Mastering APC Inverter Repair
APC UPS Inverter Repair and Troubleshooting
APC Inverter Repair Complete Guide
APC UPS Inverter Repair
Fixing APC Inverter Faults
Troubleshoot and Repair Your APC Inverter
APC Inverter Repair
Repairing APC UPS Inverter
#apc #apcups #ups #upsrepairing #inverter - วิทยาศาสตร์และเทคโนโลยี
This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me. I want everyone who has had problems with UPS devices, to know about him. He has an expert knowledge. That's why I write this comment on all his videos. I spent 4 nights without sleep looking for the problem. 👍
👍👍
ماشاءاللہ سر اللہ آپ کے علم میں اضافہ کرے بہت معلوماتی ویڈیو ہے۔
یہ ایسی ویڈیو بنائی ہے۔ کہ اگر آپ اس کو ایک بار تفصیل سے دیکھ لیں گے تو آپ کے APC 3KVA, 5KVA and 6KVA کو ریپئر کرنا نہایت آسان ہوجائیگا۔
سر اپ بالکل ٹھیک کہہ رہے ہیں بالکل ایسا ہی ہے میں اے پی سی لائن انٹریکٹو کا کام تو کر رہا ہوں لیکن ابھی آن لائن پر صحیح طرح سے کام نہیں کر سکتا اپ کی یہ ویڈیوز میری بھرپور رہنمائی کر رہی ہیں
Enjoy
Señor buen video gracias por compartir los conocimientos y ser tan profesional y colocar traductor a español saludos desde latinoamerica
Thanks brother
@@AKElectroTechbuenas tardes mi estimado, quisiera hacerle una consulta sobre la inyección de voltaje, en que componente lo solo las dos cables para las baterías de 24v, como no se ve bien nítido el vídeo no logro verlo, le agradecería muchísimo antemano por favor, gracias, está bueno el vídeo yo quisiera esa parte no más que me ayude.
Brother
I will try to make clear videos.
Thanks for your valuable comments
You are great sir
very well information sir
Very nice video And very easy explanation gate drivel pfc inverter igbt ......❤
Thanks
Very good information brother ❤
Kindly give feedback for improvement of videos
I already follows your procedure that is I check these voltages without transformer then I have connected multimeter at all the point where U1 & U2 should be present but there is no any voltage at these points like pin 4&7 of ic19/ pin4&7 of ic 21 neither pin2&7 of ic18 not pin10&16 of ic 18.
Good❤❤❤❤
Nc sir dc over voltage par vedio bnye
Ok
Sir I am already expert in repairing of inverters that is the resason that I have checked its gate drive, i have also changed it's ic18(H-driver) smd ic, i found there is no input signal at pin no 2 & 7, Also I found voltage is at pin 3 & 4 that goes out from it's pin 13 & 14 also at pin 10 & 15 that drive voltage is absent. I think it's ic21(361-0025v2) is perhaps faulty because there is no any voltage at pin 4 & 7 of this ic which goes to pin no 2 & 7 of ic18(H-driver)
Really informative. but must discharge DC bus it can be extremely harmful ..
Yes of course.
Safety first. All voltages must be checked and discharged before working on board.
Can you please explain PFC circuit in 3kva , I am repairing 9130 eaton
Ok
I will explain 9130 3kva soon. Pl wait
very very very good video 🏴🟩☑✅♥♥♥
Thanks
hi sir
can u pls make video of SURT5KVA charger failure fault rectification.
Yes
Pl wait for video or send your problem I will guide you. You can use wattsapp 00923215717132
sir aik video banyea ga kay is ups ko bgair battery kay kasy chalaye like one voltage stablizer kay tor pay kasy chalye
This UPS is designed with battery. If batteries are removed then you can't power On. I will create video on same topic
Nice information
Surt 2 kva KY drive ic check krny KY liye bhi iek video bnay
Ok
Hello sir, I am repairing APC surtd5000x UPS, I got high voltage output error in the display, can you help me? Which part should I check?
Hello
Pl check output capacitor 20uF
Thank you very much, dear friend, the 20 UF capacitor was broken and its value reached 6 uf , which was replaced and the output voltage errors were fixed.@AKElectrotech
@@AKElectroTech❤❤❤❤
Welcome
also APC's SRC3000UXI . SUA3000UXI , SRC3KVA models videos
Thses videos will be uploaded soon
tq ji waiting for same @@AKElectroTech
hi bro,
can u help me where is the problem when apc surt3000xli shows high output voltage error?
