Orientation and Configuration of Danfoss VLT FC 051/ FC 360 / FC 101 Drives || Digicon Automation

แชร์
ฝัง
  • เผยแพร่เมื่อ 3 ต.ค. 2024
  • || Three wire start stop with speed POT application ||
    Parameter list for Three wire start stop with speed POT application :
    1-20 = Motor Power [kW] [hp]
    1-22 = Motor Voltage
    1-23 = Motor Frequency
    1-24 = Motor current
    1-25 = Motor Nominal Speed
    3-15 = [ 1 ] Analog Input 53
    3-16 = [ 0 ] No function
    3-41 = Acceleration Time
    3-42 = Deceleration Time
    5-10 = [ 9 ] Latched start
    5-12 = [ 6 ] Stop inverse

ความคิดเห็น • 91

  • @vijaysharma-qn6nx
    @vijaysharma-qn6nx 4 ปีที่แล้ว +2

    thanks sir..very important knowledge.....SV Electronnics Nanded maharashtra

  • @PraveenKumar-qr8mc
    @PraveenKumar-qr8mc 4 ปีที่แล้ว +2

    Hello
    Thanks for the wonderful video. I'm using Danfoss VLT HVAC Basic Drive FC 101 and want to use pushbutton for speed up and down. But I noticed there is no terminal 33. As per the manuals, only model Danfoss VLT micro drive FC 51 and VLT automaton drive have terminal 33. Please advise how to use pushbutton for speed up and down for Danfoss VLT HVAC Basic Drive FC 101.
    Thank You

  • @peternauta
    @peternauta 3 ปีที่แล้ว +1

    Which language is this?

  • @gurpreetsinghpreet3280
    @gurpreetsinghpreet3280 ปีที่แล้ว

    Very very nice sir.

  • @ZeeshanSiddique-b7k
    @ZeeshanSiddique-b7k 8 หลายเดือนก่อน

    Very Good working

  • @jaiprakashgupta3332
    @jaiprakashgupta3332 11 หลายเดือนก่อน

    i want to know about terminal 20 and 33 setting i am using this terminal for over limit

  • @Bharataryans
    @Bharataryans ปีที่แล้ว

    How can we replace it with old drive of commercial trademill ??

  • @rameshpatil8065
    @rameshpatil8065 5 ปีที่แล้ว +1

    very helpful video

  • @subdaralam5050
    @subdaralam5050 3 ปีที่แล้ว +1

    Sir jaise Ham bahar se start stop push button use karnah aur drive ka potential use karna hai

  • @sdengineers1742
    @sdengineers1742 3 ปีที่แล้ว +1

    AM DL Sharma From Rajasthan Am Use FC 360 Drive .
    Our issue
    We Use Control card In 5.5 hp DRIVE then Run The Drive But Used this Control Card in 1.5 kw 2hp then COME Al 38
    Same Control Card Run in 5.5 hp But 2 hp Not Run come Al 38
    so Plz Tell How to Remove Al 38 In Control Card.

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  3 ปีที่แล้ว

      Alarm 38 for Internal fault, You need to update the software version of VFD to reset this Alarm

  • @ppremkumarpremkumar6822
    @ppremkumarpremkumar6822 3 ปีที่แล้ว +1

    How to connect digital scaling meter and program in danfoss vfd

  • @michaelnasief9245
    @michaelnasief9245 ปีที่แล้ว

    Dear i have danfoss FCM 305 - with worming indicated local stop - i tried every thing - can you help

  • @manjulakarunathilaka7949
    @manjulakarunathilaka7949 11 หลายเดือนก่อน

    👍👍❤ thanks frind

  • @eyadadel1959
    @eyadadel1959 2 หลายเดือนก่อน

    Hi Dear
    How to get the registers addresses of the fc101 vfd

  • @rajeshmondal2424
    @rajeshmondal2424 4 ปีที่แล้ว +1

    So good

  • @lalbabuyadav8023
    @lalbabuyadav8023 2 ปีที่แล้ว

    Ek problem hai
    Please help me
    Danfoss fc360 hai usme ek. Warning 7aa raha hai

  • @gauravsharma-gc4cp
    @gauravsharma-gc4cp ปีที่แล้ว

    Sir humari company mai danfoss vfd ,wo phase loss dikhata hai bar bar ,humne output cables aur motor check ki okay hai,shi chalti h lekin 2 -3 gnte m fault aata hai isko reset kese kre

  • @_keshav004
    @_keshav004 ปีที่แล้ว

    Please guide on automation drive.

  • @यादवजी-च4स
    @यादवजी-च4स ปีที่แล้ว

    Brak Ragister ka use kha kiya jata hy 😊

  • @drprajapati7147
    @drprajapati7147 3 ปีที่แล้ว +1

    We have Danfoss ac Drives FC 51 -micro drives ASD ENGINEERING DELHI-92

  • @sharifhossain8830
    @sharifhossain8830 3 ปีที่แล้ว

    Direction of rotation parameter which one?
    Forward or Reverse or Both
    Thanks

  • @prlove3845
    @prlove3845 21 วันที่ผ่านมา

    Sir. Please selection Krna sikhaye

  • @samisk2169
    @samisk2169 2 ปีที่แล้ว

    Hello my friend, well done for posting

  • @consoultechnical1688
    @consoultechnical1688 3 ปีที่แล้ว

    Sir fc51 drive mein samne display mein rpm kaise dekhenge.

