonakenbak7966 3 หลายเดือนก่อน +7

      And yet we pay infamous prices, noting beats quality ❤

  • @bmanpura
    @bmanpura 4 หลายเดือนก่อน +127

    'without following NEC" Proceed to draw a summoning circle on the ceiling.
    Next video: "Why I got 666 missed calls from NECA."
    Great worksmanship as always! Thanks for the amazing installation work!

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +5

      thanks

    • @walsakaluk1584
      @walsakaluk1584 2 หลายเดือนก่อน +3

      The pentagram was a nice touch.
      Somebody in the CAD department was having fun.

  • @fly4fun24
    @fly4fun24 4 หลายเดือนก่อน +246

    It makes U.S. Electrical Systems look like the 4th world country

    • @Madscientist4567
      @Madscientist4567 4 หลายเดือนก่อน +15

      America as whole😂

    • @ryuukeisscifiproductions1818
      @ryuukeisscifiproductions1818 4 หลายเดือนก่อน +30

      maybe only residential, but Conduit and wire systems like this are used everywhere in US commercial and Industrial spaces. this method is not substantially different from American conduit systems save for the breaker panel, which I gotta say, American breaker panels are better than these.

    • @nhitc6832
      @nhitc6832 4 หลายเดือนก่อน +11

      The see more benefits using the split 240V/120V phase system. But i do agree the U.S residential panels look like a mess.

    • @inkman002
      @inkman002 4 หลายเดือนก่อน +6

      No it doesn't.

    • @shawskeebennett1440
      @shawskeebennett1440 4 หลายเดือนก่อน +16

      @@nhitc6832no they don’t? If following the NEC, they aren’t supposed to look like messes. You guys are nuts to think that US isn’t superior in our codes. Follow the codes properly, not only do you have save, hidden, and more clean looking electrical installations. Not sure what type Electicians you guys are, but I take serious pride in all my jobs and my stuff looks fucking mint.

  • @fmjkevlar
    @fmjkevlar 3 หลายเดือนก่อน +28

    In the UK we use metal containment like basket or tray. The cables are then secured using metal braces if above head.
    The reason:
    A few years back, there was a fire on a construction site. The fireman entered into the building to tackle the fire. It got so Hot that the plastic cable ties (tie wraps) and plastic conduit melted, and the cables fell on to the fireman. He then got tangled up in the copper wires and eventually died from the fire.

    • @johncford3957
      @johncford3957 2 หลายเดือนก่อน

      It was an apartment building, the wires were retrofitted coaxial cable, and you are correct about the outcome.

    • @IIISpeeder
      @IIISpeeder 2 หลายเดือนก่อน +1

      thanks for your advice.. Plastics are easy to mount but sensitive to fire. Always better metal cages or wraps else pvc. I take it account.

    • @defencebangladesh4068
      @defencebangladesh4068 2 หลายเดือนก่อน

      Same.
      We use metal cages here in Bangladesh

    • @riodaser5908
      @riodaser5908 2 หลายเดือนก่อน

      Бедный 😢

    • @zaxmaxlax
      @zaxmaxlax 2 หลายเดือนก่อน

      trays are the standard in europe, its also easier to add new cables or change the layout in the future

  • @strifer43
    @strifer43 5 หลายเดือนก่อน +27

    I enjoy your videos , I might not agree with and like the way a lot of the stuff is done and find some stuff just not practical BUT I do appreciate you showing us the way other countries do electrical .

    • @CIFYou
      @CIFYou  5 หลายเดือนก่อน +1

      Thanks a lot

  • @tamaskovats
    @tamaskovats 4 หลายเดือนก่อน +143

    5:53 - guess the structural engineer agreed to chiseling out the corner of the concrete beam? 🧐

    • @tamaskovats
      @tamaskovats 4 หลายเดือนก่อน

      @user-vf7qq3ie8q haven't been much to constrictions, right? ;)

    • @tamaskovats
      @tamaskovats 4 หลายเดือนก่อน +14

      @user-vf7qq3ie8q at the exact spot, with the needed cut angle… right :)

    • @The.Drunk-Koala
      @The.Drunk-Koala 4 หลายเดือนก่อน +5

      Yeah stuff your stability.

    • @dieselsoggydog6299
      @dieselsoggydog6299 4 หลายเดือนก่อน +14

      What is more concerning is the hole drilled through what looks like a load bearing beam.

    • @UltraFiero
      @UltraFiero 4 หลายเดือนก่อน +2

      Give them some credit, it wasnt just cement spackled over a hay bale this time.

  • @K2teknik.
    @K2teknik. 3 หลายเดือนก่อน +6

    When comparing NEC against a 220/240 Volt system out of the NEC code area it is important to keep in mind the voltage difference. A 120 Volt (NEC) installation will require the dobbed amount of copper to be comparable to a 220/240 Volt system that deliver the same wattage to the end-user, that fact alone makes a NEC installation much more expensive as the 220/240 Volt.

