Configuring VLT Micro Drive FC51 for Two wire start/stop with Multi-setup (Auto/manual) || DIGICON

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ค. 2019
  • Configuring VLT Micro Drive FC51 for Two wire start/stop with Multi-setup (Auto/manual) system || Digicon Automation
    Auto Mode: Reference from PLC (Programmable Logic Controller)
    Manual Mode: Reference from POT (Potentiometer)
    Parameter No. Parameter name Set-up 1 (Auto) Set-up 2 (Manual)
    0-10 Active Set-up [ 9 ] Multi Set-up [ 9 ] Multi Set-up
    0-11 Edit Set-up [ 1 ] Set-up 1 [ 2 ] Set-up 2
    0-12 Link setups [ 20 ] Linked [ 20 ] Linked
    1-20 Motor Power As per motor data As per motor data
    1-22 Motor Voltage As per motor data As per motor data
    1-23 Motor Frequency As per motor data As per motor data
    1-24 Motor Current As per motor data As per motor data
    1-25 Motor Nominal Speed As per motor data As per motor data
    3-15 Reference Resource 1 [ 2 ] Analog Input 60 [ 1 ] Analog Input 53
    3-16 Reference Resource 2 [ 0 ] No function [ 0 ] No function
    3-17 Reference Resource 3 [ 0 ] No function [ 0 ] No function
    3-41 Ramp 1 Up Time As per Requirement As per Requirement
    3-42 Ramp 1 Down Time As per Requirement As per Requirement
    4-10 Motor Speed Direction [ 0 ] Clockwise [ 0 ] Clockwise
    4-14 Motor Speed High Limit 50Hz 50Hz
    4-16 Torque Limit Motor Mode 150% 150%
    4-17 Torque Limit Generator Mode 100% 100%
    5-10 Terminal 18 Digital Input [ 8 ] Start [ 8 ] Start
    5-11 Terminal 19 Digital Input [ 0 ] No function [ 0 ] No function
    5-12 Terminal 27 Digital Input [ 0 ] No function [ 0 ] No function
    5-13 Terminal 29 Digital Input [ 0 ] No function [ 0 ] No function
    5-15 Terminal 33 Digital Input [ 23 ] Set-up select bit [ 23 ] Set-up select bit
    5-40 Function Relay (Relay 1) [ 5 ] Running [ 5 ] Running
    6-10 Terminal 53 Low Voltage - 0.00 V
    6-11 Terminal 53 High Voltage - 10.00 V
    6-19 Terminal 53 mode - [ 0 ] Voltage mode
    6-22 Terminal 60 Low Current 4.00 mA -
    6-23 Terminal 60 High Current 20.00 mA -

ความคิดเห็น • 44

  • @kaizeninelectrical7780
    @kaizeninelectrical7780 2 ปีที่แล้ว

    Very useful sir , great keep it up ,now our m/c running ☺️☺️

  • @vishwabandhumundra1248
    @vishwabandhumundra1248 7 หลายเดือนก่อน

    Thanks thanks and thanks a lot for this video. Problem resolved.

  • @usmanautomation9111
    @usmanautomation9111 3 ปีที่แล้ว +1

    Great sir.

  • @hareshpanchal2110
    @hareshpanchal2110 4 ปีที่แล้ว +1

    Thanks sir.....very helpful

  • @InstrumentCalibration
    @InstrumentCalibration ปีที่แล้ว

    GREAT VIDEO

  • @DilipKumar-bg7jj
    @DilipKumar-bg7jj หลายเดือนก่อน

    Super

  • @gauravshah3246
    @gauravshah3246 3 ปีที่แล้ว +1

    Gazab hai

  • @rathodaravind2935
    @rathodaravind2935 3 ปีที่แล้ว +1

    good explan sir

  • @harpreetsingh2696
    @harpreetsingh2696 3 ปีที่แล้ว

    Sir ABB VFD par v video baneye .apke video sa hame bhut knowledge mile ha vfd par.Thanks a lot!

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  3 ปีที่แล้ว

      Actually we are authorized channel partner of danfoss, so can't make a video on ABB

  • @petercroyle5662
    @petercroyle5662 3 ปีที่แล้ว +1

    Where do I get the switch set for this project?

  • @sauhangnaam4268
    @sauhangnaam4268 6 หลายเดือนก่อน

    Sir danfoss 360 ko synchronisation kaise kre or external source kliye parameters kya h

  • @AnilKumar-uk7bt
    @AnilKumar-uk7bt 4 ปีที่แล้ว

    Sir soft starter par v auto menul video bania

  • @GURMEETSINGH-ov9dr
    @GURMEETSINGH-ov9dr 4 ปีที่แล้ว +1

    Please add vedio with complete installations with on off switch or frequency up and down

  • @maghajame8568
    @maghajame8568 ปีที่แล้ว

    where terminal 33 defined in program?

