  • @test0957
    @test0957 หลายเดือนก่อน

    This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me. I want everyone who has had problems with UPS devices, to know about him. He has an expert knowledge. That's why I write this comment on all his videos. I spent 4 nights without sleep looking for the problem. 👍
    👍👍

  • @fayyazahmad5813
    @fayyazahmad5813 9 หลายเดือนก่อน

    ماشاءاللہ سر اللہ آپ کے علم میں اضافہ کرے بہت معلوماتی ویڈیو ہے۔

    • @AKElectroTech
      @AKElectroTech  9 หลายเดือนก่อน

      یہ ایسی ویڈیو بنائی ہے۔ کہ اگر آپ اس کو ایک بار تفصیل سے دیکھ لیں گے تو آپ کے APC 3KVA, 5KVA and 6KVA کو ریپئر کرنا نہایت آسان ہوجائیگا۔

    • @fayyazahmad5813
      @fayyazahmad5813 9 หลายเดือนก่อน

      سر اپ بالکل ٹھیک کہہ رہے ہیں بالکل ایسا ہی ہے میں اے پی سی لائن انٹریکٹو کا کام تو کر رہا ہوں لیکن ابھی آن لائن پر صحیح طرح سے کام نہیں کر سکتا اپ کی یہ ویڈیوز میری بھرپور رہنمائی کر رہی ہیں

    • @AKElectroTech
      @AKElectroTech  9 หลายเดือนก่อน

      Enjoy

  • @orlandoponce9200
    @orlandoponce9200 5 หลายเดือนก่อน +1

    Señor buen video gracias por compartir los conocimientos y ser tan profesional y colocar traductor a español saludos desde latinoamerica

    • @AKElectroTech
      @AKElectroTech  5 หลายเดือนก่อน

      Thanks brother

    • @carlosnacionvelasquez7336
      @carlosnacionvelasquez7336 2 หลายเดือนก่อน +1

      ​@@AKElectroTechbuenas tardes mi estimado, quisiera hacerle una consulta sobre la inyección de voltaje, en que componente lo solo las dos cables para las baterías de 24v, como no se ve bien nítido el vídeo no logro verlo, le agradecería muchísimo antemano por favor, gracias, está bueno el vídeo yo quisiera esa parte no más que me ayude.

    • @AKElectroTech
      @AKElectroTech  2 หลายเดือนก่อน

      Brother
      I will try to make clear videos.
      Thanks for your valuable comments

  • @zwarrior3398
    @zwarrior3398 6 หลายเดือนก่อน +1

    You are great sir

  • @starplannersstar7353
    @starplannersstar7353 8 หลายเดือนก่อน

    very well information sir

  • @akashwankar2210
    @akashwankar2210 7 หลายเดือนก่อน

    Very nice video And very easy explanation gate drivel pfc inverter igbt ......❤

  • @naeemtariq2526
    @naeemtariq2526 9 หลายเดือนก่อน

    Very good information brother ❤

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      Kindly give feedback for improvement of videos

  • @TechnicalAlrounder
    @TechnicalAlrounder 8 หลายเดือนก่อน +1

    I already follows your procedure that is I check these voltages without transformer then I have connected multimeter at all the point where U1 & U2 should be present but there is no any voltage at these points like pin 4&7 of ic19/ pin4&7 of ic 21 neither pin2&7 of ic18 not pin10&16 of ic 18.

  • @sonyelectronicsgw7462
    @sonyelectronicsgw7462 8 หลายเดือนก่อน +1

    Good❤❤❤❤

  • @srana7804
    @srana7804 5 หลายเดือนก่อน

    Nc sir dc over voltage par vedio bnye

  • @TechnicalAlrounder
    @TechnicalAlrounder 8 หลายเดือนก่อน

    Sir I am already expert in repairing of inverters that is the resason that I have checked its gate drive, i have also changed it's ic18(H-driver) smd ic, i found there is no input signal at pin no 2 & 7, Also I found voltage is at pin 3 & 4 that goes out from it's pin 13 & 14 also at pin 10 & 15 that drive voltage is absent. I think it's ic21(361-0025v2) is perhaps faulty because there is no any voltage at pin 4 & 7 of this ic which goes to pin no 2 & 7 of ic18(H-driver)

  • @Munawarkhan107
    @Munawarkhan107 4 หลายเดือนก่อน

    Really informative. but must discharge DC bus it can be extremely harmful ..

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน

      Yes of course.
      Safety first. All voltages must be checked and discharged before working on board.

