TXV replacement on ICP Carrier heat pump

แชร์
ฝัง

ความคิดเห็น • 164

  • @RT10Viperman
    @RT10Viperman 2 ปีที่แล้ว +11

    A couple of things I was taught in Carrier school was always use the smallest amount of heat to get the silver to flow on the TXV, wrap the valve, Do it quick in and out, and always bright shine the suction line under the TXV sensing bulb for a good conduction of heat, The small line is called a quench line just encase the TXV fails closed it allows a small amount of refrigerant to flow back to the compressor to keep it from burning up. 34 years commercial and transportation refrigeration mechanic

    • @taddial5475
      @taddial5475 9 หลายเดือนก่อน +2

      Actually, in this application it's an external equalizer.

  • @craigschultz928
    @craigschultz928 3 ปีที่แล้ว

    Hi Ted! Your videos are great! Looking forward to the next new shop update ! 😊👍

  • @bobgallo2178
    @bobgallo2178 3 ปีที่แล้ว +6

    You young guys pay attention to what Ted did, I once broke the equalizer tube off, had to drill and new hole. That was not fun. Also, when going to add gas, when I was in Syracuse, Carrier said to let it run for 15 minutes before adjusting the charge. I am retired and don't envy you guys for some of the junk that you have to work on these days. Ya all be safe out there.

  • @robertwood9628
    @robertwood9628 3 ปีที่แล้ว +7

    Another easy way to replace the equalizer tube is to score it with a knife and snap it apart. Then take a 1/8 or 1/4 piece of tubing to make a coupling and braze both ends. That way you don't have to worry about solder getting into the line or plugging up the tube.

  • @peterhodgkins6985
    @peterhodgkins6985 3 ปีที่แล้ว +5

    I'm not terribly experienced in residential HVAC, but in my limited experience, the heat pumps tend to take a lot of time to stabilize as demonstrated in this video! Being in a hurry will getcha into trouble sometimes! ;) Good video!

  • @taddial5475
    @taddial5475 9 หลายเดือนก่อน +1

    Hey Ted, great video. I quit using cork tape on heat pump applications a few years ago, because I would come back later and find it had melted off when it went into heating mode! Started using the foam tape-doesn't stick as well, but like you, I put zip ties on anyway.

  • @stevencbowen
    @stevencbowen ปีที่แล้ว +1

    Great video and commentary. You are a real professional.

  • @a11ten071
    @a11ten071 2 ปีที่แล้ว +1

    TNX for the ride along great video much appreciated👍

  • @donlove3741
    @donlove3741 2 ปีที่แล้ว

    Gotta love InsaneClownPosse .
    Worked a few 20 ton ICP Rooftops-before 5 years most need a CondFan motor ot wiring burned at contactor dead inducer motors..
    Replaced many Lennox/ICP/Trane TXV/TEVs.
    Usually added or replaced liquid drier as well dang Danfoss !
    Boys and girls did this stuff for 25yrs(30%industrialHVAC 80%Commercial Industrial Refrigeration) I forgot how cramped residential space were!
    Boys and girls LISTEN TO THIS MAN ! He's 100% correct.HVAC Ain't instantaneous results.
    Run them bad boys for 15 20 mins then finish diagnosis! I Refrigeration some adjustments/repairs may need a visit tomorrow once it's all back to steady state.
    This guys the real deal !
    I'd call him !

  • @robinmclaren4596
    @robinmclaren4596 2 ปีที่แล้ว +1

    Enjoying your post just happened to find you keep up the good work 😉😉☺️

  • @AMDRADEONRUBY
    @AMDRADEONRUBY 3 ปีที่แล้ว +5

    Nice a new video from the best guy Ted you rock.

  • @hg2.
    @hg2. 3 ปีที่แล้ว +1

    Great to see the nuances along the way!

  • @gocubsgo5055
    @gocubsgo5055 3 ปีที่แล้ว +2

    I've once had the opening on the feed tube closed over with solder. I make my own new hole in the line now!

  • @wonderhomie2011
    @wonderhomie2011 3 ปีที่แล้ว +2

    That factory filter door was upside down. Nicely done repair.

  • @Georges3DPrinters
    @Georges3DPrinters 3 ปีที่แล้ว

    Excellent work. Appreciate this video and the troubleshooting steps.

  • @95thousandroses
    @95thousandroses 3 ปีที่แล้ว

    Great video. Going to give Chris at HVACR videos some competition on trainer content if you keep this up.