  • @naushadmohammad2784
    @naushadmohammad2784 10 หลายเดือนก่อน

    Motor thermistor kaise connect karenge isme

  • @daveal3d
    @daveal3d 4 ปีที่แล้ว +1

    I don't see a switch between Hand and Auto. Your A/M toggle switch alternates between 2 setups (1 and 2). Is there a possibility to control HAND, AUTO, OFF remotely through digital input or modbus command?

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      NO, for Hand control u have to press button on LCP display.

    • @daveal3d
      @daveal3d 4 ปีที่แล้ว

      @@DIGICONAUTOMATION What about for AUTO? Is there anyway to link that to a Dig.In contact or through Modbus?

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      @@daveal3d NO, it's not possible to control hand, auto using modbus or digital input, we have to operate these function manually....

    • @daveal3d
      @daveal3d 4 ปีที่แล้ว

      @@DIGICONAUTOMATION For some reason some of my signle phase drives go back to OFF after a trip (8: Undervoltage DC bus). Even though in the parameters i set to infinitely reset trips/alarms, it still goes to OFF. Any advice?

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว

      @@daveal3d I'm recently uploaded a video on that topic, so hope u get help from that video....th-cam.com/video/wcmCiJTLroo/w-d-xo.html

  • @SanjivMaheshwari
    @SanjivMaheshwari 4 ปีที่แล้ว

    Sir, please tell me can be supply DC input from solar to the drive to generate triple phase 415 V

    • @shihabulislam4643
      @shihabulislam4643 2 ปีที่แล้ว

      No you need power inverter for that.
      It’s have AC input AC output.

  • @maidulislam2216
    @maidulislam2216 3 ปีที่แล้ว

    i am used 12,18,42,53,55 terminal. i want to know 42 parameter setup. can u help me sir

  • @SanjivMaheshwari
    @SanjivMaheshwari 3 ปีที่แล้ว

    क्या इस ड्राइव को सोलर इनपुट से चला सकते हैं। मुझे 1 hp का submersible pump chala hain। Abhi 8 panels hain।

  • @milanvasic3643
    @milanvasic3643 2 ปีที่แล้ว

    modbus communication??

  • @pramodkumarmandal7940
    @pramodkumarmandal7940 4 ปีที่แล้ว

    do bar menu dabane par pw aa ja to kia ki ya jia ya do bar menu daba ne par passord magane par kiya kare

  • @maidulislam2216
    @maidulislam2216 3 ปีที่แล้ว

    sir vsd off mode also colling fan running. vsd no have silant mode. have any advice . fc 51

    • @maidulislam2216
      @maidulislam2216 3 ปีที่แล้ว

      sir selecter switch off mode also vsd coolling fan running. running sound coming.

    • @shihabulislam4643
      @shihabulislam4643 ปีที่แล้ว

      See parameter 14-52 fan control mode .
      Set on auto , not always run

  • @arvindkumarpal6124
    @arvindkumarpal6124 4 ปีที่แล้ว +1

    Ye kaise malum padega ki ye parameter Torque ,reference current 4 ml, reference pot 10 volt,motor name plate etc..... Ke hi h.

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  4 ปีที่แล้ว +1

      Iske liye aapko vlt guide download karni hogi jisme aapko sabhi parameters ka no. and name diya hoga...

  • @Fi_Fi555
    @Fi_Fi555 5 หลายเดือนก่อน

    Ghalti se auto on ka button press hoo gaya ab woh start nahi hoo rha

  • @rameshpawar1412
    @rameshpawar1412 3 ปีที่แล้ว +1

    Sir alarm red show kar raj hai our display par AL13 aa rah hai please help

    • @DIGICONAUTOMATION
      @DIGICONAUTOMATION  3 ปีที่แล้ว

      th-cam.com/video/gwkSmxpki80/w-d-xo.html

    • @rameshpawar1412
      @rameshpawar1412 3 ปีที่แล้ว

      Tnq sir

    • @vineeshsingh6889
      @vineeshsingh6889 ปีที่แล้ว

      @@DIGICONAUTOMATION sir mere drive me kuch problem hai, please sir number de do jo ki me aap se sahi se samajh saku.

  • @ankitpawar7098
    @ankitpawar7098 2 ปีที่แล้ว

    मुझे मेरे ड्राइव मे प्रॉब्लर्म आ रही है मे आपै बट कर सकता हु