APC SURT UPS Fault Codes | All Diagnostic Codes
ฝัง
- เผยแพร่เมื่อ 6 ก.ย. 2024
- In this video, I will tell you about all the fault codes of apc surt ups. These fault codes are also called diagnostic codes. They tell you that which part of ups you have to repair.
This is a very informative video.
SUBSCRIBE my channel for more videos like this.
query solved...
apc ups
ups
apc ups fault codes
apc ups diagnostic codes
how to repair apc ups
apc surt ups faults
how to fix apc ups
apc ups repair
ups apc
#apc #ups #upsrepairing
MashAllah sir app to SURT Kay most expert Hain .well done .
very informative video jzakallah
Nice information.
Jazak ALLAH
In 4:10 we have the DC Bus Overvoltage Error. Any information about this error? The service manual has not any tip. Thanks for your videos...Regards fro Brazil.
Sorry for subtitles.
I will recheck and amend where needed.
If you have this type of fault then kindly check
R760, R761, R762, R763, R764 and R865 for negative bus and
Check R766, R767, R768, R769, R770 and R771.
@@AKElectroTech R771 open
Replace it and I hope problem will solved
@@AKElectroTech It was solved. Thanks.
Hi. If during repair, all the leds on the panel should light up(load led), what is the problem? This condition exists while there is only coverter and the buss voltage is fixed by using battery. Inverter and charger are removed from the board
The first time, after completing the board, the output in battery and line mode was correct. On the line mode, when we pressed the off key, the converter and charger exploded again.(Apc model is lynx 2kva)
Your charger is not burst. Charger is Ok but battery converter was burst.
IC 2 located on control board may be faulty because display is showing max current while UPS have no load.
Be cool and repair battery converter
Well done I need this same...kindly Make all ups Video .
Huawei .legerand and Inform
Yes
Pl wait
Yes sir I always with you....agar aap mujay personal curse bhaj dain Tou main pay kr sakta hu sir Please.
No need to pay money for any course. I will try to upload videos for various UPS. Although my videos are not professional but I will try to do best for learning. Thanks
sirji aap ka vdo itna simple hai ki easly we can do the repair.. hats off to u sir ji .. god bless u and ur beloved once @@AKElectroTech
@@rajukv5915
I will try to make videos very simple so any one can repair easily. Thanks
I repair apc lynx that conerter and charger are broken. I have a Question
You can share video on +923215717132
@@AKElectroTech telegram?
Sorry
Wattsapp
@@AKElectroTech ok tanks
Hello and first of all thank you!
Question, regarding 3:48 fault. Unfortunately the subtitles are not very good. Would you mind explaining what this fault could mean and where I could start investigating? Thank you!
Hello and I know that subtitles and even quality and editing is also not good. I am not professional but try to improve. Thanks
Coming to your question regarding 01100 fault (Soft Start fault)
First check your batteries.
Check PFC portion for any shortage.
Check battery relay.
And I hope you will find your solution.
You're doing good! Much appreciated, thank you! Keep up the good work@@AKElectroTech
JazakAllah
Bagus
Thanks
Hello
I have a fault: Battery Bus Soft Start Fault
What could be the problem? Where to look first?
You said: Check PFC portion for any shortage.
Where is this PFC located?
Thank you
Batteries are new...in one of the batterie cartridge a fuse was blown.
Hello
Pl mention ups type and model ie
SURT or SURTD model and kva
@@AKElectroTech SURTD5000XLI
Pl check PFC portion.
Q726 and Q727 are used on battery.
Q709 and Q710 are +ve PFC
Q708 and Q711 are -ve PFC.
Check this portion along with optocouplers and associated components.
RY702 may be checked. This relay is used for battery.
If this portion is short, then check inverter Q715, Q716, Q717, Q718 Q706, Q736, Q705, Q736 with D750 and D751.
@@AKElectroTech Hello. Upon inspection i found that resistor R828 and capacitor C721 are burned. Should i just replace them or is a possibility that something else is in fault?
Hello.
I have an 8 kva model with error code 01100.
Can you tell me by any chance where the problem is?
Yes of course
01100 means battery soft start. It may happen due to PFC IGBTs short, or in case of battery low then it may be happen
@@AKElectroTech It is possible somehow that the battery soft start capacitors are out of they parameters?
soft start capacitors are not present.
It may possible that battery capacitors may be faulty
No.
4 big capacitors are DC bus capacitors which hold +400V and -400V DC.
C1447 and C1448 located at inverter board are DC capacitors. Both have 470uF 450V value.
Okay thank you. I will check this tomorrow and I will be back with a response if any of this ideas may help.
AoA sir over temperature ho kia karien battery theek hain heat sink ka fault kia hota hai
WAS
Over temperature means there are three thermostat one located in battery compartment and two are attached with PFC and Inverter heat sinks named SW701 and SW702. If they are ok then check IC13 in SURTD_model and IC8 in SURT model.
Traducción del audio en español
Added
❤
Need solution for logic supply fault jii . Apc 3kva ups
Ok pl wait
Surt 3kva no dis play Folty
Check ribbon cable or fusible resistors on display board and control board. Near ribbon cable or RJ45 cable connector
how to fix 11001 error fan error?
Fan error is 00110.
sorry yes same error. how can i fix that error .the fan not spinning @@AKElectroTech
sorry, yes how can i fix the error?
@@AKElectroTech
Check fan by applying 24vdc
fan is working, but in mother board fan 24 v not coming
@@AKElectroTech