Compressor Replacement! Using Triple Vacuum Evacuation!

แชร์
ฝัง
  • เผยแพร่เมื่อ 12 พ.ค. 2023
  • In this video we remove a compressor that Burnt Out and blew a pin. Install a new compressor, and pull a triple Vacuum!
    Like and Subscribe
    email me
    jeffshvacadventures@gmail.com

ความคิดเห็น • 52

  • @JeffsHVACAdventures
    @JeffsHVACAdventures  ปีที่แล้ว +9

    So the more I thought about this one the more I’m thinking there is an issue with the TXV staying open too far. Usually a non adjustable TXV has a Minimum Superheat setting which keeps the superheat positive. I am getting a 0 superheat. Even after I put the bulb in 32° water, I only got about 8° of super heat. The TXV should have closed a lot more than that in freezing water. I am following up in a couple weeks to replace the filter drier (standard practice after a burnout) and I will bring a TXV with me when I go back.
    Jeff

  • @matth.4932
    @matth.4932 5 วันที่ผ่านมา

    Best how to video of unbrazing! You earned my subscribe! Was nice of you to clear the leaves out for home owner.

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  4 วันที่ผ่านมา

      Appreciate that. I did get most of the leaves out of the base pan.

  • @jrh86
    @jrh86 ปีที่แล้ว +2

    Brilliant job👍👍👍

  • @Aviation2016
    @Aviation2016 ปีที่แล้ว +1

    I subbed. Im in school to become a tech and that was a very good video of a triple evacuation. Im always looking to do things the best I can when I work. Thank you for the video, I saved it to look back on.

  • @dfwhvac
    @dfwhvac ปีที่แล้ว +2

    Yellow jacket makes a vacuum rated stubby hose . I use it to attach my micron gauge and then close the ball valve on the hose when I’m ready to charge so oil never hits the sensor

  • @SupremeRuleroftheWorld
    @SupremeRuleroftheWorld ปีที่แล้ว +2

    the TXV is probably borked from the junk that came from the old compressor. it should always be replaced after a violent compressor death. dont forget any check valves and/or the 4 way valve! and ensure its running proper in both modes. its really sucks if you have to replace those...

  • @dfwhvac
    @dfwhvac ปีที่แล้ว +1

    And I believe your pinned comment is correct , I bet the txv is most definitely over feeding . That sucks because those type of things there’s really no way to know that until you get the system back up and running . A lot of guys at my company when compressors fail are starting to always add TXVs to the repair quotes just to cover the ass and I’m probably going to start doing the same thing , within reason of course

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +2

      Yea it certainly does suck having to go back to the customer with the news but usually they understand in the long run.

  • @jenniferm5375
    @jenniferm5375 ปีที่แล้ว

    Jeff, a couple of weeks ago we had the exact same problem compressor making weird noises at starting, well same thing low super heat and sub cooling wouldn't rise, replaced txv and compressor and what a difference, su cooling went up and super heat is at where it should be

  • @chrissipple1018
    @chrissipple1018 ปีที่แล้ว +2

    That little of missing insulation will not hurt anything, it just looks a lot cleaner.

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +1

      Yup. I didn’t have any to put back anyway. 😂🤙

  • @alross18058
    @alross18058 ปีที่แล้ว +2

    I used to always put in a suction filter after a burnout

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว

      I considered that but where the acid test came negative I decided against it.

  • @97Napkins
    @97Napkins ปีที่แล้ว

    close suction isolation valve and no leak from compressor

  • @VinceCuzmono
    @VinceCuzmono ปีที่แล้ว +2

    Outstanding!!! Love the bulb test. Does no super heat mean you have liquid going back to compressor?
    Yeah something is up, maybe that 5/16 is kinked somewhere or the meter device on the outdoor unit is gunked up. 🤔

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +1

      Yea no super heat means liquid is coming back. I’m going to follow up in a couple weeks to change the filter drier anyway. (Usually always do that after a burnout.) And I might pull the outdoor piston and clean and also maybe check that indoor TXV again. It was working but i have a suspicion it might not be working properly.