  • @Munawarkhan107
    @Munawarkhan107 4 หลายเดือนก่อน

    Can you please explain PFC circuit in 3kva , I am repairing 9130 eaton

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน

      Ok
      I will explain 9130 3kva soon. Pl wait

  • @MuhammadIqbal-zc9jy
    @MuhammadIqbal-zc9jy 2 หลายเดือนก่อน +1

    very very very good video 🏴🟩☑✅♥♥♥

  • @rajukv5915
    @rajukv5915 4 หลายเดือนก่อน

    hi sir
    can u pls make video of SURT5KVA charger failure fault rectification.

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน

      Yes
      Pl wait for video or send your problem I will guide you. You can use wattsapp 00923215717132

  • @starplannersstar7353
    @starplannersstar7353 8 หลายเดือนก่อน

    sir aik video banyea ga kay is ups ko bgair battery kay kasy chalaye like one voltage stablizer kay tor pay kasy chalye

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน +1

      This UPS is designed with battery. If batteries are removed then you can't power On. I will create video on same topic

    • @amitcreativeupsworld6083
      @amitcreativeupsworld6083 8 หลายเดือนก่อน

      Nice information

  • @naeemtariq2526
    @naeemtariq2526 9 หลายเดือนก่อน

    Surt 2 kva KY drive ic check krny KY liye bhi iek video bnay

  • @user-wt6oz2bz1x
    @user-wt6oz2bz1x 4 หลายเดือนก่อน +1

    Hello sir, I am repairing APC surtd5000x UPS, I got high voltage output error in the display, can you help me? Which part should I check?

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน +1

      Hello
      Pl check output capacitor 20uF

    • @user-wt6oz2bz1x
      @user-wt6oz2bz1x 4 หลายเดือนก่อน +1

      Thank you very much, dear friend, the 20 UF capacitor was broken and its value reached 6 uf , which was replaced and the output voltage errors were fixed.​@AKElectrotech

    • @user-wt6oz2bz1x
      @user-wt6oz2bz1x 4 หลายเดือนก่อน +1

      ​@@AKElectroTech❤❤❤❤

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน

      Welcome

  • @rajukv5915
    @rajukv5915 4 หลายเดือนก่อน

    also APC's SRC3000UXI . SUA3000UXI , SRC3KVA models videos

    • @AKElectroTech
      @AKElectroTech  4 หลายเดือนก่อน

      Thses videos will be uploaded soon

    • @rajukv5915
      @rajukv5915 4 หลายเดือนก่อน

      tq ji waiting for same @@AKElectroTech

  • @emsa_co
    @emsa_co 6 หลายเดือนก่อน

    hi bro,
    can u help me where is the problem when apc surt3000xli shows high output voltage error?

    • @AKElectroTech
      @AKElectroTech  6 หลายเดือนก่อน +1

      Replace Output capacitor or output sensing resistors

    • @emsa_co
      @emsa_co 6 หลายเดือนก่อน

      I replaced output capacitor and it Works. thank you alot, good teacher.@@AKElectroTech

  • @sardarmuhammad405
    @sardarmuhammad405 7 หลายเดือนก่อน

    AOA.sir maray ps ups aaya huwa hai 24v 2400va ka .is ma 20 fets lagay huwa hain usma say 11 fet short thay ar side ma driver transistor (ztx790) ar (2n2222) b short huway thay. To manay fets b change kia ar ztx 790 transistor k jagay Mps2907 transistor laga dia to abi masla ya aaraha hai k ak side k saray Fets garam horahay hain .samaj nai aaraha kya masla hosakta hai barai meherbani rehnumai karain

    • @AKElectroTech
      @AKElectroTech  7 หลายเดือนก่อน

      WAS
      Pl tell me model and company

    • @sardarmuhammad405
      @sardarmuhammad405 7 หลายเดือนก่อน

      @@AKElectroTech apc ups hai 2400va likha huwa hai 24 volt ma

    • @AKElectroTech
      @AKElectroTech  7 หลายเดือนก่อน

      Pl check power supply voltage which needed for driver stage. If your both transistors are short then apply may be damaged because +ve supply attached on collector of 2N2222 and -ve or Gnd on collector of ZTX790 and output driven by emitters of both transistors to power stage.
      Pl also check circuit behind both transistors.
      Now come to final checking procedure.
      Connect 02 batteries to board without power transformer and switch on UPS. Check 12VDC on both outer side inverter plates. If 12V is coming then your UPS is Ok other wise check that driver stage which is not delivering 12VDC

    • @sardarmuhammad405
      @sardarmuhammad405 6 หลายเดือนก่อน

      @@AKElectroTech jazakallah sir g for ur kind info.