  • @bunky060171
    @bunky060171 3 หลายเดือนก่อน +4

    Most people are not realizing that all of this work will get skim-coated in place by plaster or cement, and will not be visible when completed. Hat tip to this guy for clean workmanship, using the standards that are applicable in his country. (also noted, his knowledge of geometry on the fly to swing a 72° arc to get five evenly spaced pendant light backboxes....r x 1.1754 for those at home) If he was in the States, he would most likely be a licensed electrician, trained to standards that are in effect here. The standards set forth where he is are just as comprehensive, and just as rigorously enforced - if not more so.
    I think it is cool to see how the rest of the world does their wiring practices. There are a lot of aspects here in the States that are way behind the rest of the world (DIN rail and equipment inside residential panels - what the rest of the world calls a 'consumer panel'? yes please.)

  • @johnchristianson515
    @johnchristianson515 4 หลายเดือนก่อน +28

    Very nice work, though NEC guidelines are less for people like this and more for those that do a crappy job.

  • @jayson0024
    @jayson0024 4 หลายเดือนก่อน +11

    The electrical system is installed so artfully; it's beautiful.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      thanks

  • @cabrerabywaters
    @cabrerabywaters 4 หลายเดือนก่อน +19

    After watching this video the tenants understood why all dead spirits appear from the ceiling lights

  • @Arkadiuszczekay
    @Arkadiuszczekay 4 หลายเดือนก่อน +4

    The installation in houses in the Netherlands is similar. The difference is that all pipes are embedded in concrete. Pipes and boxes are placed on special formworks before pouring concrete.

  • @blackdesire2197
    @blackdesire2197 4 หลายเดือนก่อน +38

    Hello, as a German "Elektromeister" , I see many problems here. I don't know if you are familiar with the 'DIN VDE'. It precisely regulates how electrical installations should look and the technical requirements they must meet. I claim that, although we might not build as aesthetically pleasing in Germany, our electrical installations are technically much safer than those here.

    • @maxmustermann9858
      @maxmustermann9858 4 หลายเดือนก่อน +6

      What’s in this case less save compared to a installation according to VDE?
      Would something just like the conduit work be possible in Germany? I thinks it’s a beautiful work and it allows for easy repairs and adjustment compared to putting cables into the wall without conduit.

    • @blackdesire2197
      @blackdesire2197 3 หลายเดือนก่อน

      @@maxmustermann9858 DIN 18015-3 specifies installation zones as an example. This ensures that no cables are accidentally drilled into, as all cables and lines are laid in specified zones. This means that other tradesmen always know where cables are laid and where they are not. This is completely disregarded, for example. Without good documentation, there is a high risk that someone will accidentally drill into a cable at some point.

    • @cal5566
      @cal5566 3 หลายเดือนก่อน +12

      The only real "bad" aspect of this install is jamming loads of cables into one terminal, copper bus bars are much more effective, better connections, faster install time and less space taken up in the enclosure. Bunching lots of small cables in one terminal can lead to uneven tightness in the connection

    • @kitame6991
      @kitame6991 3 หลายเดือนก่อน +3

      @@cal5566 same concerns, is that terminal "12:00" really capable of handling that many cables?
      in my opinion a DIN distribution block would be a perfect addition for this situation.

    • @leverloos
      @leverloos 3 หลายเดือนก่อน +5

      Germany, Where they plaster cables without pipe into walls...

  • @imyournme6632
    @imyournme6632 4 หลายเดือนก่อน +17

    If people talk about something this minute to critique how clean you do it. They have never seen any switchbox out in the field. That simple

  • @orastojames7468
    @orastojames7468 5 หลายเดือนก่อน +12

    As senior electrician in Kenya and east Africa, i recommend this system 🎉 brilliant.

    • @CIFYou
      @CIFYou  5 หลายเดือนก่อน

      thanks

    • @georgendiga
      @georgendiga 4 หลายเดือนก่อน +1

      Thank here in kenya everbody is electrician. They do dirty and dangerous connection

    • @JeffPenaify
      @JeffPenaify 4 หลายเดือนก่อน +2

      @@georgendigawhat do you use for electrical installations in Kenya?

    • @K2teknik.
      @K2teknik. 3 หลายเดือนก่อน

      @@JeffPenaify Let me guess: Whatever you can get your hands on for cheap. Just like many other places in this world.

  • @g6autobot
    @g6autobot 2 หลายเดือนก่อน

    I would hire him for my home in a heartbeat! This installation exceeds NEC standards so in theory it would definitely pass inspection in the US.