  • @73elperro
    @73elperro ปีที่แล้ว +1

    Excellent video,thank you for sharing your knowledge!!

  • @159753android
    @159753android 3 ปีที่แล้ว

    I’m new to hvac and I’m so glad a pro calls it welding sometimes too lol

  • @clanharris4
    @clanharris4 3 ปีที่แล้ว +2

    I always angle the cap tube with the direction of the flow, it helps prevent and fouling of the port into the valve.

  • @soteroseniceros2914
    @soteroseniceros2914 3 ปีที่แล้ว

    Nice!!! I had the same problem. I changed out the TXV.

  • @dylandrymond3951
    @dylandrymond3951 3 ปีที่แล้ว +2

    Thanks for the clip Ted. I use hose clamps and scrap those copper clamps and then cork tape. I have a trick for you on how to check a txv in under 60 seconds. I'm sure most people don't know. Let me know if you want me to explain it. Thanks again.

    • @jgt6061
      @jgt6061 3 ปีที่แล้ว +1

      What is the trick?
      High to normal subcooling and high superheat?

  • @Del-ok8uw
    @Del-ok8uw 11 หลายเดือนก่อน +1

    Very good work and patience 👍

  • @charlesyates6687
    @charlesyates6687 3 ปีที่แล้ว +2

    Had a a/c guy out last year had a unit in his van that had a flex tubes on it to put into the window and he plugged it into the condenser outlet outside and cooled the house down while he was fixing our a/c . Thought that was a great idea keep your customer cool while fixing their unit .

  • @tombeilman5579
    @tombeilman5579 3 ปีที่แล้ว +5

    I wanted to see if you could straighten the fins

  • @dimaslespier2688
    @dimaslespier2688 3 ปีที่แล้ว

    I like your approach to charging. Especially with the new refrigerants as they are all blends and the chemical make up of them sometimes makes them separate. Patience is a virtual.

  • @christianmerryman1854
    @christianmerryman1854 3 ปีที่แล้ว

    This was very help I am working on a unit the pressures are 400 on my high side and my suction side is 100 .

    • @jgt6061
      @jgt6061 3 ปีที่แล้ว

      Dirty condenser coil

    • @jgt6061
      @jgt6061 3 ปีที่แล้ว

      Maybe
      Check superheat and subcooling

  • @Ted_E_Bear
    @Ted_E_Bear 3 ปีที่แล้ว +1

    Great video Cowboy Ted !

    • @awxlio8496
      @awxlio8496 3 ปีที่แล้ว

      They need to do more of those

  • @sknight0391
    @sknight0391 3 ปีที่แล้ว +20

    YES!!!! When I saw that drain trap I was like....."Come on Ted, stick your finger in it!" And then you did 😄👌

  • @adobo6905
    @adobo6905 3 ปีที่แล้ว +3

    It is easier to braze the 3/8 liquid line feeding the TXV outside the plenum and then position it inside and continue connecting the rest of the piping. lol

  • @roybatty6368
    @roybatty6368 2 ปีที่แล้ว

    Carrier really makes great equipment

  • @MrNaraagmgl
    @MrNaraagmgl 3 ปีที่แล้ว

    My customer has exact the same downflow Carrier .Supply box has full.kd water spread to Main flex duct which couldn't hold full of water .It affected ceiling. It was inside attic i offered to relocate horizontally install .Cause downflow unit creates a lot condensation

  • @baileysair
    @baileysair 3 ปีที่แล้ว +1

    Love the tubotorch!

  • @bryanphipps5912
    @bryanphipps5912 2 ปีที่แล้ว +1

    Sensiing bulb is installed upside-down . The little line should be on the bottom while the long tube traveling back to the actual txv is on top. Other then your choice of torche nice video

  • @Biarkii
    @Biarkii ปีที่แล้ว

    I love the alvin and the chipmunks speed ups

  • @christophermiller1520
    @christophermiller1520 3 ปีที่แล้ว

    Ruud and Rheem have the best clamp for the bulb they use to send copper band iron but now they got these little clamps with threaded hole for the screw and u just tighten the one screw

  • @philosothink
    @philosothink ปีที่แล้ว

    i had a very similar problem, with the SAME unit. paused on the data plate. worse suction pressures. it boiled down to the TXV. I ordered a replacement via Supplyhouse, and after install, it did the same damn thing... I had to turn that job over to the Carrier rep. Lost about 600 bucks... and that was by far the dirtiest drain I've ever seen!