Replace Output capacitor or output sensing resistors
I replaced output capacitor and it Works. thank you alot, good teacher.@@AKElectroTech
AOA.sir maray ps ups aaya huwa hai 24v 2400va ka .is ma 20 fets lagay huwa hain usma say 11 fet short thay ar side ma driver transistor (ztx790) ar (2n2222) b short huway thay. To manay fets b change kia ar ztx 790 transistor k jagay Mps2907 transistor laga dia to abi masla ya aaraha hai k ak side k saray Fets garam horahay hain .samaj nai aaraha kya masla hosakta hai barai meherbani rehnumai karain
WAS
Pl tell me model and company
@@AKElectroTech apc ups hai 2400va likha huwa hai 24 volt ma
Pl check power supply voltage which needed for driver stage. If your both transistors are short then apply may be damaged because +ve supply attached on collector of 2N2222 and -ve or Gnd on collector of ZTX790 and output driven by emitters of both transistors to power stage.
Pl also check circuit behind both transistors.
Now come to final checking procedure.
Connect 02 batteries to board without power transformer and switch on UPS. Check 12VDC on both outer side inverter plates. If 12V is coming then your UPS is Ok other wise check that driver stage which is not delivering 12VDC
@@AKElectroTech jazakallah sir g for ur kind info.
@@AKElectroTech i ve already checked all the voltages on the board. Also checked the voltage on collector of both ( ztx790 & mps2222) .and i also checked amps of transformer from h bridge which was 15 amp without load is that correct?
How to check gate drive of this ups, sir in my apc smart 1500 ups gate drive of +ve chennel is missing results no output how to repair this problem please help me.
Pl mention your board as smart 1500VA smd and version like 4G or 3.6G
only SUA1500I-IN is written on backside & smart 1500 is written front side this UPS. All this components are smd
If you share you whatsapp number I will send you it's pics
Pl remove transformer and check board without transformer. Check -8v at pin 1 and 12V at pin 16 of ic19 then check 5vDC voltage at pins 6 and 7 which are going to IC 21 pins 2 and 5. IC21 will generate 5v at pins 4 and 7 which will apply IC 18 pins 2 and 7. Remember these voltage will present when you will power on board. During fault this will disappear.
You told me to check 5vdc on pin 6 & 7 which are going to ic 21 pin 2 & 5. But Pin2 of ic 21 is from pin 5 of ic19. Voltages at pin 2 & 5 of ic21 L1in & L2in are ok & it's output from pin 3 & 6 L1out & L2out is also OK but in my case ic21 pin 4&7 U1out & U2out is missing that is the reason these voltages (U1out & U2out are not present at gate of both +ve chennels.
sir is ki schematic mill sakty hay ?
I am doing reverse engineering.
کیا میرے کام سے لگتا ہے۔ کہ میرے پاس سب کچھ ہے۔ یہ شارٹ کٹ کیز shortcut keys میری اپنی ریسرچ ہے۔ مطلب کہ میں اس طرح کام کرتا ہوں۔
@@AKElectroTech sir app ki video say hi lag raha hay app bhot achy hain . bhot nice , app please reverse engineering kar kay is ka or 2kva ka schematic please share karyea ga or mazeed asy information say bhary video share karyea ga or 4 battery wala 5kva apc us pay bhi videos banayea ga
main nay aik russian channel dakha tha unho nay bhi schematic banaye hoye thi but unho nay dainy say inkar kar dia tha . remont.ru tha shayeed channel
میں اس طرح سے ویڈیوز بنانے کی کوشش کرتا ہوں۔ تاکہ آپ لوگوں کو ذیادہ سے ذیادہ فائدہ ہو۔
Need solution for 5kva ideal condition
What type of solution you need for 5kva ups ?
Ups in ideal condition after ac and DC given also
Control card is good.. no short in main board but ups is not getting ON
Are you sure that your control card is Ok. Pl check it.
Kindly tell about your UPS model ie 5kva SURT or SURTD model.