    • @frankduarte7109
      @frankduarte7109 17 วันที่ผ่านมา

      When you go back to change the txv and drier will you use the same refrigerant? Or do you have to go back in with virgin after a burnout

  • @jamestoy426
    @jamestoy426 ปีที่แล้ว

    What did take out the compressor? I think I would go back and change the liquid line out because there was not enough discharge. to get rid of the heat and I think the compressor overheated. I also agree with Jon Hvac I would also change the TXv would not be a bad idea

  • @oscarguzman9669
    @oscarguzman9669 8 หลายเดือนก่อน

    dode it was gray , just miss one think every time you change an compressor change the tsv

  • @samersarah957
    @samersarah957 2 วันที่ผ่านมา

    Nice job bro what size of tip use for compressor lines and how to set torch I mean how many pressure for acetylene and oxygen? Thank you

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  2 วันที่ผ่านมา

      I’m not exactly sure what size the tip I use is but I set my pressures at 7 acetylene and 14 oxygen. Some guys due 10-20 but I’m good at 7-14.

  • @jonhvac
    @jonhvac ปีที่แล้ว +3

    I'd change the TXV

  • @richlikeg3722
    @richlikeg3722 ปีที่แล้ว

    What tip did you use on your torch? You were able to heat it up fast. Does breaking vacuum hurt the micron gauge?

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +1

      Just a standard tip. No, the micron gauge can handle a little pressure.

  • @joselanda8316
    @joselanda8316 ปีที่แล้ว

    That txv over feeding is probably what killed the compressor in the first place...

  • @dipley3771
    @dipley3771 ปีที่แล้ว

    Maybe airflow, also don’t see how adding that extra refrigerant would cause it to start flooding back again. Did you let it run 15 minutes after that?

  • @xelaju8
    @xelaju8 ปีที่แล้ว

    What kind of brazing rod did you use for the compressor? silfos15?

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +2

      Harris Stay-Silv 15. 15% silver 80% copper 5% phosphorus

  • @stevebates6281
    @stevebates6281 ปีที่แล้ว

    Hi. I need to replace a Mitsubishi compressor. Will map pro gas get hot enough to separate the lines from the compressor? Are you using oxy acetylene?

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว

      I don’t think Map gas will get it hot enough. And if it does it will take a really long time. Your gonna need Oxy acetylene (recommended) or turbo torch.

  • @sheldon8115
    @sheldon8115 ปีที่แล้ว +1

    I don’t think it’s the size of the discharge line because your head pressure was normal. I think Txv

  • @Kilcrops0914
    @Kilcrops0914 ปีที่แล้ว +1

    At least now you know what killed that compressor

  • @glennsepelak5113
    @glennsepelak5113 ปีที่แล้ว +1

    Copeland wants stubs on compressor, Do Not beat it shut.

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว +1

      Didn’t know that. Been beating them shut for 20 years. Thanks for the advice.

  • @lunytoo
    @lunytoo 11 หลายเดือนก่อน

    Hi Jeff I’m curious you could have quoted a new condenser right?

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  11 หลายเดือนก่อน

      This one is going back a ways but I’m thinking this compressor was under warranty.

  • @applianceman6009
    @applianceman6009 ปีที่แล้ว

    Glad that’s a Copeland. I am not a fan of LG.

  • @timrob0420
    @timrob0420 ปีที่แล้ว

    Don’t those tests say must be running compressor and take sample of vapor refrigerant??

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  ปีที่แล้ว

      Ideally yes. But where this compressor was bad and blew a pin, I had no choice.

  • @bigdaddy4975
    @bigdaddy4975 ปีที่แล้ว

    Running no superheat is really bad for the compressor no wonder it burned up.

  • @osvaldomcs1213
    @osvaldomcs1213 6 วันที่ผ่านมา

    Never charge on the low side. Liquid in the compressor.

    • @JeffsHVACAdventures
      @JeffsHVACAdventures  6 วันที่ผ่านมา +1

      That's the only way you can charge when topping a system off. A heat pump has a suction accumulater which protects the compressor. I agree you don't want to slug a compressor with liquid while it's running but charging with liquid slowly through your suction side is the only option most times on AC systems.

  • @osvaldomcs1213
    @osvaldomcs1213 6 วันที่ผ่านมา

    You just killed the new compressor