E5 HPC fault Manitowoc ice machine troubleshooting and repair
ฝัง
- เผยแพร่เมื่อ 29 มี.ค. 2024
- This Manitowoc ice machine was shutting off on E5 HPC fault. I found the Fan Cycle Control pressure switch to be burnt. The burnt switch and burnt wires would not allow power to pass to the condenser fan motor. The machine would over heat and shut itself off.
I also repair this Manitowoc ice machine by replacing the fan cycle control switch.
Always used the flare block to re-round the pinched tubing. Glad it worked out for ya...
And screw the TH-cam police. You do you.
Thanks for putting up valuable content.
I could probably find a better way to reopen the pinch. I unfortunately don’t have a flare block. lol. I was warned but didn’t listen.
Awesome video.. always do a visual inspection.
Yes! Always!
👍👍👍
💪🛠️
That’s funny someone gave you crap about throwing an old part. The TH-cam police will get ya 😂
I was warned but didn’t listen. 👂. I’ll be better next time.
Does that pinch off method have any potential to put a leak in the copper line? Just asking to see if this is a good regular method or a now and again thing.
I’ve never seen it but I’m sure others have. Anyone else have a problem with leaks when pinching copper?
Nice one again
Thanks again! I appreciate you.
Good fix on this one
Right on! 👍 🤫