APC SURTD UPS Control Card Repair Guide: Step-by-Step Tutorial
ฝัง
- เผยแพร่เมื่อ 20 ต.ค. 2023
- #apc #ups
APC SURTD UPS Control Card Repair Guide: Step-by-Step Tutorial
APC SURTD UPS
Control Card Repair
UPS Control Card Repair
APC Online SURTD UPS
Uninterruptible Power Supply Repair
DIY UPS Repair
Step-by-Step Tutorial
Electronics Repair
Circuit Board Fix
Troubleshooting UPS Control Card
How to Fix a UPS
Revive Dead UPS
APC UPS Maintenance
control circuit of apc ups
dead ups repairing
apc ups control board
#apc #ups #upsrepairing #inverter #akelectrotech
This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me. I want everyone who has had problems with UPS devices, to know about him. He has an expert knowledge. That's why I write this comment on all his videos. I spent 4 nights without sleep looking for the problem. 👍
👍👍
ماشاءاللہ سر ایک اور معلوماتی ویڈیو دیکھ کر خوشی ہوئی اللہ اپ کے علم اضافہ فرمائے
sir ji . i want to down load SW from ST72324 MCU which is used in APC BI850sine Inverter ..can u pls suggest how to do that . I have CH341A in my hand
Ola amigo, voce vende placa de controle surt 6000,
Hello friend
No at this time.
Greeting sir, I have a surtd 3000xli showing the error 00010 I replaced the control board with a new one, and the error is fixed. Can you help me sir where is the fault in faulty control board. Thanks in advance
@PakGuides
This fault 00010 is related with backfired relays. Backfeed means that AC input relays are not operating.
There may be so many issues in control card.
1. Backfeed relays are operated by IC18 (ULN2003). Check wiring pin 13 of this ic to backfeed relays.
2. It is possible that controller stop back feed relays due to not sensing AC input. You can check D23, IC35 and IC27 and related components.
This portion is used for AC sensing.
3. It is possible that ADC is not sensing AC references at pin_120 and pin_121.
@@AKElectroTech sir, bundle of thanks
olá tenho uma placa de controle do SURT 6KVA com falha PFC como eu faço pra resolver essa falha
Hello
Which PFC side is not working.
Pl follow these steps
Install batteries in ups and apply input voltage to ups. UPS power supply will activated and check DC positive bus on d716 and DC negative bus on d715.
Now which bus side is not working on supplying input power to ups.
a placa de controle assim que colocar a tensão de entrada ele já dispara o disjuntor da bancada. Não dar tempo de verificar as tensão positiva e tensão negativa no diodo.@@AKElectroTech
@@mailsonfreitas3967
You mean that input circuit breaker tripped when applying input voltage to ups. If this condition appears then check input circuit of PSDR board.
Otherwise follow these steps:
Connect batteries to ups and connect dmm negative lead to battery black and positive lead on d716. Now switch 'ON' ups on battery and check DC voltage on this diode. Same for d715 diode and check DC voltage.
Also check that ups is normal functioning on battery or going to pfc fault state.
Then apply input voltage and repeat same procedure.
I hope you will find any solution
APC SMT ka kuch dair baad AVR relay weld aa jata hay,
AVR proper function kar raha hota hay.
Supply card na laga ho to yeh issue aata hay
AVR relay or relay driver circuit mat be faulty.
hi bro,
where is connection of cathode of diode 24(D24) that is below 74htc245(ic 19)?
this diode of control board was burnt but cathode of that has no connection with everywhere?
Brother
D23 is used after input transformer on PSDR board and convert AC sensing in to DC voltage and connect it to D24. D24 received 24VDC from D23 and 24V_SW from LV power supply from PSDR board.
D24 cathode connected with R182 parrallel with R250. Both R182 and R250 are 100 Ohm.
@@AKElectroTech thanks alot. You helped me well.
Hi bro,
Please take a video about ((backfeed relay weld)) fault in apc ups.
When this fault happens,led 2 from down to top turning on.
Ok
@@emsa_co
It is the reflection of lower LED. Only one is glowing with fault LED
olá amigo!! tenho surt6000kva xli ta com falha DC BUS OVERVOLTAGE eu identifiquei que o problema tá na placa de controle. a tensão no diodo 716 tem 200 volts no diodo no 715 tem 67volts. você pode me ajudar.
Dear friend
How do you identify control board?
Connect batteries and apply input voltage. Now check D716 and D715 for +ve and -ve bus.
já verifiquei mas as tensão estão baixo@@AKElectroTech
já coloquei a placa de contro em outro surt6kva deu a mesma falha
@@mailsonfreitas3967
Install Ok control board to this faulty ups and check status
ele funcionou ... perfeitamente.. @@AKElectroTech
Sir 2 kva online apc ups kay pfc feedback control pay video banyea .
Oķ
Dear Sir, Can you make a video on Error: 01010.
Yes
This is charger fault. I will create video on it
sir 5kva mai fan error kese clear krna haia
replace fan or drive where connector is connected. IC36 and Q36 are used for fan drive and fan error
@@AKElectroTech sir aik capactor damage hai control pe number hai uska 33 35v L09 fan on na huni waja ye tu nhi kia
@@rizwanullah2892 These all capacitors 33uf35v are connected on power supply portion. What is L09 and where this is located
@@AKElectroTech 33uf35v l09 is complete model number of capactor sir .
Ok replace it if it is damaged.
sir how to repair apc error p13
Please go to event log for detail and check the fault code.
Clear its alarms.
Go to configuration and reset factory default
Inverter hardware ckt
Check inverter portion
Is unit Ka software kase kartay hain
اس پہ بھی جلد ہی ایک ویڈیو بناونگا۔
اس کی کیبل ایک طرف سے سیریل اور دوسری طرف سے RJ45 سے ہو گا۔
Battery calibration Nahi Hoti..
I mean 0 ke value
بیٹری کی تاریخ تبدیل کردیں۔ مسئلہ حل ہوجائے گا
سر مجھے اس UPS کے PFC کو ریپیئر کرنے میں پرابلم ہو رہی ہے میں نے پہلے دو دفعہ اپ کو کمنٹ کیے جس میں میں نے اپنا فون نمبر دیا تھا لیکن وہ دونوں دفعہ کمنٹ ڈیلیٹ ہو گئے سر مجھے آپ کی مدد چاہیے
اچھا میں جلد ہی PFC اور Inverter پہ تفصیل سے ویڈیو بنا کے اپ لوڈ کرونگا۔
سر پی ایف سی کے ٹرانسسٹر لگانے کے بعد جب یوپی ایس کو آن کرتا ہوں تو جب پی ایف سی کام کرنا شروع کرتا ہے تو نہت زیادہ کرنٹ لیتا ہے
دو چیزیں ہیں۔ ایک کنٹرول کارڈ اور دوسرا پی ایس ڈی آر PSDR بورڈ۔
پہلے یہ تعین کرلیں کہ کنٹرول کارڈ ٹھیک ہے یا PSDR بورڈ ۔
پلیز C807 کپیسٹر پہ 24 وولٹ دیں۔ اس کے بعد inverter and PFC کے Opto driver چیک کرلیں۔ وہاں پہ 17 وولٹ آرہے ہونگے۔ آپ ان Optos کو 2 وولٹ دے کر چیک کرلیں۔
سر آپ کے بتائے ہوئے طریقے کے مطابق میں نے اپٹو کپلر چیک کیے ہیں سارے ٹھیک کام کر رہے ہیں