    • @sardarmuhammad405
      @sardarmuhammad405 6 หลายเดือนก่อน

      @@AKElectroTech i ve already checked all the voltages on the board. Also checked the voltage on collector of both ( ztx790 & mps2222) .and i also checked amps of transformer from h bridge which was 15 amp without load is that correct?

  • @TechnicalAlrounder
    @TechnicalAlrounder 8 หลายเดือนก่อน

    How to check gate drive of this ups, sir in my apc smart 1500 ups gate drive of +ve chennel is missing results no output how to repair this problem please help me.

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      Pl mention your board as smart 1500VA smd and version like 4G or 3.6G

    • @TechnicalAlrounder
      @TechnicalAlrounder 8 หลายเดือนก่อน

      only SUA1500I-IN is written on backside & smart 1500 is written front side this UPS. All this components are smd

    • @TechnicalAlrounder
      @TechnicalAlrounder 8 หลายเดือนก่อน

      If you share you whatsapp number I will send you it's pics

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      Pl remove transformer and check board without transformer. Check -8v at pin 1 and 12V at pin 16 of ic19 then check 5vDC voltage at pins 6 and 7 which are going to IC 21 pins 2 and 5. IC21 will generate 5v at pins 4 and 7 which will apply IC 18 pins 2 and 7. Remember these voltage will present when you will power on board. During fault this will disappear.

    • @TechnicalAlrounder
      @TechnicalAlrounder 8 หลายเดือนก่อน

      You told me to check 5vdc on pin 6 & 7 which are going to ic 21 pin 2 & 5. But Pin2 of ic 21 is from pin 5 of ic19. Voltages at pin 2 & 5 of ic21 L1in & L2in are ok & it's output from pin 3 & 6 L1out & L2out is also OK but in my case ic21 pin 4&7 U1out & U2out is missing that is the reason these voltages (U1out & U2out are not present at gate of both +ve chennels.

  • @starplannersstar7353
    @starplannersstar7353 8 หลายเดือนก่อน

    sir is ki schematic mill sakty hay ?

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน +1

      I am doing reverse engineering.

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน +1

      کیا میرے کام سے لگتا ہے۔ کہ میرے پاس سب کچھ ہے۔ یہ شارٹ کٹ کیز shortcut keys میری اپنی ریسرچ ہے۔ مطلب کہ میں اس طرح کام کرتا ہوں۔

    • @starplannersstar7353
      @starplannersstar7353 8 หลายเดือนก่อน

      @@AKElectroTech sir app ki video say hi lag raha hay app bhot achy hain . bhot nice , app please reverse engineering kar kay is ka or 2kva ka schematic please share karyea ga or mazeed asy information say bhary video share karyea ga or 4 battery wala 5kva apc us pay bhi videos banayea ga

    • @starplannersstar7353
      @starplannersstar7353 8 หลายเดือนก่อน

      main nay aik russian channel dakha tha unho nay bhi schematic banaye hoye thi but unho nay dainy say inkar kar dia tha . remont.ru tha shayeed channel

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน +1

      میں اس طرح سے ویڈیوز بنانے کی کوشش کرتا ہوں۔ تاکہ آپ لوگوں کو ذیادہ سے ذیادہ فائدہ ہو۔

  • @sureshv6748
    @sureshv6748 8 หลายเดือนก่อน

    Need solution for 5kva ideal condition

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      What type of solution you need for 5kva ups ?

    • @sureshv6748
      @sureshv6748 8 หลายเดือนก่อน

      Ups in ideal condition after ac and DC given also

    • @sureshv6748
      @sureshv6748 8 หลายเดือนก่อน

      Control card is good.. no short in main board but ups is not getting ON

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      Are you sure that your control card is Ok. Pl check it.

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      Kindly tell about your UPS model ie 5kva SURT or SURTD model.

  • @fayyazahmad5813
    @fayyazahmad5813 8 หลายเดือนก่อน

    السلام علیکم سر میرے پاس D ماڈل کا 5KW کا ایک APC یو پی ایس ہے جس کا PFC جلا ہوا ہے۔ اس کا صرف پازیٹو PFC جلا ہے۔ چونکہ پازیٹو PFC اور BBPFC کے ٹرانسسٹر ایک ہی ہیٹ سنک پر ہوتے ہیں اس لیے میں نے دونوں قسم کے ٹرانسسر نکال لیے ۔پازیٹو PFCکے ٹرانسسٹر اور اس کا آپٹو کپلر بھی جلا ہوا تھا جسے میں نے تبدیل کر دیا۔ اب ٹرانسسٹر لگانے سے پہلے جب سگنل چیک کیا تو پازیٹو پی ایف سی کے گیٹ اور ایمٹر پر تقریبا 12 وولٹ DC ارہے ہیں اور فریکوئنسی تقریبا 31KHz ہے۔جبکہ آپٹو کپلر کی input پر فریکونسی 25KHz ہے۔ جبکہ BBPFC جو کہ نہیں جلا تھا اس پر سگنل 4V سے 5V تک اتا ہے اور فریکونسی 7KHz سے 12KHz تک تبدیل ہوتی ہے۔ جب کہ کنٹرولر کارڈ میں لگے ہوئے دونوں سائیڈ کے FET ٹھیک ہیں۔ سر رہنمائی فرمائیں کیا یہ سگنل ٹھیک ہیں یا غلط ہیں ۔اور اگر یہ سگنل ٹھیک نہیں تو مجھے کیا کرنا چاہیے ۔

