Configuring Danfoss VLT Drives for Two Wire Start / Stop with Speed Up / Down || Digicon Automation
ฝัง
- เผยแพร่เมื่อ 3 ต.ค. 2024
- || Two wire start stop with Speed up / down push button application ||
Parameter list for Two wire start stop with speed up and speed down application :
1-20 = Motor Power [kW] [hp]
1-22 = Motor Voltage
1-23 = Motor Frequency
1-24 = Motor current
1-25 = Motor Nominal Speed
3-41 = Acceleration Time
3-42 = Deceleration Time
5-10 = [ 8 ] Start
5-12 = [ 19 ] Freeze - reference
5-13 = [ 21 ] Speed- up
5-15 = [ 22 ] Speed- down
Very nice explain and informative video's keep it up on regular in new topicc
Hi can u help me to Wire this. Once the RTD senses Hig Temp. The Danfoss Controller Increase the Frequency Signal Output to Motor.
coloco os mesmos parametros e o inversor não funciona o speed up e speed down, o que pode ser?
Sir apka video dekhke drive chalu kiya to huwa nahi
What is 3 wire control?
What is meant by freeze reference
It's Freezes the actual reference, which is now the
point of enable/condition for [21] Speed up and [22] Speed down to be used.
Sir yehi parameter daale maine drive chl nhi rahi h pehle PLC se oprate krte the drive ko mainual chl nhi rahi h micro 51 h vlt hi h
First you have to factory reset your drive and then, enter the parameters.
@@DIGICONAUTOMATION ok sir tnx
4 k 22 me 2 enter krne pr hoga na reset
@@tarsemsingh8570 14-22 = 2