  • @Myname64196
    @Myname64196 2 หลายเดือนก่อน +2

    I'm from Russia, and I saw many videos where our electricians love do the same. I think it's redundant work. From an aesthetic point of view, yes, it looks good, from a practical point... all these measures do not so much improve safety as increase the cost

  • @stevenelmore7773
    @stevenelmore7773 4 หลายเดือนก่อน +5

    Degree in electronics and spent 35 years in the field and never heard this before

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +3

      Now you know, congratulations

    • @Chris_at_Home
      @Chris_at_Home 3 หลายเดือนก่อน

      I worked in telecommunications and never saw anything other than metal conduit and boxes used in all our facilities. There are reasons for this.

  • @chrisardern4594
    @chrisardern4594 3 หลายเดือนก่อน

    Excellent workmanship I was just wondering how long a installation like this would take and the cost. Nice bit of over torque with the power driver.

  • @a7md044
    @a7md044 2 หลายเดือนก่อน +2

    5:42
    Why do we, as structural engineers, always say that the concrete cover is so important? Structural bars must always be covered if it is exposed (how is rust produced? Water + oxygen = rust - Because it is exposed, it becomes easier). Thus, the structure has weakened and is unable to perform the function for which it was designed.
    I do not criticize the worker's work, I'm just discussing structurally

    • @A6Legit
      @A6Legit 2 หลายเดือนก่อน

      I think it gets covered with more cement or plaster, would it matter then? If not just applying a sealer to it.

  • @bubaks2
    @bubaks2 4 หลายเดือนก่อน +1

    Please make more in depth electrical installation videos. I wanna see everything. ❤❤

  • @d-bake7726
    @d-bake7726 2 หลายเดือนก่อน

    I'm am American journeyman electrician and that looks great 👍.

  • @samuelwilson5465
    @samuelwilson5465 3 หลายเดือนก่อน

    These guys have pride in their work. Its Amazing

  • @scottpierce3351
    @scottpierce3351 5 หลายเดือนก่อน +11

    There would be no reason to pipe a closed loop for all 5 boxes in the circle. When you go to wire it, one of those conduit chases will be left empty. Looks good like that but not practical. Very nice work

    • @CIFYou
      @CIFYou  5 หลายเดือนก่อน +4

      After making the plaster ceiling, those 5 boxes will have 5 light bulbs.

    • @ericnelson4540
      @ericnelson4540 4 หลายเดือนก่อน +11

      He's just making a demon trap sigil. Sam and Deam would approve.

    • @IIISpeeder
      @IIISpeeder 2 หลายเดือนก่อน +1

      @@ericnelson4540 anastomosis for make easy the wiring? maybe useful but may get a tube unused. But i do the same because here in Peru always we update the wiring setting.

  • @christopherhayden7422
    @christopherhayden7422 4 หลายเดือนก่อน +2

    Very nice work,! Love watching you work your craft!! I just wish the US would adopt the metric system. It would make life a whole lot easier! 🤠

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +1

      thanks, I wish your wish could come true

    • @Sauvenil
      @Sauvenil 3 หลายเดือนก่อน +1

      The measurement system doesn't matter. The measurements aren't any more or less useful in any system. This is a silly comment.

    • @christopherhayden7422
      @christopherhayden7422 3 หลายเดือนก่อน +1

      @@Sauvenil The metric system is ten times faster and easier. It's OK, your not the first apprentice to try to sound like an adult. 😄

    • @Sauvenil
      @Sauvenil 3 หลายเดือนก่อน +1

      @@christopherhayden7422 "ten times faster and easier" is a lie people like to tell. Almost like it's bragging, when it's not actually that way: it ISN'T any faster than imperial, and "easier" you have to prove in every situation to prove it true.
      6 feet is basically 2m, so it's not like you are just working with ones and tens and scaling back and forth, and you still need basic math to do anything human-sized. If someone decided that ~6ft (average sized man) was 1 meter, THEN it would probably be easier. But they had to pick a relatively arbitrary size and call it a meter. (Yes, I know why the meter is the size it is.)
      No, it's usually just a way for arrogant people to attempt to say they're better.

    • @badisbouchama1801
      @badisbouchama1801 3 หลายเดือนก่อน

      ​@@Sauvenil metric is by far easier , stop defending the undefendable.

  • @anthonyrivers8395
    @anthonyrivers8395 4 หลายเดือนก่อน +5

    OSHA’s mind blown😂😂. It all looks great. Live from New York. A lot of Romax used now. Torn down a lot of BX cable throughout the years.

  • @OzonoOzono
    @OzonoOzono 4 หลายเดือนก่อน +7

    4:12 when you trying to make an electrical installation but end up summoning a demon

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +1

      Oh don't think too much, I just need 5 equal points on the circle

    • @IIISpeeder
      @IIISpeeder 2 หลายเดือนก่อน

      @@CIFYou dont worry about the joke. You are a true greek geometry user. Talks very good about your general knowledge. And Taste...