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      وعلیکم السلام
      یہ Input line voltage پہ فریکوینسی 25KHerts ہوگی۔اور بیٹری پہ 30kherts ہوگی۔ جیسے آپکے UPS میں مسئلہ ہے۔ ان پٹ لائن پہ BB PFCاستعمال نہی ہوتا۔ پوزیٹو اور نیگیٹو PFC کام کرتا ہے۔ اور بیٹری پہ نیگیٹو PFCکام نہی کرتا باقی دو کرتے ہیں۔ آپ کے UPS میں BB والی سائڈ پی وولٹ کم آرہے ہیں۔ اگر میرے بتائے ہوئے طریقے سے آپ کا پاور بورڈ PSDR board ٹھیک ہے۔ تو کنٹرول پہ آجائیے۔ آپ کنٹرول پہبQ39 چیک کرلیں اگر یہ ٹھیک ہو تو IC37 کو چیک کریں۔

    • @fayyazahmad5813
      @fayyazahmad5813 8 หลายเดือนก่อน

      السلام علیکم سر آپ کے کہنے کے مطابق میں نے کنٹرولر بورڈ میں Q39اور IC37 کو چیک کیا دونوں ہی ٹھیک ہیں اس کے بعد مین کنٹرولر IC سے آنے والے سگنل کو چیک کیا (جس کوسرکٹ ڈایاگرام میں BB_PWM_TTL اور PPFC_PWM_TTL سے ظاہر کیا گیا ہے) اس میں PPFC والا سگنل ٹھیک تھا جبکہ BB_PFC والا سگنل ویسے ہی وولٹیج اور فریکونسی دونوں تبدیل کر رہا تھا۔ رہنمائی فرمائیں کہ اب میں کیا چیز چیک کروں۔

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      ابھی اس کا Main controller IC جس کا نمبر TMS320F2810 ہے۔ اس کا مسئلہ ہی ہے۔ اس کو آپ تبدیل کردیں۔ لیکن ایک بات یاد رکھیں کہ نئی ic نہی چلے گی۔

    • @fayyazahmad5813
      @fayyazahmad5813 8 หลายเดือนก่อน

      ظاہر ہے جب تک فرم ویئر نہیں ہوگا نیا کنٹرولر نہیں چل سکتا۔ اس کا مطلب ہے پورا کنٹرولر کارڈ ہی تبدیل کریں کیا یہ کنٹرولر کارڈ مل جاتا ہے ؟

    • @AKElectroTech
      @AKElectroTech  8 หลายเดือนก่อน

      جی ہاں۔
      کنٹرول کارڈ مل جاتا ہے۔

  • @AminKhan-uo6vv
    @AminKhan-uo6vv หลายเดือนก่อน +1

    سر جی میرے یوپی ایس میں لوڈ نھیں دکھا رھا کہ کتنا ھوگیا ھے کیونکہ لوڈ والی کوئی لائٹ نھیں جل رھی دوسری بات یہ کہ بیٹری کی صرف ایک لائٹ جل رھی ھے آخری سیل دکھا رھا ھے

    • @AKElectroTech
      @AKElectroTech  หลายเดือนก่อน

      پلیز ماڈل بتا دیجئے

    • @AminKhan-uo6vv
      @AminKhan-uo6vv หลายเดือนก่อน

      @@AKElectroTech APC 1500

    • @AminKhan-uo6vv
      @AminKhan-uo6vv หลายเดือนก่อน +1

      smart

    • @AKElectroTech
      @AKElectroTech  หลายเดือนก่อน

      پلیز آپ IC 4 اور IC5 اور اس کے نزدیک والے رسسٹرز کو چیک کرلیں۔ آپ کا مسئلہ حل ہوجائیگا

  • @qamarabbas1440
    @qamarabbas1440 2 หลายเดือนก่อน

    Apka contact number

    • @AKElectroTech
      @AKElectroTech  2 หลายเดือนก่อน

      +923215717132 wattsapp