Cooled better before the coil was replaced.

แชร์
ฝัง
  • เผยแพร่เมื่อ 6 ก.ค. 2024
  • Refrigerant flow issues after evaporator coil replacement.
    #airconditioning #cooling #airconditioner #hvac #hvaclife #hvacrepair #hvacservice #hvactechnician

ความคิดเห็น • 17

  • @tedperry2441
    @tedperry2441 8 วันที่ผ่านมา +10

    I would always put the sticker on the air handler from the piston number so you can see whats is installed without removing it.

    • @AaronPowellvox
      @AaronPowellvox 8 วันที่ผ่านมา +2

      I do that too but not many people do it. If the sticker is gone I write it on there.

  • @topher8634
    @topher8634 8 วันที่ผ่านมา +5

    What I usually do on those type of valves is I'll close the suction half way then I'll shut the liquid. That way you don't have far to go. If the compressor is any good, it'll hold anyway. Scrolls don't have reeds like a recip but they'll hold most of the pressure while pumping down. It's difficult to fully pump down 410a anyway, the internal relief usually opens up before it's fully pumped down.

  • @lbstilts
    @lbstilts 8 วันที่ผ่านมา +5

    I keep a set of gas orrifice drills to ensure always having the right size piston. You can keep a box full of the flow pistons still not have the right one.

  • @toddhodges4914
    @toddhodges4914 8 วันที่ผ่านมา

    Thanks for sharing!

  • @OnusBones
    @OnusBones 8 วันที่ผ่านมา +2

    Very nice, and interesting as always.

  • @keithsac2542
    @keithsac2542 8 วันที่ผ่านมา +2

    Good find.

  • @eastcoast186
    @eastcoast186 8 วันที่ผ่านมา

    Thanks for the video

  • @gabrielstern4992
    @gabrielstern4992 8 วันที่ผ่านมา +1

    Charles jumping in again saw you said Goodman so I was right there is a good chance the coil originally had a txv. But Goodman charges extra for the txv and does not include it with the evap coil now I know they make so called adjustable txvs so you may want to discuss with the custumer that option of putting a txv in it which the original probably had or a universal adjustable txv as options.
    But if I am right this is why if it had a txv why you replace it with a txv and not put a piston in it because that's not what it was designed to use.

  • @joshuasmith973
    @joshuasmith973 8 วันที่ผ่านมา

    17:52 Amen brother, always something in the damn way.😅😅😅

  • @arthurhartwick7974
    @arthurhartwick7974 8 วันที่ผ่านมา +2

    Get yourself a psychrometer probe for outdoor air and use measure quick

  • @deanmartin1966
    @deanmartin1966 8 วันที่ผ่านมา +3

    I’m not a fan of TXV’s either.

    • @Josh-px6xb
      @Josh-px6xb 8 วันที่ผ่านมา +3

      A piston makes a system critically charged.. and in the summertime, there is going to be some slugging going on

    • @deanmartin1966
      @deanmartin1966 8 วันที่ผ่านมา +1

      @@Josh-px6xb Whenever I encounter a bad txv, I usually change it to a piston. No slugging here, I know how to charge a piston with super heat. 3 x WB - constant 80 - OAT / 2.

  • @Garth2011
    @Garth2011 8 วันที่ผ่านมา +1

    Why would an HVAC put in a 59 vs the 93 piston? Maybe a different condenser previously?

    • @AaronPowellvox
      @AaronPowellvox 8 วันที่ผ่านมา +4

      They probably lost the original and then just put in what they had. It doesn’t make it any better but that’s probably why.

  • @woodystokes1543
    @woodystokes1543 4 วันที่ผ่านมา