  • @joeydelmarsjr.646
    @joeydelmarsjr.646 3 ปีที่แล้ว

    i got a 4ton for 1300sqft thats 350ft per ton in southern Nevada easy 115 degree days, i aim to get 1600cfm and my filter is 20x20x1 side by side for a total of 20x40 filter return. i currently use the honeywell HD merv 11 filters but i think ill start using the 3m 1200 merv 11 because of the more surface area on the filter to help decrease static pressure if that doesnt help ill try to use 4in filter

  • @HsingSun
    @HsingSun 3 ปีที่แล้ว

    Originally, they built the ac draining system unit inside the house was not working perfectly because there were two 90 degree angle which caused clogging easily. Four years ago, after I cleaned up and unclogged three times the draining line, it was still clogged at that time. So, I had to cut-off one 90 degree angle tubing and I made it work since then.

  • @mikemcgill8119
    @mikemcgill8119 3 ปีที่แล้ว

    Hey Mr Ted I watch a ton of your videos, I think you do great work and always try and do what’s best for the Customer ( I try and do the same) anyway a bit of advice, maybe next time bring the bulb out of the cabinet through the panel with the suction line, it allows you to mount easier and you can also place the bulb on the position of the pipe that the manufacturer recommends ( that seems to change every time I read the literature) then I just insulate with armaflex

    • @SeanBaker
      @SeanBaker 3 ปีที่แล้ว

      My TXV is outside of my coil cabinet.

    • @williekeener9604
      @williekeener9604 3 ปีที่แล้ว

      Mike, I think that by putting it in the factory cavity, he did put the bulb in the manufacturer recommended position. All of the carriers seem to have that depression. The bulb is also strapped to the line so it’s touching when when you heat the pipe to install. Weird how it fails.

  • @DutchMastaa
    @DutchMastaa 3 ปีที่แล้ว +7

    Every particle that bypassed the filter is in the PVC

  • @krissewar1044
    @krissewar1044 2 ปีที่แล้ว

    I use the existing pressure tube swedged to weld over the new one. No pans burnt. No weld drip into the suction. And no waiting for the bulb install.

  • @txbuzzard3260
    @txbuzzard3260 2 ปีที่แล้ว +1

    Do you not purge your linesets with nitrogen when soldering?

  • @wannis100
    @wannis100 3 ปีที่แล้ว +1

    Thank you, I am ready to work for you.

  • @rocker8692
    @rocker8692 3 หลายเดือนก่อน

    Hi Ted, do you braze with oxy and acetylene or just acetylene?Thanks

  • @whatamidoing7061
    @whatamidoing7061 3 ปีที่แล้ว +2

    Are you running nitrogen thru when unbrazing?

  • @huntforandrew
    @huntforandrew 2 ปีที่แล้ว

    I have one of these and water is leaking from the bottom of the unit. I cleaned out the condensate pipe but it's still leaking. What are your thoughts?

  • @jorgeestrada3894
    @jorgeestrada3894 3 หลายเดือนก่อน

    Thank you sir for sharing your videos.....what kind of torch are you using ? Acetylene/oxigen or oxigen only?

  • @jgt6061
    @jgt6061 3 ปีที่แล้ว

    Wow this one seems kinda weird bc at first subcooling and superheat indicated low freon, a little bit later indicated bad txv I never seen that happen before within the same service call, I guess things you don’t know about do happen. Also for this unit very easy txv install even a rookie can do this with eyes closed! Here in Texas units in attics and very tough to get to but that is why we charge 800 plus to replace txv in attics

  • @bryanmitchell5728
    @bryanmitchell5728 2 ปีที่แล้ว

    Did you fix the smashed evaporator? Shouldn’t it have a trap for the drain?

  • @HsingSun
    @HsingSun 3 ปีที่แล้ว

    Can you clean the grill without remove the drain lines?

  • @rmheatandcool9784
    @rmheatandcool9784 2 ปีที่แล้ว

    What size tips u use with your b tank?

  • @jimgill5706
    @jimgill5706 2 ปีที่แล้ว

    You should be using Stay Brite 8 on that TXV. I quit brazing new copper years ago. No nitrogen, no scale and no risk of component damage, and no leaks.

  • @JamesBrown-db9pk
    @JamesBrown-db9pk 3 ปีที่แล้ว

    happy 4th cowboy

  • @jima3129
    @jima3129 11 หลายเดือนก่อน

    Couldnt you just use stainless zip ties for the bulb , Ted? They are nice. Or all stainless hose clamps?

