RSLOGIX5000 CompactLogix MSG to RSLOGIX500 MicroLogix1400 Ethernet Comm

แชร์
ฝัง
  • เผยแพร่เมื่อ 7 ธ.ค. 2020
  • If this video is helpful, please like, share and subscribe to my channel! Thank you.
    MSG on CompactLogix (1769-L33ER) to read/write data to MicroLogix1400 (1766-AWA)
    1. Message Type: SLC Typed Read
    2. Message Type: SLC Typed Write

ความคิดเห็น • 12

  • @AkashSharma-rn4hn
    @AkashSharma-rn4hn 3 ปีที่แล้ว

    Thanks for detail teaching.You got a new subscriber mate 🙌

    • @SYPHOANG
      @SYPHOANG  3 ปีที่แล้ว

      Akash Sharma: Thanks for the sub! Should you have any questions, just let me know.

  • @tanachaiphoset3451
    @tanachaiphoset3451 3 ปีที่แล้ว

    Thank . Best for detail !.

    • @SYPHOANG
      @SYPHOANG  3 ปีที่แล้ว +1

      @Tanachai Phoset: Thank you for subscribing to my channel. Are you still working today? Merry Christmas to you and your family. Should you have any questions, just let me know.

    • @tanachaiphoset3451
      @tanachaiphoset3451 3 ปีที่แล้ว

      @@SYPHOANG Thank for support and teac me. If me have questions please clearly .Thank.

  • @jsdtshenchangguo
    @jsdtshenchangguo 6 หลายเดือนก่อน

    6:45 & 9:53 After apply the communication path on RsLogix5000 (2 comma space IP Add of ML14), it occurs a “Error Path”. So, how it works after? Everytime when I run programme under this case, there will always be an error om the MSG structure......

    • @SYPHOANG
      @SYPHOANG  6 หลายเดือนก่อน

      @jsdtshenchangguo: Make sure both controllers are on the same network and have the same subnet mask.

    • @jsdtshenchangguo
      @jsdtshenchangguo 6 หลายเดือนก่อน

      Thanks for your reply. I later succeeded by creating MSG on MLX1400's side (Rslogix500), and setting the PLC/SLC mapping on Compactlogix's side (Rslogix 5000). But I do tried many times before, created MSG on Rslogix 5000, always have the problem of "Error Path". I noticed that in your video there is the same "Error Path". So, I asked the question.@@SYPHOANG

  • @ajithkumarelumalai5349
    @ajithkumarelumalai5349 ปีที่แล้ว

    Can i connect different models in ab micrologix and compact plc

    • @SYPHOANG
      @SYPHOANG  ปีที่แล้ว

      @Ajithkumar Elumalai: I am not sure what you meant? IO modules or?

    • @ajithkumarelumalai5349
      @ajithkumarelumalai5349 ปีที่แล้ว

      @@SYPHOANG no. you have done this with l32ER Cpu .But I have l32E cpu ,can I do this same on this model

    • @SYPHOANG
      @SYPHOANG  ปีที่แล้ว +1

      @@ajithkumarelumalai5349 Yes, you surely can. It is the same procedure. Thank you for your support and subscribing to my channel.