  • @hannessommer9002
    @hannessommer9002 2 หลายเดือนก่อน

    As a German electrician, I see we got different ways to complete the same job and some stuff is the same but your joints for your wires in these wire boxes I don’t like much. We preferred use like wago or something but not because it’s quicker, it’s because the structure of a joint with a springloaded connections that can’t go lose after time as your connections with Zinn and heat. I like to see your work, it’s like meditation to a nice voice. It’s not your voice, I know but it’s nice ☺️👍🏻
    Have a great day and keep your joy up for your work! I like your intention!☺️💪🏻💪🏻

  • @j.r.3215
    @j.r.3215 3 หลายเดือนก่อน +1

    As I recall the poster stated this was an "Emerging Country", (interput this as 3rd world country), so any discussion about not conforming to NEC, EU, Canadian code does NOT apply.
    And making it easier/cheaper for the Contractor does NOT mean it is good/better as code is just doing the bare minimum. I for one don't want "bare minimum" in any of my buildings.

  • @cal5566
    @cal5566 3 หลายเดือนก่อน +1

    Best tip I see here is the bucket for loose cable rolls. Looks very nice but is very space and time inefficient in my opinion.

  • @watomb
    @watomb 4 หลายเดือนก่อน +1

    Coupling between lines can cause a lot of EMI issues. If they start running AFCI breakers they will quickly do it right vs pretty.

  • @Salamander4444
    @Salamander4444 4 หลายเดือนก่อน +2

    as an American electrician everybody saying how neat it all is...don't get me wrong its nice but I'm trying to figure out the breakers/wire color coding(neutrals, hots, grounds, etc.) and how many phases if it even has phases. I loved the video and I'm curious if they get paid by the hour, by the work done and what the scheduling is like cause that's probably time consuming

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +1

      I get paid according to the bidding package.

  • @lusqwerty
    @lusqwerty 3 หลายเดือนก่อน

    If I am not mistaken in the area where we live this kind of PVC is not allowed especially when you exposed the installation. Because PVC are weak against impact. Minimum requirement are IMC not EMT. Also this kind of installation makes the slab or walls become weak. Why not just run a cable tray instead of those long pipes. Cable trays can be more economical as it can fit different sizes of wires.

    • @danimlinsek9891
      @danimlinsek9891 3 หลายเดือนก่อน +1

      U do know dat this will be all cowerd up right.. Plaster, cement or drywall behind witch is filled whit isolation

  • @GothGuy885
    @GothGuy885 4 หลายเดือนก่อน +2

    Tho I am not familiar with the electrical code there, I give him full props for Aesthetics and neatness 😀

  • @violettownmicroenterprises1528
    @violettownmicroenterprises1528 2 หลายเดือนก่อน

    Quality Assurred.
    what a change from 25 years ago !!👍

  • @Bus2000
    @Bus2000 3 หลายเดือนก่อน

    Good te see the US is learning how we do it for years in Europe 👍

  • @stevenschleigh1002
    @stevenschleigh1002 3 หลายเดือนก่อน

    I have a pic on my phone from a house here in Texas in the US..
    All the ceiling lights and wall recepticles were ran off one fuse, all of them were connected together in the ceiling, in a big knot, in the open, not mounted or in a box.. on top of insulation.. with wire cap connections.
    2 bedroom, 1 n 1/2 bathrooms. Laundry room. Living room, kitchen, front porch..
    7 lights.
    4 wall recepticles
    All ran to one spot, and all bound together with wire caps off the breaker line..
    Caps on caps on caps.
    Pairing up n capping em.
    After all connected..
    They folded n balled up the string of wiring..
    And set it on the livin room insulation.
    Its the size of a cantaloupe.
    The best part..
    They installed a plate over the breaker so it wouldnt kick off due to over draw of power.
    It was the metal plating off the back of a desktop computer where your ports stick out the back of the case.
    Screwed to the fuse panel box.
    No wonder it was deemed for demolition
    N yes. In the walls n all after removing the drywall..
    Alot of the wires sheathing had melted off.
    Total fire hazard if the walls would of had any kind of insulation in them..
    I mean still was anyways
    Damn i love America.
    Hahahahaha

  • @miguelnavarro3830
    @miguelnavarro3830 3 หลายเดือนก่อน

    Hello there. I just to tell you that I admire your work. It is like art...!!

  • @edc1569
    @edc1569 3 หลายเดือนก่อน

    Worried about the amount of building that's been removed, is that ok? In the UK we run rings and radials, it's much cheaper. I guess its easier to replace a cable here, but with modern techniques and PVC cables that last forever, not sure you'll have get enough maintenance benefit, just the shear amount of conduit increases your risk of a fixing damaging a cable.

  • @marshallb5210
    @marshallb5210 4 หลายเดือนก่อน +7

    4:55 never leave your safety squints at home guys!

  • @CP-gz6lx
    @CP-gz6lx 3 หลายเดือนก่อน

    wow I've never seen such a clean electrical installation !!!