  • @kronos3244
    @kronos3244 2 ปีที่แล้ว

    @ Anti DIY HVAC. Hey Ted My Ac unit cools my house ok but my vents seem to not be blowing that well. The air is cool and it works well but what seems like low air flow. Your professional opinion what would you say it is?

  •  2 ปีที่แล้ว

    Hey Ted this is pretty important question when you brazed that txv in did you use nitrogen and do you have to wrap that txv with a wet rag or do you just get away without doing that on those jobs? I’m not being funny I’m really asking you.

  • @marvinsellers4457
    @marvinsellers4457 ปีที่แล้ว

    Hey Hoss the turtle won the race just saying I’m on board with you on charging

  • @ishalljr
    @ishalljr 3 ปีที่แล้ว

    What size tip is that?

  • @vuonghung3134
    @vuonghung3134 3 ปีที่แล้ว

    good job 👍👍👍👍

  • @hdshows8704
    @hdshows8704 ปีที่แล้ว

    Can a hose clamps works?

  • @lancerudy9934
    @lancerudy9934 2 ปีที่แล้ว

    Do you ever use heat block?

  • @nomusicrc
    @nomusicrc 2 ปีที่แล้ว

    What is the tube for

  • @Ontimecontractors903
    @Ontimecontractors903 2 ปีที่แล้ว

    What is the actual name for what you call tar tape? I've been seeing it lately in the field in my area. I guess everyone else has left duct tape.

  • @jodytucker4474
    @jodytucker4474 2 ปีที่แล้ว

    So could sucking up that much dust through the crappy filters creat that much debris (mud) in the drain??

  • @christopherscott8853
    @christopherscott8853 3 ปีที่แล้ว

    I've never used that wet goop heat sink. Just wet rag strips. How do you like it? Anybody?

  • @gankstar2000
    @gankstar2000 3 ปีที่แล้ว

    Well done, Ted!!! God bless; Jesus loves you!!!

  • @brettsalling
    @brettsalling 2 ปีที่แล้ว

    Just went through the same exact thing on the same exact unit about a month ago

  • @JoseAlvarez-rz6sl
    @JoseAlvarez-rz6sl 2 ปีที่แล้ว

    Where can I get that battery washer that's a very nice one

  • @howardharaway2259
    @howardharaway2259 9 หลายเดือนก่อน

    Why unsweat the equalizer tube ? I always carry 1/8" couplers..Its alot easier.

  • @panamacitybeachbum
    @panamacitybeachbum 2 ปีที่แล้ว

    Fin comb?

  • @beamylist1612
    @beamylist1612 3 ปีที่แล้ว +4

    Long story short avoid putting in txv , nice vid mate.

    • @FrostBlueFire
      @FrostBlueFire 3 ปีที่แล้ว +1

      If you wanna play pussy footing, sure. TXVs dont go bad as many people think they do. Pull a good vacuum, and make sure you braze with nitrogen. Easy money, easy diagnostics. If you wanna be cheap, then spend extra time tossing in a piston

    • @zack9912000
      @zack9912000 3 ปีที่แล้ว

      @@FrostBlueFire You remember that massive failures we had just a few years ago the seals were mucking up because a bad reaction to the refrigerant oils. Changed 40 plus out that year

  • @alibuolayyan9038
    @alibuolayyan9038 3 ปีที่แล้ว +5

    Mud collects in the drain pipe because they do not use a filter or the filter is not good

  • @mattflorence6060
    @mattflorence6060 3 ปีที่แล้ว

    Ted, have you tried Measure Quick yet?? I have the Fieldpiece probes that I use Measure Quick on and I really do like it.
    Just wondering, nice video and nice repair sir.
    FMS Heating and Air from NC

  • @dadefope80
    @dadefope80 3 ปีที่แล้ว

    Next Level

  • @nomadismileseeker6611
    @nomadismileseeker6611 3 ปีที่แล้ว +12

    I would have just changed the coil. If it’s not leaking, it will be soon enough.

    • @zack9912000
      @zack9912000 3 ปีที่แล้ว +3

      same, not worth the headaches that follows

  • @panamacitybeachbum
    @panamacitybeachbum ปีที่แล้ว

    Oh no. The ubiquitous Turbo Torch makes the scene.

  • @stevealoia
    @stevealoia 3 ปีที่แล้ว +3

    Nice doing a txv on Monday . I use stay bright8 on the valve . I can’t see cooking a valve like a txv

  • @_GandalfTheGrey_
    @_GandalfTheGrey_ 2 ปีที่แล้ว

    What does a job like this cost a customer? Seems like it requires more skill and danger potential to the technician. Anyone know an average rate for a job like this in a place like southern california?

