Repair - APC Back-UPS M1000

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ม.ค. 2025

ความคิดเห็น • 68

  • @serpins99
    @serpins99 22 วันที่ผ่านมา

    I had exactly the same problem. Changed C40 and C41 and the UPS is online again. I didn't have 16v capacitors but changed using 63v capacitors without any issue. Thanks thanks thanks what a useful video.

  • @peshmadscientist1833
    @peshmadscientist1833 2 ปีที่แล้ว +3

    Brilliant! Customer had some clucking and clacking at first then no regular ac operation. I suspected a relay but thanks to you I found 22uf caps in control circuit exhibiting signs of high esr. Replaced c40,41 and few others weak in that area. Used low esr high temp leaded versions. A 4.7uf and 10uf also replaced. All surface mount. To open, more screws hiding under front panels. Bat cover moves down and control board cover moves up. Carefull the ribbon cable.

  • @shadowkriz
    @shadowkriz 2 ปีที่แล้ว +2

    I got the same one, WITH THE SAME PROBLEM, and this video just turned on a light of hope.
    THANKS BRO!

  • @p2kart
    @p2kart ปีที่แล้ว +1

    Thanks, like others I replaced C40 and C41, I cant reitterate how careful you need to be with those traces, they are unnecessarily thin, and pulled pads off both C40 and C41, luckily I was able to trace them back to near by components.

  • @JaafarA
    @JaafarA หลายเดือนก่อน

    thanks for your post which directed me to fix my ups, I replaced both C40 and C41 despite they both measure 22uF, but may be they drift under voltage and temperature. Now the ups comes alive again.

  • @roblane6368
    @roblane6368 2 ปีที่แล้ว +1

    I've just carried out a repair on one of these models (UK version - 230VAC), it had exactly the same fault, the rattling relays on startup then fail to detect mains supply. I changed all the relays however the fault remained. Thank you for doing this video - it saved me hours of fault tracing - it turned out on mine that C40 was OK but C41 was low at about 15uf - should have been 22uf. Changed C41 and the unit sprang into life. Thanks again for this.

  • @hernancoronel
    @hernancoronel 3 ปีที่แล้ว +3

    If I had done that relay repair, when I finally receive the proper relay it is 99.99999% chance that it will NEVER be replaced LOL! Great job in explaining the troubleshooting process and everything you did. I actually have TWO of these exact model UPSs in the queue to repair and I didn't even really knew where to start (which should have been obvious) but your video has definitely inspired to tackle them and hopefully repair them. Thank you, thank you, thank you!

  • @michaeldoyle706
    @michaeldoyle706 3 ปีที่แล้ว +4

    This worked great for my RS1500. C41 was bad. Thanks for the great video.

  • @Cadorna-Tagarna
    @Cadorna-Tagarna 3 ปีที่แล้ว

    I have a RS 800 and a RS 1000, the RS 800 failed a few months ago, the RS 1000 failed today. They are exactly the same symptoms, I will check those capacitors. He had not been able to find reliable information to proceed with a repair.
    Thank you very much!
    Excellent work
    Good video.

    • @z1power
      @z1power  3 ปีที่แล้ว +1

      Good luck with your repair!

    • @Cadorna-Tagarna
      @Cadorna-Tagarna 3 ปีที่แล้ว

      @@z1power Thanks!

    • @Cadorna-Tagarna
      @Cadorna-Tagarna 3 ปีที่แล้ว

      ​@@z1power 273 / 5000
      I finally got the C40 and C41 capacitors and replaced them in the RS 1000, the UPS was like new!
      In the UPS RS800 I replaced the capacitors C57, C59 and C60, it also worked very well!
      I only had a few common electrolytic capacitors, but they worked wonders.
      Thank you very much for your video and your work, it helped me a lot.
      Greetings from Chile

  • @vickslab4608
    @vickslab4608 ปีที่แล้ว

    Thank god I found this video, I have the same UPS but in 1500 doing the click of death sound. I am going to try and replace C40 and C41. I wish I had an ESR meter. I want to keep this unit as long as possible as these UPS are pretty simple inside to diagnose compared to the newer ones. Less features, less things to go wrong.