  • @chickencurry7642
    @chickencurry7642 4 หลายเดือนก่อน +8

    US isnt world's centre. Every country has its own standards for all kinds of things, electrical wiring included. US has a grid-to-resident supply of 110v. Some countries have 220v. Also, I see that power sockets in US households don't have a dedicated switch beside them. I personally find that to be dangerous, especially because whenever you plug in something that draws a lot of electricity (like a toaster, heat gun, refrigerator etc...), it sparks when you plug them in. I get that you have breakers as a safety measure but as someone who grew up in a country where we have dedicated switches next to each power outlet, I find this to be much safer and reassuring.

    • @cheereebus
      @cheereebus 4 หลายเดือนก่อน +2

      US has grid-to resident supply of 240v with a split phase neutral used to provide two legs of 120v for common outlets and fixtures while maintaining 240v to higher-demand items like stoves.

  • @johnravenengalan5492
    @johnravenengalan5492 4 หลายเดือนก่อน +4

    Ny boss would agree with this work. It’s very clean. Can I ask since it is not using NEC, are they using IEC standards?

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +4

      Oh, it is following IEC standard

    • @K2teknik.
      @K2teknik. 3 หลายเดือนก่อน +1

      @@CIFYou Then you can tell us which IEC standards that was in play here, there is a lot of them and they are in many sub variants, not all places use the newest variant (they do not have to), now and then these sub variants differ a lot, some are a total rewriting others are just a small adjustment here and there. Local code determinate what IEC to follow and what sub variant to use too.

    • @vxart
      @vxart 3 หลายเดือนก่อน +1

      ​@@K2teknik.In that case, you may refer to specific regulation. To tell everything here, akin to opening a textbook and throw everything here.
      You shall guess what country based on the color code of the wire.
      If not, even we tell everything on the regulations, here..... Its useless, pointless and idiotic.

  • @treffle17
    @treffle17 3 หลายเดือนก่อน

    I just love how clean this is

  • @paullangford8179
    @paullangford8179 3 หลายเดือนก่อน

    It's very simple: after a couple years of use, count the number of "crispy critters". If it remains at zero, then the installation is safe.

  • @heronb2
    @heronb2 3 หลายเดือนก่อน

    Hi I am in Canada and i have so much admiration for your work just want to know in which country are you?

  • @moe85moe85
    @moe85moe85 4 หลายเดือนก่อน +4

    whatever about the NEC guidelines - did they just break out a chunk of the concrete to radius the tubing ?

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +1

      maybe

  • @satyam1529
    @satyam1529 4 หลายเดือนก่อน

    Very systematically arranged & wiring done😊😊😊😊

  • @ryuukeisscifiproductions1818
    @ryuukeisscifiproductions1818 4 หลายเดือนก่อน +5

    as far as running conduit, no this is not substantially different from the US. The materials and exact specifications might differ slightly, but as far as running wire in conduit, its basically the same any US installation which uses conduit.
    The only real point of difference is the breaker box, which i have to say, American breaker boxes are much better than that style of box, far easier and less labor intensive to install, since American breaker panels use bussbars to supply all the breakers, this makes it more flexible and safer.
    Now dont get me wrong, I'm not saying the American system is better in every way, our system does have its problems in other area's, but as far as breaker panels go, American ones (this includes canada and mexico), are better that other standards.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +4

      I understand, thank you for giving me more knowledge. Actually in America the quality is much better. I'm sure about that. I looked into NEC. It is very good and safe for users

    • @steveurbach3093
      @steveurbach3093 4 หลายเดือนก่อน +1

      I think the UK buss to branch system beat those wires (the breakers are similar. Both beat the US residential as the Mains side is bolted.

    • @phuturephunk
      @phuturephunk 4 หลายเดือนก่อน

      They do make DIN bussbars that can simply a lot of what you see in the video, gotta pay more though. We just never really adopted DIN specifications for power distribution in the US. Honestly, I kind of like DIN compared to standard breakers in the US, for the modularity. You can build a box to basically any size for a set of rails.

  • @HighVoltageNL
    @HighVoltageNL หลายเดือนก่อน

    In Europe we have different standards, but it looks good, seems well done.

  • @colinturner7363
    @colinturner7363 3 หลายเดือนก่อน

    that looked absolutely superb installation wise.

    • @K2teknik.
      @K2teknik. 3 หลายเดือนก่อน

      Yes, it looks nice, but is it up to the local electrical code? Well, we do not know, many kinds of info is missing before a judgement can be made.

  • @geoffreygraham290
    @geoffreygraham290 4 หลายเดือนก่อน +1

    Don't really see any violations. Maybe more than 360° on conduit runs. I do alot of this same type on installs in motor control cabinets using tray cable. The 2" hole in the j-box was concerning.

  • @Scout-ew7wb
    @Scout-ew7wb 3 หลายเดือนก่อน

    Lovely Work. Hats Off To The Guy ❤

    • @CIFYou
      @CIFYou  3 หลายเดือนก่อน

      thanks

  • @ketanpadal9833
    @ketanpadal9833 4 หลายเดือนก่อน +5

    Can you tell me how you make your wire so perfectly straight like a straight line?

