Programming my VFD to drive the single phase 120V PSC motor

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ส.ค. 2024
  • Programming the single phase 110V input - 3 phase 110V output VFD to run with the 120V Permanent Split Capcitor (PSC) motor on my King Low speed (1750 rpm) bench grinder
    Motor is King Canada KC-895LS 8" Low Speed Bench Grinder 120V, 3A, 1750RPM
    VFD model is H100-2.2C2-1B
    Input: 110V 50/60Hz
    Output: 0-110V 12.5A 0-1000Hz
    Parameters what I am using, not validated as functionally correct.
    F003 main freq = 60hz
    F004 ref freq = 60hz
    F005 max freq = 100hz for 1750rpm unit 60 for 3600rpm unit
    F007 min freq = 10 hz
    F008 Max Voltage = 120V
    F026 stop mode = 0
    F028 stop freq = 0.5 hz
    F030 stop braking time = 0.0s
    F031 DC braking level = 2.0 (dont care as long as F30 = 0.0)
    F039 start freq for braking = 4.0 (dont care as long as F30 = 0.0)
    F141 motor rated voltage = 120V
    F142 motor rated current = 3.0 (use according to motor)
    F143 number of motor poles = 02
    F170 selection of display 1 = 2 (for RPM)
    F184 RPM display factor = 0.5 (for 1750, use 1.0 if motor is 3600)
    F193 output open phase = 0
    F194 0hz output enabled = 0

ความคิดเห็น • 12

  • @joe-tech
    @joe-tech ปีที่แล้ว

    Thank you for the help

  • @claudiogarrido2270
    @claudiogarrido2270 11 หลายเดือนก่อน

    Hola, muchas gracias por compartir, quisiera me pudieras decir como cambiar el sentido de giro del motor?. Muchas gracias

    • @prairieedgeservice
      @prairieedgeservice  11 หลายเดือนก่อน +1

      Cuando el motor eléctrico esté parado, presione y mantenga presionado el botón F/R durante 3-5 segundos. F/R = avance/retroceso. El LED F/R cambiará de estado y el motor ahora funcionará en la dirección opuesta.

  • @victoralfonsooviedotejada6153
    @victoralfonsooviedotejada6153 11 หลายเดือนก่อน

    Saludos buenas noches tengo una pregunta.
    El VDF se puede poner a encender automático osea cuando haya un corte de energía que el mismo VDF se resete y encienda solo sin la necesidad de darle al boton run?

    • @toddbenko6701
      @toddbenko6701 11 หลายเดือนก่อน

      No creo que esto sea posible con la configuración VFD original. Creo que tendría que configurar el VFD para usar un interruptor de funcionamiento externo que podría estar siempre cerrado o usar un retardo de tiempo. De cualquier manera, necesitaría explorar opciones utilizando componentes de interruptor externos.

    • @victoralfonsooviedotejada6153
      @victoralfonsooviedotejada6153 11 หลายเดือนก่อน

      @@toddbenko6701 excelente gracias hermano por su respuesta un fuerte abrazo desde Republica Dominicana.

  • @joe-tech
    @joe-tech ปีที่แล้ว

    Hi there can you provide the link for the Manual you got H100-2.2C2-1B
    Thanks
    Input: 110V 50/60Hz
    Output: 0-110V 12.5A 0-1000Hz
    Parameters what I am using, not validated as functionally correct.
    F003 main freq = 60hz
    F004 ref freq = 60hz
    F005 max freq = 100hz for 1750rpm unit 60 for 3600rpm unit
    F007 min freq = 10 hz
    F008 Max Voltage = 120V
    F026 stop mode = 0
    F028 stop freq = 0.5 hz
    F030 stop braking time = 0.0s
    F031 DC braking level = 2.0 (dont care as long as F30 = 0.0)
    F039 start freq for braking = 4.0 (dont care as long as F30 = 0.0)
    F141 motor rated voltage = 120V
    F142 motor rated current = 3.0 (use according to motor)
    F143 number of motor poles = 02
    F170 selection of display 1 = 2 (for RPM)
    F184 RPM display factor = 0.5 (for 1750, use 1.0 if motor is 3600)
    F193 output open phase = 0
    F194 0hz output enabled = 0

    • @prairieedgeservice
      @prairieedgeservice  ปีที่แล้ว

      website for the VFD manufacture is www.zhonghuajiangspindle.com/VFD-2.2KW.html
      manual is available at community.carbide3d.com/uploads/short-url/sPh8tLgHr8zcgjSTjTfZp8PDyl.pdf
      Lots of good information about unit installation from carbide3 site: community.carbide3d.com/t/how-to-h100-vfd-1-5kw-air-cooled-spindle-setup-zhong-hua-jiang/54310

  • @ephraimsilberberg708
    @ephraimsilberberg708 หลายเดือนก่อน

    Do you have a link to the vfd that you are using? Is it a single phase 220v?

    • @prairieedgeservice
      @prairieedgeservice  หลายเดือนก่อน

      all the information you seek is in the other video. This video is the continuation which regards the programming of the unit found in the first video
      th-cam.com/video/qpZFb5PtnTk/w-d-xo.html

  • @sohaeb-ot9ci
    @sohaeb-ot9ci ปีที่แล้ว

    I have like this vfd single phase to three phase 120 volt can I connect with motor single phase? Thanks

    • @prairieedgeservice
      @prairieedgeservice  ปีที่แล้ว

      The answer is NO. You will need to select a different VFD model. I believe you will need a VFD model that specifies 3 phase input 120V to 3 phase output 120V. Remember we are not running a 3 phase motor, but we are connecting a single phase motor with 2 phases in a 3 phase connection. This is not fully balanced hence don't expect perfect operation.n