  • @scottbierly3398
    @scottbierly3398 3 ปีที่แล้ว +1

    Great video, many thanks! I have a mere APC350 that went crazy, and the new battery didn't fix it. Even though it is likely very different inside, you really helped me get the gist of these things. It seems to be a common failure mode of power circuitry that not only is it failing electrolytics, but it is often the smaller feedback or sensing ones that die. Thank you!!

  • @ovalwingnut
    @ovalwingnut ปีที่แล้ว

    GR8T Job. Lots of lessons for "us" out here on the Interwebs. Thanks for the ride along!

  • @rogercolina87
    @rogercolina87 ปีที่แล้ว

    Thanks, I repaired my computer with the help of this video.

  • @NoferTrunions
    @NoferTrunions ปีที่แล้ว +1

    Wow, I have an RS 1500 that outputs 135v when on inverter. Was thinking maybe the caps (40 41) from your video. When bad caps have been found in this model, my first thought is... Bad Caps (!) as with all mobos, monitors and PSUs. Caps = GOAT repair fix.
    However looking at that nasty square wave, I might just trash it.
    ....still, it is a puzzle and I like solving puzzles. Problem is I know nothing about the circuitry other than what you explained.
    It's been on the shelf for some years and I don't remember if the over voltage was only present during backup. If all the time, then perhaps the Boost feature.

  • @BW-cw9xw
    @BW-cw9xw ปีที่แล้ว +2

    My BR1500i also have same problem, inverter / relay / battery charging all work, just detect AC mains got problem, from management port, it show input have 56V / 3xxV, I will try replace those two capacitor, thnaks.

    • @BW-cw9xw
      @BW-cw9xw ปีที่แล้ว

      Problem solve, C40 in negative charge pump circuit to generate negative voltage around -9v across C41

  • @jameskrivitsky9715
    @jameskrivitsky9715 3 ปีที่แล้ว

    Good job tracing the problems. Even for just additional parts identification, I gained a bit more info for troubleshooting my APC ES 500 supply. Thanks JwgK

    • @z1power
      @z1power  3 ปีที่แล้ว

      Glad it helped!

  • @noimagination99
    @noimagination99 3 ปีที่แล้ว +1

    Thanks! I bet this fixes mine. I replaced the batteries, then it started always switching to battery power. Reinstalled powerchute, and the UPS thinks it's getting 156 VAC. Later, it thinks it's 104 VAC coming in. Clearly the input AC monitoring circuit has failed, and your video points me to the likely problem.

  • @SolarBuck
    @SolarBuck 5 หลายเดือนก่อน

    I have the BX1500 that is acting very similar. Can you tell me if those Caps you replaced C40 and C41 are surface mount or not? I couldn't tell from the video. I am decent at soldering but don't have the equipment for surface mount. I guess I can take mine apart and see but I like to take apart fix and put back together because if it sits around I may never around to putting it back together.

  • @dom61085
    @dom61085 5 หลายเดือนก่อน

    I have a apc ups pro 1000 with this issue. I lack the equipment to confirm. Will not run except on battery and will charge when off. I want to get it fixed but I can't find a repair shop in south FL that will touch it. Any help would be appreciated

  • @ZeinabSanei-jx1bl
    @ZeinabSanei-jx1bl 9 หลายเดือนก่อน

    Hi. If during repair, all the leds on the panel should light up(load led), what is the problem? This condition exists while there is only coverter and the buss voltage is fixed by using battery. Inverter and charger are removed from the board

  • @oskimac
    @oskimac 3 ปีที่แล้ว +2

    Nice tip about using a small ac transformer to look at mains on the scope.

  • @luisrebolledo8123
    @luisrebolledo8123 3 ปีที่แล้ว

    Excellent video on how to repair the most common fault in these UPS. The diagram is the same as the APC RS100. Thank you.
    Excelente video de como reparar la falla mas común en estos UPS. El diagrama es el mismo del APC RS100. Muchas gracias.

  • @danielsegura3453
    @danielsegura3453 ปีที่แล้ว

    Good video, i had a issue with apc rs1500 that he don't back to Online ac after checking battery, how can I fix that

  • @askarasaad1161
    @askarasaad1161 2 ปีที่แล้ว +1

    Great video thanks l have the same APC product faulty one model sc1000 with approximately 160vac out put and increased up to 174v with load if you can help with best regards

  • @a_la7065
    @a_la7065 ปีที่แล้ว

    Goodday. Thanks for your informative video. Could anyone please advice me on Q29 data; it virtually was dematerialized.