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +2

      A laser ruler will do that and especially follow the drawings

    • @ketanpadal9833
      @ketanpadal9833 4 หลายเดือนก่อน +1

      @user-vf7qq3ie8q makes sense, the wires that I use are usually all wiggly and wobbly they never fully become straight like that

    • @braindecay9477
      @braindecay9477 4 หลายเดือนก่อน

      ​@@ketanpadal9833you have to pull it through something like a tight handgrip, a small pipe,...that straightens the wire out - every electrician should know that trick, works very well

    • @NileshKumar-uf4vh
      @NileshKumar-uf4vh 4 หลายเดือนก่อน +2

      ​@@ketanpadal9833thick stranded wires will behave differntly difficult to pull also.
      Everyone uses multiple thin stranded wires except few countries.

    • @IIISpeeder
      @IIISpeeder 2 หลายเดือนก่อน

      They use a curved tube to get straight the wire. look at minute 6:32

  • @lmaopew
    @lmaopew 4 หลายเดือนก่อน

    I'm no american, idk how the nec works, but i do prefer your way of doing it, it all looks so neat and like it needs to be that way, nothings out of place, everything is as it should. I would trust this more

  • @dapperdave2090
    @dapperdave2090 หลายเดือนก่อน

    I must have missed it... but where are we at??? .... and is this plastic pipe the same as PEX-B??? what does the finished walls, ceilings and floors look like???

  • @BACKFIREFUR
    @BACKFIREFUR 3 หลายเดือนก่อน

    This is exactly how i would do my house. I also love the industrial look of it. I would leave all the tubing exposed. But that's just me.

  • @Yomvzzy
    @Yomvzzy 3 หลายเดือนก่อน +1

    Thanks for turning the crib to a supernatural charging station

  • @paulsharpe3794
    @paulsharpe3794 3 หลายเดือนก่อน

    Hi there I'm in the UK and I think that this may be one of the best installations I've seen

    • @CIFYou
      @CIFYou  3 หลายเดือนก่อน

      thanks

  • @donmiller504
    @donmiller504 3 หลายเดือนก่อน

    I thought PVC was too flammable to use in conduit? at ~6:00 they ate a whole lot of the Primary concrete joins support to curve those conduit traces through. hope that's not load baring. This stuff looks great, very aesthetically pleasing.

    • @CIFYou
      @CIFYou  3 หลายเดือนก่อน

      thanks

  • @mansouralblooshi3004
    @mansouralblooshi3004 2 หลายเดือนก่อน

    Excellent work as usual. keep it going

  • @ViniciusGrandoVieira
    @ViniciusGrandoVieira 4 หลายเดือนก่อน +1

    Incredible, where are you from? I would like to know the name os this PVC system that you use.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +1

      I come from Vietnam, it is a type of fireproof pvc-u. This is just the wiring for an ordinary apartment

  • @tunapig
    @tunapig 4 หลายเดือนก่อน

    a man after my own heart. Speaking as a general contractor.
    I see that he installed the demon summoning portal on the ceiling. That's a new one on me but I'm sure it's the standard in his country.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      Oh don't think too much, I just need 5 equal points on the circle

  • @JeraldDalnay
    @JeraldDalnay 4 หลายเดือนก่อน +1

    can you please tell me what PVC type you installed? it's seem like very easy to use and very easy to bend unlike the other PVC pipe...I like your job very neat...

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +3

      it is a kind of thin pvc, it is very popular. When bending, there should be a spring inside to avoid bending the tube.

    • @JeraldDalnay
      @JeraldDalnay 4 หลายเดือนก่อน

      @@CIFYou can you please tell me what exactly the name of that pipe...or may I request if is it okay if your next content in your TH-cam please mention in your vlog, what are the name of the tools you use.. please...thank you

    • @SirrPiper
      @SirrPiper 4 หลายเดือนก่อน +1

      You can bend regular pvc like that, look for that spring to bend pvc and you’ll be fine!

    • @kathrynwhitby9799
      @kathrynwhitby9799 4 หลายเดือนก่อน +1

      @@JeraldDalnay look for 'plastic conduit'. It has a different wall thickness to plastic plumbing pipes.
      In the UK it comes in 20 & 25 mm diameters.

  • @themetalfusionologist
    @themetalfusionologist 4 หลายเดือนก่อน +3

    Is that PEX pipe you are using for conduit?
    Being in the U.S., we aren’t allowed to use it of course, but I like how clean you made it look

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน +2

      It is completely different from pex pipe, it is a type of PVC produced to make electrical conduits

    • @dieselsoggydog6299
      @dieselsoggydog6299 4 หลายเดือนก่อน

      @@CIFYou What is the fire rating for that PVC?

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      it does not catch fire.