السلام علیکم سر میرے پاس D ماڈل کا 5KW کا ایک APC یو پی ایس ہے جس کا PFC جلا ہوا ہے۔ اس کا صرف پازیٹو PFC جلا ہے۔ چونکہ پازیٹو PFC اور BBPFC کے ٹرانسسٹر ایک ہی ہیٹ سنک پر ہوتے ہیں اس لیے میں نے دونوں قسم کے ٹرانسسر نکال لیے ۔پازیٹو PFCکے ٹرانسسٹر اور اس کا آپٹو کپلر بھی جلا ہوا تھا جسے میں نے تبدیل کر دیا۔ اب ٹرانسسٹر لگانے سے پہلے جب سگنل چیک کیا تو پازیٹو پی ایف سی کے گیٹ اور ایمٹر پر تقریبا 12 وولٹ DC ارہے ہیں اور فریکوئنسی تقریبا 31KHz ہے۔جبکہ آپٹو کپلر کی input پر فریکونسی 25KHz ہے۔ جبکہ BBPFC جو کہ نہیں جلا تھا اس پر سگنل 4V سے 5V تک اتا ہے اور فریکونسی 7KHz سے 12KHz تک تبدیل ہوتی ہے۔ جب کہ کنٹرولر کارڈ میں لگے ہوئے دونوں سائیڈ کے FET ٹھیک ہیں۔ سر رہنمائی فرمائیں کیا یہ سگنل ٹھیک ہیں یا غلط ہیں ۔اور اگر یہ سگنل ٹھیک نہیں تو مجھے کیا کرنا چاہیے ۔
وعلیکم السلام
یہ Input line voltage پہ فریکوینسی 25KHerts ہوگی۔اور بیٹری پہ 30kherts ہوگی۔ جیسے آپکے UPS میں مسئلہ ہے۔ ان پٹ لائن پہ BB PFCاستعمال نہی ہوتا۔ پوزیٹو اور نیگیٹو PFC کام کرتا ہے۔ اور بیٹری پہ نیگیٹو PFCکام نہی کرتا باقی دو کرتے ہیں۔ آپ کے UPS میں BB والی سائڈ پی وولٹ کم آرہے ہیں۔ اگر میرے بتائے ہوئے طریقے سے آپ کا پاور بورڈ PSDR board ٹھیک ہے۔ تو کنٹرول پہ آجائیے۔ آپ کنٹرول پہبQ39 چیک کرلیں اگر یہ ٹھیک ہو تو IC37 کو چیک کریں۔
السلام علیکم سر آپ کے کہنے کے مطابق میں نے کنٹرولر بورڈ میں Q39اور IC37 کو چیک کیا دونوں ہی ٹھیک ہیں اس کے بعد مین کنٹرولر IC سے آنے والے سگنل کو چیک کیا (جس کوسرکٹ ڈایاگرام میں BB_PWM_TTL اور PPFC_PWM_TTL سے ظاہر کیا گیا ہے) اس میں PPFC والا سگنل ٹھیک تھا جبکہ BB_PFC والا سگنل ویسے ہی وولٹیج اور فریکونسی دونوں تبدیل کر رہا تھا۔ رہنمائی فرمائیں کہ اب میں کیا چیز چیک کروں۔
ابھی اس کا Main controller IC جس کا نمبر TMS320F2810 ہے۔ اس کا مسئلہ ہی ہے۔ اس کو آپ تبدیل کردیں۔ لیکن ایک بات یاد رکھیں کہ نئی ic نہی چلے گی۔
ظاہر ہے جب تک فرم ویئر نہیں ہوگا نیا کنٹرولر نہیں چل سکتا۔ اس کا مطلب ہے پورا کنٹرولر کارڈ ہی تبدیل کریں کیا یہ کنٹرولر کارڈ مل جاتا ہے ؟
جی ہاں۔
کنٹرول کارڈ مل جاتا ہے۔
سر جی میرے یوپی ایس میں لوڈ نھیں دکھا رھا کہ کتنا ھوگیا ھے کیونکہ لوڈ والی کوئی لائٹ نھیں جل رھی دوسری بات یہ کہ بیٹری کی صرف ایک لائٹ جل رھی ھے آخری سیل دکھا رھا ھے
پلیز ماڈل بتا دیجئے
@@AKElectroTech APC 1500
smart
پلیز آپ IC 4 اور IC5 اور اس کے نزدیک والے رسسٹرز کو چیک کرلیں۔ آپ کا مسئلہ حل ہوجائیگا
Apka contact number
+923215717132 wattsapp