  • @3dFirefly
    @3dFirefly 2 ปีที่แล้ว

    Thank you for this video, so yea I have 4 different units that needs to be looked at, all of em says to replace battery but the batteries tested good. one works fine until it charges the battery up, when it gets to fully charge it throws the replace battery light. I hope to find what's wrong with them.

  • @allent
    @allent ปีที่แล้ว

    Looking for the values of the capacitors so I can buy some, can anyone share that info for the ones being talked about?
    I got hold of a schematic but the resolution is too low to read any details such as part numbers.

  • @GSDHANI
    @GSDHANI ปีที่แล้ว

    I have the same ups. In inverter section IRF 3205 mosfet get burnt every time I replace. Can you halp me where might be error

  • @germanlescano4228
    @germanlescano4228 2 ปีที่แล้ว

    Thanks!!! my rs 1000 had the same problem, i change those capacitors and now it's working again.

  • @mrmotofy
    @mrmotofy 2 ปีที่แล้ว

    I have a RS1500 that seems to be the same issue. What caps would be the correct replacement? What's a good source?

  • @TitanBoreal
    @TitanBoreal 2 ปีที่แล้ว +1

    Great! i really needed this video to exist!
    Its safe to change the capacitors voltage while mantaining the uf ? becouse i see that you didnot replace with exactly the same voltaje.

    • @z1power
      @z1power  2 ปีที่แล้ว

      It’s safe to change voltage as long as the new v is higher

  • @HarryoGaming
    @HarryoGaming ปีที่แล้ว

    How do I stop the charge function of the ups?

  • @chuckbenedict7235
    @chuckbenedict7235 ปีที่แล้ว

    I have a 1500 XS with a similar problem. Online light comes on for just a moment, then it switches to backup. A few seconds later, the cycle repeats. Almost as if it cannot detect line voltage ;-). I took out c40 and c41...one registered .5mf and the other 10mf (both rated for 22 mf). I'm guessing the rest of these surface mount caps are trashed (altho rated accuracy may be less important). I'm going to replace all the surface mounts. Thanks for the video!

    • @chuckbenedict7235
      @chuckbenedict7235 ปีที่แล้ว

      Update. I replaced C40 and C41. I used two soldering irons (like hot tweezers) so as not to damage the traces pulling the caps. I did not replace the rest of the caps. UPS started right up and is powering equipment.

  • @ZeinabSanei-jx1bl
    @ZeinabSanei-jx1bl 9 หลายเดือนก่อน

    The first time, after completing the board, the output in battery and line mode was correct. On the line mode, when we pressed the off key, the converter and charger exploded again.(Apc model is lynx 2kva)

  • @coloradowilderness3139
    @coloradowilderness3139 3 ปีที่แล้ว

    Really waiting for this kind of step by step tutorial on APC. Do more ...
    Thanks

    • @z1power
      @z1power  3 ปีที่แล้ว

      I'd like to but I don't get broken stuff coming my way that often

  • @justinblair379
    @justinblair379 2 ปีที่แล้ว

    Do a video on the same exact model fixing an overload error without any load on the UPS

  • @thabibikas
    @thabibikas 2 ปีที่แล้ว

    hi, Great job.
    So the main problem was the capacitors?

    • @z1power
      @z1power  2 ปีที่แล้ว

      Yes, correct

    • @thabibikas
      @thabibikas 2 ปีที่แล้ว

      @@z1power Thank you!

  • @72chargerse72
    @72chargerse72 ปีที่แล้ว

    I just just scrapped one 1200va same make same problem ..

  • @jtechlabs1
    @jtechlabs1 3 ปีที่แล้ว

    Nice video.
    I have the same unit. After replacing the batteries the unit would keep switching between battery and mains.
    I adjusted the sensitivity to low, using the built in sensitivity adjustment, however, I am wondering if there is something wrong internally as my utility power is pretty stable and reliable and I should not have needed to make this change. Any suggestions about what I should look into to fix this?

    • @z1power
      @z1power  3 ปีที่แล้ว

      Might be the same fault, seems to be common in these units

  • @Echo3_
    @Echo3_ 3 ปีที่แล้ว

    I have one that was never opened from 2009 and it is doa, I know the batteries are likely no good but it should at least power on , it is an apc rs 800 blk, I plan to open her up and see what there is to see.