    • @dieselsoggydog6299
      @dieselsoggydog6299 4 หลายเดือนก่อน +3

      @@CIFYou The high chlorine content of PVC-U causes an advantageous combustion behaviour. Self-ignition resulting from temperature influences occurs only at 450 °C. PVC-U burns when exposed to an open flame, but extinguishes immediately after removing the flame. The oxygen index amounts to 42 %. (Materials that burn with less than 21 % of oxygen in the air are considered to be flammable). PVC-U thus falls in the best flammability class V0 according to UL94, and in the B1 building material class

    • @OspreyKnight
      @OspreyKnight 4 หลายเดือนก่อน

      We have similar types of conduit, its just not common.

  • @nischaltam
    @nischaltam 2 หลายเดือนก่อน

    My only problem is that he break the supporting beam on the ceiling compromising the structural integrity

  • @pohbenson4070
    @pohbenson4070 3 หลายเดือนก่อน

    1 drunking or cable tray can carry all cable, make all's in center can save to avoid disturbing others architectures or equipment's installation space....
    I wondering after they put that's many of conduit's on ceiling, how's the plaster ceiling support get space to install.....
    This kind of installation will make trouble with others specific contractor's super headache and hard to install their things....
    or maybe the whole renovation everyone just corporate to priority and suit for electrical installation works, even no need to install furniture or ceiling?

  • @2loco
    @2loco 3 หลายเดือนก่อน

    Beautiful work brother.

  • @kukumbagumba2264
    @kukumbagumba2264 3 หลายเดือนก่อน +2

    Now I’m mad my house doesn’t have electrical installation like this

  • @asymptoticsingularity9281
    @asymptoticsingularity9281 3 หลายเดือนก่อน

    Love it when money forces changes to the code. AFCI for example.

  • @ХүрэлхуягМ
    @ХүрэлхуягМ หลายเดือนก่อน

    You said those pipes are pvc. Do you know ppr can bend like that?

  • @kurtwm2010
    @kurtwm2010 หลายเดือนก่อน

    You should look at my fuse box. Makes me wonder if we have any standards in the USA.

  • @FarhanElectrcian2829DGK
    @FarhanElectrcian2829DGK หลายเดือนก่อน

    As an electrician i don't see this work in my country but this work is easy for me 😅

  • @carlossilva3122
    @carlossilva3122 หลายเดือนก่อน

    What's that machine he's using to secure the fittings? Is that some sort of nail gun?

  • @dantruong2582
    @dantruong2582 4 หลายเดือนก่อน +3

    I think we can do this in N.America to NEC code. It just, who wanna spend that much money, for something you look at once and seal behind a wall.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      Oh, I think American standards are better

    • @braindecay9477
      @braindecay9477 4 หลายเดือนก่อน +5

      It makes it so much easier when you have to change anything afterwards - new internet cables, a new outlet,...it absolutely sucks to work with a messy, disorganized electrical installation

    • @kathrynwhitby9799
      @kathrynwhitby9799 4 หลายเดือนก่อน

      @@braindecay9477 yep. i'm looking at having to rearrange all my wiring in the attic (1st floor apartment) that was installed in the 60s (UK resident) prior to having a consumer unit upgrade.

    • @miyamotomusashi7612
      @miyamotomusashi7612 4 หลายเดือนก่อน

      The MC menace and it's consequences lol.​@@braindecay9477

    • @OspreyKnight
      @OspreyKnight 4 หลายเดือนก่อน

      Brutalism is always an option.

  • @SMARTCAMERA-nh6ex
    @SMARTCAMERA-nh6ex 9 วันที่ผ่านมา +1

    Full super ❤

  • @IIISpeeder
    @IIISpeeder 2 หลายเดือนก่อน

    Its Art, Its easy to mount.. but the true work its the tracing. In the breaker box, i choose the bus contact else to work the wires,. these pvc tubes are better quality than Peru. I m impressed with the breaker switchs they are very compact because only takes a unique slot. Here takes two slots. But, i dont like the beam damage..

  • @joewebb4836
    @joewebb4836 หลายเดือนก่อน +1

    When all that pvc pipe burns, every one will die from the smoke.

    • @darkslidesk8t3r
      @darkslidesk8t3r หลายเดือนก่อน

      Try replacing the words "pvc pipe" with other terms and see if that brings a different outcome. Try "furniture", "clothing", "electronics", it seems to work in the sentence, no? :D
      Jokes aside, pvc conduits are usually flame retardant, meaning they won't keep burning and self-extinguish, shrinking in attempt to protect the wires. As opposed to nearly all other household items.

  • @destinywhitehouse8247
    @destinywhitehouse8247 2 หลายเดือนก่อน

    What pipe grade are you using

  • @localdeer1171
    @localdeer1171 4 หลายเดือนก่อน +3

    What is this system called and what country is it used in?