  • @blake8297
    @blake8297 3 ปีที่แล้ว +1

    Haha, Ted has learned how to fast forward through parts of his video.

  • @gman8260
    @gman8260 2 ปีที่แล้ว

    Where did all the mud come from? Look no further than the interior of the cabinet. It is filthy and that debris eventually works its way through the condenser fins, down the drain pan and lodges in the condensate drain.

  • @daviddesilva4971
    @daviddesilva4971 3 ปีที่แล้ว

    A heads up on the vacuum running would be appreciated. Thxs for the vids!

  • @phillipwickstrom1593
    @phillipwickstrom1593 3 ปีที่แล้ว +2

    I'm going to call it Jimmy Wiggler from now on. Thanks.

  • @russelhancock5718
    @russelhancock5718 ปีที่แล้ว

    She's a Crusty One Mr Grinch.

  • @xcalibre222
    @xcalibre222 2 ปีที่แล้ว

    I see they make a fin comb for straightening those fins out . I don't think they would do any damage if done carefully. You don't use those? Thanks for the Great Vids. :)

  • @mataiaren6917
    @mataiaren6917 3 ปีที่แล้ว

    I knew you were the voice actor for Alvin. HVAC is just a pastime for you Ted.

    • @tomwalker9184
      @tomwalker9184 3 ปีที่แล้ว

      Ted you are from a place where life is a little slower and people take time to smell the Rose's so to speak, sit on the front porch an enjoy life a little. SO TED ALWAYS BE YOU AND YOU WILL NEVER GO WRONG.!!!

  • @NY411Info
    @NY411Info 3 ปีที่แล้ว +1

    Ted, It's dust from a crappy fitting air filter.

  • @josephtramutola592
    @josephtramutola592 3 ปีที่แล้ว

    I would’ve replaced the dryer I know you’re pumped down in the dryer probably is inside the equipment .

  • @La2venida
    @La2venida ปีที่แล้ว

    So simptoms:
    Hi Su cool
    Hi Superheat
    Lo suction press
    Normal/hi Head
    For a bad txv , will this be the ONLY set of simptoms , or can you have another combination set of simptoms ?

  • @toolfanatic
    @toolfanatic 3 ปีที่แล้ว +1

    👍🏼

  • @RVail623
    @RVail623 3 ปีที่แล้ว +1

    Just curious: what would the cost be (parts & labor), for replacing that semi-flattened coil?

    • @adamcraig1568
      @adamcraig1568 3 ปีที่แล้ว +1

      1500-2k with reputable company with a decent overhead

    • @zack9912000
      @zack9912000 3 ปีที่แล้ว

      As stated above if it is a r22 system, it will cost you more though.

    • @waltersmith7950
      @waltersmith7950 2 ปีที่แล้ว

      I'm just curious and used to work in a factory that manufactured refrigeration units - we would use a fin comb to correct slight damage on a new coil. Could it be that the fins can't be realigned due to the age of the aluminum? I was hoping to see some air flow created at those flat spots.

  • @jeramymann5397
    @jeramymann5397 3 ปีที่แล้ว

    Mr. Cook can you share the link to your vacuum connection for clearing condensation lines

  • @toddbellefeuille5376
    @toddbellefeuille5376 3 ปีที่แล้ว +1

    Ted for President!!!

  • @Mercmad
    @Mercmad 3 ปีที่แล้ว +1

    that drain needed a good jetting i think. 😁

  • @sharky5570
    @sharky5570 3 ปีที่แล้ว +1

    Parts runner would be nice

  • @MariosACandRefrigeration
    @MariosACandRefrigeration 2 ปีที่แล้ว

    why not, remove evap.wash replace valve and reinstall.?

  • @davidlopan6649
    @davidlopan6649 3 ปีที่แล้ว +1

    Whats the going rate for a txv change-out?

    • @Del-ok8uw
      @Del-ok8uw 11 หลายเดือนก่อน

      $60+ hour

  • @user-sr6qp6fg6k
    @user-sr6qp6fg6k 21 วันที่ผ่านมา

    no filter change till you got there

  • @stephwaylonwells3218
    @stephwaylonwells3218 3 ปีที่แล้ว

    👍

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 3 ปีที่แล้ว

    🤠

  • @clanharris4
    @clanharris4 3 ปีที่แล้ว

    And try and clean up the copper of the bulb and the tube it's going on.