  • @harshpanchal3372
    @harshpanchal3372 5 ปีที่แล้ว

    Nice video 👍

  • @MrMsJomol
    @MrMsJomol 3 ปีที่แล้ว

    is there any ready signal form vfd for programing with plc?

  • @sandeepkaushik1998
    @sandeepkaushik1998 4 ปีที่แล้ว +1

    Sir delta drive ke auto/manual ckt ke bare me bi btaoge.sir plz

  • @adrianacastaneda5548
    @adrianacastaneda5548 3 ปีที่แล้ว

    Buen día. Será que me podrías apoyar con los parámetros y conexión que debería utilizar para un alternado de dos variadores con transductor? Es decir que encienda uno, se para y encienda el segundo, luego se pare y encienda nuevamente el primero etc
    🙏🏻

  • @mohammedeathesham2151
    @mohammedeathesham2151 3 ปีที่แล้ว

    Dear sir,
    You explaination was very simple and good.
    I am facing one similar problem at site can you please help me out.
    When i am starting the motor it's frequency is directly going to 50hz.
    I want to control the frequency from 20hz and as vtg increases frequency should also increase.
    Can you please guide me to do the settings for the frequency.

    • @ultimatesolution9935
      @ultimatesolution9935 ปีที่แล้ว

      अगर आप FC 51 use kar rahe hai to
      Parameter
      4-12........motor speed low limit
      Aur 3-02......minimum reference check check kare
      Inme aap 50hz rakhe hue hai.isko 0 ya kuchh rakhe jisse aap start Karna chahte hai.

  • @ultimatesolution9935
    @ultimatesolution9935 ปีที่แล้ว

    Danfoss me multistage speed ke baare me video banaye.

  • @dibyaranjanbehera6366
    @dibyaranjanbehera6366 ปีที่แล้ว

    Frequency kaise badha te hain

  • @shubhambhardwaj2687
    @shubhambhardwaj2687 2 ปีที่แล้ว

    Sir. Who is relay trip parameters in vlt micro drive 51

  • @drprajapati7147
    @drprajapati7147 3 ปีที่แล้ว +1

    yes good

  • @ganpatmungase8517
    @ganpatmungase8517 5 ปีที่แล้ว +1

    Dear sir
    whats difrants in - FC -051, FC360 and FC - 101

    • @boobathirajaduraisamy5155
      @boobathirajaduraisamy5155 4 ปีที่แล้ว +1

      FC101 Refrigeration Drive most used in chillers, Air-conditioning,
      FC051 is Small Application used automachine drive,
      FC360 is Fan application and Pumb application Specifically used and number of digital input is high.
      Basic different is Different firmware and parameters used in the drive
      You want any help please Call 8637641293 I will guide you,
      Currently I am working in danfoss drives..

  • @PDQknives
    @PDQknives 4 ปีที่แล้ว +1

    Thanks you, great video! I need to run a motor up to 70 Hz using an external potentiometer, and i can't do it. 3-15 parameter is in "1" already. The motor gets to 50 Hz. Do you know what could be happenning? Thanks!

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      thank you..
      You need to set three parameters...as per below,
      3-03 = 70 Hz
      4-14 = 70 Hz
      6-15 = 70 Hz

    • @PDQknives
      @PDQknives 4 ปีที่แล้ว +2

      @@DIGICONAUTOMATION Thank you very much!

    • @ultimatesolution9935
      @ultimatesolution9935 ปีที่แล้ว

      ​@@DIGICONAUTOMATIONbut sir motor may get hot ,I think

  • @mahmoodbhaijaan4062
    @mahmoodbhaijaan4062 4 ปีที่แล้ว +1

    sir muje motor ki frequency badaani hai konsa parameter hai

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      Parameter 3-03 = Max. frequency that you want
      Parameter 4-14 = Max. frequency that you want

  • @ratneshtripathi1095
    @ratneshtripathi1095 2 ปีที่แล้ว

    Vlt 5000 ka revars and farvard fara mitar sir

  • @engineeraliahmadsabir2382
    @engineeraliahmadsabir2382 3 ปีที่แล้ว

    Good

  • @anirbanghosh1592
    @anirbanghosh1592 4 ปีที่แล้ว

    dear sir,
    in circuit diagram u have shown that latched start to terminal no 12,do it means a continuous nc puls should be given at point 12 or one time nc pulse is required

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว +1

      Terminal 12 is for +24V supply, where for latched start we used a terminal no. 18

    • @ultimatesolution9935
      @ultimatesolution9935 ปีที่แล้ว

      Friend,really terminal 12 is a source of +24vdc

  • @suncontrols1884
    @suncontrols1884 4 ปีที่แล้ว +1

    hi im velu from sun controls bangalofre . i have one doubt my danfoss vfd showing overcurrent error without conneting motor wht is the issu plesae help me

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      Okay sir, you have to do factory reset your VFD.
      th-cam.com/video/7RAzQeYtttY/w-d-xo.html

    • @suncontrols1884
      @suncontrols1884 4 ปีที่แล้ว +1

      Thank u for reply...one more doubt if I do factory reset all saved data will be delete or only alarm will delete?