    • @braindecay9477
      @braindecay9477 4 หลายเดือนก่อน +4

      It's Vietnam - they mentioned the currency they use in one Video

  • @drumboy256
    @drumboy256 3 หลายเดือนก่อน +1

    “While we don’t recommend smoking, using a lighter could be beneficial to your install…..”

  • @t23001
    @t23001 4 หลายเดือนก่อน

    Very neat and artistic. This method is not more efficient or better than North American systems for installation time, the amount or the amount of materials used, or safety.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      You're right, it's not too strict compared to North America

  • @johnnelstevemanalon3335
    @johnnelstevemanalon3335 3 วันที่ผ่านมา

    00:07 I don't know if that has been coordinated with the Structural Engineer of this Building.

  • @rinzler9775
    @rinzler9775 3 หลายเดือนก่อน

    Looks pretty, but the extra expense may outweigh the benefits.

  • @vahidashaikh8435
    @vahidashaikh8435 3 หลายเดือนก่อน

    This work is too perfect

  • @garcjr
    @garcjr 4 หลายเดือนก่อน

    As long as you're not overloading circuits and using the appropriate gauge wire, I don't see how this is a problem. This is OCD electrical and there ain't nothing wrong with that.

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      thanks

  • @gooldscross8702
    @gooldscross8702 3 หลายเดือนก่อน

    Not too keen on phase colours L2 and L3 Green and Yellow 😦in the consumer unit as the earth/ground is these 2 combined.

  • @boaragile82
    @boaragile82 4 หลายเดือนก่อน

    Looks great. I cringed when lighter was applied to HS tube close to other wires.

  • @dekingcharles5222
    @dekingcharles5222 3 หลายเดือนก่อน

    This is good but the control box is not the same in Nigeria. Anyway his work is great.

  • @cristinelcostachescu9585
    @cristinelcostachescu9585 หลายเดือนก่อน

    You NEVER disconnect the ground!! The ground wires should be connected at all times, and should NOT be interrupted by a breaker!
    Also, never tie multiple wires to the same connection, one gets loose and you now have a fire hazard waiting to happen. And so many more issues...
    The whole conduit thing looks neat and feeds my OCD, but why did you have to screw up everything at the panel connections...

  • @andrewwatts3083
    @andrewwatts3083 3 หลายเดือนก่อน

    Why use conduit if the wire is already mechanically protected and double insulated ?

    • @danimlinsek9891
      @danimlinsek9891 3 หลายเดือนก่อน

      Pour concreat ower it and u will se why+ if u decide i want somenthing added a can alweys pull more wires fthrew.. Insted of owerloading 1 cable

  • @mindaugasv85
    @mindaugasv85 4 หลายเดือนก่อน +1

    Wow man! You made this with these primitive tools. Amazing 😉 p.s. why all red this time (L1/L2/L3)?

    • @CIFYou
      @CIFYou  4 หลายเดือนก่อน

      Each of these red conduits will carry 3 wires, 1 hot wire, 1 neutral wire and a ground wire.

  • @sendiulo
    @sendiulo 2 หลายเดือนก่อน

    Ah, the safety sqint. Love it. 😍

  • @agresywnakaczka3885
    @agresywnakaczka3885 4 หลายเดือนก่อน +9

    bro this electrical installation is expensive asf

    • @NileshKumar-uf4vh
      @NileshKumar-uf4vh 4 หลายเดือนก่อน

      No. It's standard.

    • @agresywnakaczka3885
      @agresywnakaczka3885 4 หลายเดือนก่อน

      @@NileshKumar-uf4vh nuh uh
      definitely not in my country

    • @NileshKumar-uf4vh
      @NileshKumar-uf4vh 4 หลายเดือนก่อน

      @@agresywnakaczka3885 what I meant is labor is cheap and quality of install and work is better. Hence standard . Standard doesn't mean madeup govt shit where I'm from.

    • @agresywnakaczka3885
      @agresywnakaczka3885 4 หลายเดือนก่อน

      @@NileshKumar-uf4vh You clearly have no idea what you're talking about.
      How is it supposed to be cheap and better to make a separate line for every damn receiver?
      it will take several times longer, and be several times more expensive. Not cheaper.

    • @NileshKumar-uf4vh
      @NileshKumar-uf4vh 4 หลายเดือนก่อน

      @@agresywnakaczka3885 every country isnt same. Some countries still have reasonable prices for everything. It doesn't take longer or much more money as conduits are cheap and labour is cheap. If I have things done like this now in initial stage cost will not be an issue as most people charge less for bulk initial work and I can have as many outlets possible. No need of extension cords etc ever.

  • @setsunaes
    @setsunaes 3 หลายเดือนก่อน +2

    4:40 years later the owners will not understand why the hell many demons, ghosts and even freaking Satan are all the time appearing in their department.

  • @SiliconPower74
    @SiliconPower74 2 หลายเดือนก่อน

    I dont like to trim or chop parts of a concrete beam to route conduit. it feels wrong