    • @z1power
      @z1power  3 ปีที่แล้ว

      Hope it works out well!

  • @gumnahs
    @gumnahs 3 ปีที่แล้ว

    What type of relay is this “omron G2RG 2A4 relay”. How to test it. I am also facing the same relay sound back and forth problem.

    • @z1power
      @z1power  3 ปีที่แล้ว +1

      Test or replace C40 and C41 first

    • @gumnahs
      @gumnahs 3 ปีที่แล้ว

      @@z1power thanks!

    • @240mains
      @240mains 3 ปีที่แล้ว +3

      when relays chatter\buzz , the relay is most likely good .
      What is driving the solenoid is most likely bad .
      That doesn't say that the driver transistor is bad ,
      but something is wrong with the driving signal .
      ( relays can go bad , however
      the magnetic strenght and opposing spring force
      may not be a match , anymore )
      Without looking at signals in the system , you'll have to
      pull parts and manually test each one .
      ( Shotgun troubleshooting , guess and replace and hope the system works )
      not the best way to do it . As a last ditch effort , it might work .
      Those small silver caps are most likely solid tantalum .
      ( considering age of unit, i would have replaced the whole set )
      i noticed all the electrolytic caps looked good ,
      No rounded tops . No leakage .
      ( that doesn't mean these caps are actually good )
      just a level of Confidence that they still sufficiently work .
      Caps ,...the most dificult parts to make .
      Caps ,...the most failed components of all .
      ( if you had gone straight to the caps ,
      the relays could have been left alone )
      need a hot air wand\pencil to help remove those caps
      to help avoid tearing traces .
      Too sad no one has a schematic and parts locator diagram of a UPS .
      there is a lot going on in an UPS .
      If ups were simple , we would all build one .

    • @gumnahs
      @gumnahs 3 ปีที่แล้ว

      @@240mains thanks !

    • @coloradowilderness3139
      @coloradowilderness3139 3 ปีที่แล้ว

      @@240mains
      Well explained . Thanks

  • @layton3503
    @layton3503 3 ปีที่แล้ว

    I have a Backups XS 1500, has a similar problem, it does not detect AC, so the alarm sounds and it runs on Battery. I never hear any clicks from the relays. I pulled it apart and checked the simple stuff, but it's closing in on 20 years old. I appreciate the video, but not sure it's really worth replacing the caps. Everything is a risk . I think I am just replacing the unit, I will be lucky to get 20 years from the new one.

    • @z1power
      @z1power  3 ปีที่แล้ว

      No doubt a wise decision!

    • @Cadorna-Tagarna
      @Cadorna-Tagarna 3 ปีที่แล้ว

      I have a RS 1000 and a RS 800, the RS 800 stopped working, at no time did the relays sound, it just stopped detecting the input voltage correctly. What I did, was replace the capacitors and now it works like new. From what I have read it is a very common fault, it is easy to repair and with reliable results.
      The z1power video explains the problem and the solution very well, I hope you dare to repair it, there is already a lot of discarded hardware and it is always good to give old hardware a chance that is easy to repair to remain useful.

  • @dineshkumara9488
    @dineshkumara9488 2 ปีที่แล้ว

    1500 ups how voltage 12?, 24? Please help me

    • @z1power
      @z1power  2 ปีที่แล้ว +1

      24

  • @mrsunelectronics544
    @mrsunelectronics544 3 ปีที่แล้ว

    I just cannibalized the cheap devices as a good source of spare parts, as the output emits a horror bad sine wave, can damage devices! is not used with me.
    good video well explained .... keep it up

  • @ProjectCubase
    @ProjectCubase 2 ปีที่แล้ว

    Завтра такой же буду робить , все ,теж само

  • @luisalejandrorojasrondon6149
    @luisalejandrorojasrondon6149 2 ปีที่แล้ว

    Far directions tengo un ups. Model BN 1500 M2

  • @Eidany1
    @Eidany1 3 ปีที่แล้ว

    How to jumper limit shutdown apc 525. ic pic16c72a?

  • @andreaorlando8476
    @andreaorlando8476 ปีที่แล้ว

    hi could you help me with the same model? I hear a hiss coming from the main capacitor and moreover if I turn it off the two relays start to trip every 30 sec by themselves.the mainboard does not charge the batteries