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว +1

      @@suncontrols1884 All data will be deleted

  • @ManojKumar-xm3oi
    @ManojKumar-xm3oi 5 ปีที่แล้ว +1

    Sir Dc Se chalane keley kaya program danlna padega

  • @niksontalan5803
    @niksontalan5803 4 ปีที่แล้ว

    Hello mr.can you make totorial vidio how seting parameters vfd motor dc for me..?

  • @rahuldeo7892
    @rahuldeo7892 4 ปีที่แล้ว

    I have 7.5 hp danfoss fc51 and it taking 4 to 20 ma frequency command but after power trip vfd is not taking 4 to 20 ma command and there is any alarm and i have connected 55 and 60 number terminals. Please suggest me how do i check and what is parameters of 4 to 20 ma for plc or pid and 0 to 10 volt for 10k port.

    • @ultimatesolution9935
      @ultimatesolution9935 ปีที่แล้ว

      Dear friend,
      According to me,
      For 4-20ma
      3-15......[2]
      For start command you can select 5-10....[8]
      6-22....4ma
      6-23...20 ma
      Rest keep default settings
      Connection diagram:
      Term. 60 ...... +
      Term.55......... -
      Connection of start command
      Between term.12 and Terminal 18.....NO contact.
      Rest on your feedback

  • @guddumoriya5258
    @guddumoriya5258 ปีที่แล้ว

    Lock or unlock kaise kiya jaaye

  • @lalbabuyadav8023
    @lalbabuyadav8023 2 ปีที่แล้ว

    Hi good morning

  • @supanditroy7191
    @supanditroy7191 2 ปีที่แล้ว

    Frequency wrong show ho raha

  • @sonajipohne2359
    @sonajipohne2359 3 ปีที่แล้ว

    Dear Sir
    Danfoss drive FC 102
    This driver problem is ....
    Short circuit (16A) on display
    How to solve this problem
    Plz help me sir

  • @harpreetsingh2696
    @harpreetsingh2696 4 ปีที่แล้ว

    ID Run ka kya parameter ha sir

  • @classicwheelsunited
    @classicwheelsunited 3 ปีที่แล้ว

    Hi there! I am interested on the Digicon Start/Stop panel. Does it have a part number or can you tell me where to buy it? Best regards, Istvan

  • @varatharajvaratharaj1635
    @varatharajvaratharaj1635 ปีที่แล้ว

    Over load production setting

  • @machagiriprasad2305
    @machagiriprasad2305 3 ปีที่แล้ว

    Wiring vfd to motor

  • @pramodkumarmandal7940
    @pramodkumarmandal7940 4 ปีที่แล้ว +1

    Password laga ho to kai se parameter set kare ge

  • @sanjuaher2181
    @sanjuaher2181 3 ปีที่แล้ว +1

    Sanjay Aher

  • @radhikavermaofficial1811
    @radhikavermaofficial1811 5 ปีที่แล้ว +1

    Vlt 2800 parameter setting

  • @EdmundDwight-i8o
    @EdmundDwight-i8o 21 วันที่ผ่านมา

    Clark William Hernandez Shirley Martin Nancy

  • @asifsaifi6122
    @asifsaifi6122 3 ปีที่แล้ว

    Kisi Koo old VFD chaiye too muje reply karke mujse baat kar skte hoo

  • @chaudharykaif
    @chaudharykaif 3 ปีที่แล้ว +1

    Port ka parameters tobbataye hi nahi

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  3 ปีที่แล้ว

      For POT, If u connect the wire on terminal 53 then set [1] on parameter 3-15..

    • @chaudharykaif
      @chaudharykaif 3 ปีที่แล้ว

      @@DIGICONAUTOMATION thanks sir

    • @chaudharykaif
      @chaudharykaif 3 ปีที่แล้ว +1

      @@DIGICONAUTOMATION vfd037M43A display pe hpf dhikha raha hai to kaya problem hai

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  3 ปีที่แล้ว

      @@chaudharykaif Can u share a picture ?

    • @chaudharykaif
      @chaudharykaif 3 ปีที่แล้ว

      Picture kis pe share karo

  • @syedtayyab2411
    @syedtayyab2411 4 ปีที่แล้ว

    Sir aap ka no milega kya

  • @aaronelieservalenzuelamart2734
    @aaronelieservalenzuelamart2734 4 ปีที่แล้ว

    En español por fa

  • @sharandeep6819
    @sharandeep6819 3 ปีที่แล้ว