FAULT FINDING ON A HEATING SYSTEM! PRESSURE TO BEAT THE CLOCK! 🤯

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 มิ.ย. 2022
  • FAULT FINDING ON A HEATING SYSTEM! PRESSURE TO BEAT THE CLOCK! 🤯
    Beat the clock! Tackling electrical fault finds can be super challenging and highly satisfying all at the same time! How do you handle the pressure when fault finding? In this episode, Cory has a packed day of multiple electrical faults finds and an EICR can he get everything complete in the allowed day?
    Speed up your installs with Tamioelectrics - use code 'Artisan' to save 25% at check out! bit.ly/3u6Udh3-Tamoielectric
    Subscribe to our TH-cam Channel for more great electrical content: th-cam.com/users/artisanelectr...
    Get more from Artisan Electrics here!👇
    linktr.ee/artisanelectrics
    Artisan Electric Discord - Let's create the biggest Electrical Community! 👇
    / discord
    ⏱️Timestamps
    05:06 Red Hot Heating
    08:40 Double Check
    10:56 Next Job
    13:31 Let’s Get Started
    14:22 First Things First
    16:55 Junction Boxes
    19:23 Tamioelectrics
    20:51 Ring Testing
    21:46 Onto The Next One
    24:12 Not Filled In
    🧰🛠️ Tool Of The Day 👇
    Klein Tools Digital Clamp Meter - amzn.to/3xYMmDs
    Wera Tool-Check Plus - amzn.to/3xZxfJZ
    Unilite Work Lights:
    Get 25% off all Unilite Products using our code "ARTISAN25"
    UK Store - bit.ly/UNILITE
    Europe Store - bit.ly/UNILITE-EU
    USA Store - bit.ly/UNILITE-NA
    Australia Store - bit.ly/UNILITE-AUS
    🏷️😱 Big Boots - get 5% off our amazing work boots when you use our discount code "ARTISAN" at checkout here bit.ly/BIGBOOTS
    🎵 Use music the Artisan Way - Sign up to Epicmedic Sound here 👇🏼
    www.epidemicsound.com/referra...
    🔔 Become a Channel Member To Get Access To Exclusive Perks 👇
    ➤ / @artisanelectrics
    ✅ Check Out All Our Favourite Tools Here 👇
    ➤ www.amazon.co.uk/shop/artisan...
    -----Electricians Business Course-----
    📩 Sign Up To The Electricians Business Course Here And Get The First 4 Lessons Free 👇
    ➤ bit.ly/2Z582zI
    🔔 Subscribe to TOOLS4SPARKS TH-cam Channel 👇
    We Also Have A Dedicated TH-cam Channel About Tools:
    ➤ / tools4sparks
    -----MY ENERGY PROVIDER-----
    🐙 Get £50 credit when you switch to Octopus Energy 👇
    ➤ share.octopus.energy/zappy-sh...
    🏷️ DISCOUNT BUSINESS SUPPLIES 👇
    ➤ www.amazon.co.uk/tryAB?tag=ar...
    📈Make the most of your TH-cam analytics with TubeBuddy - Sign up here👇
    ➤www.tubebuddy.com/ARTISAN
    -----TRADES INSURANCE DISCOUNT-----
    If you need to renew your public liability insurance or need tools in van insurance, I recommend Rhino Trade Insurance, I've just renewed my insurance with them.
    🏷️ Use My Discount Code “ART5” and you get a 5% Extra Discount On Their Already Excellent Prices.
    ➤ www.rhinotradeinsurance.com/quote
    📞 or call 01162437904.
    📱 Don't Forget to Follow Social Media, FOLLOW US on Your Favourite Social Networks 📱
    💬 Artisan Electrics Discord
    ➤ / discord
    📸 Artisan Electrics Instagram Account 👇
    ➤ / artisanelectrics
    🐦 Artisan Electrics Twitter Account 👇
    ➤ / artelectrics
    📓 Artisan Electrics Facebook Account 👇
    ➤ / artisanelectrics
    ⏰ Artisan Electrics TikTok Account
    ➤ / artisanelectrics
    💼 Artisan Electrics Linkedin
    ➤ / artisan-electrics
    🎥 Get in touch with the Media Team
    ➤media@artisanelectrics.co.uk
    This video is for entertainment purposes only please do not attempt to copy or recreate it. Do so at your own risk.
    #sparkylife #electricianlife #artisanelectrics
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 150

  • @artisanelectrics
    @artisanelectrics  ปีที่แล้ว +3

    Speed up your installs with Tamioelectrics - use code 'Artisan' to save 25% at check out! bit.ly/3u6Udh3-Tamoielectric

  • @ronanotoole1973
    @ronanotoole1973 ปีที่แล้ว +17

    "No fishy smell. VERY important in multiple aspects of life" - Corey, 2022 😁
    Another great show guys 👍

  • @OraEtLabora0
    @OraEtLabora0 ปีที่แล้ว +1

    5:18 neat squash, the drink of winners!🤣

  • @snazy7777
    @snazy7777 ปีที่แล้ว +18

    John Ward is a flipping legend !!
    All of my (limited) electrical knowledge comes from him.

    • @CommercialGasEngineerVideos
      @CommercialGasEngineerVideos ปีที่แล้ว +1

      True, John is a legend. He has a good channel for wiring.

    • @corymac
      @corymac ปีที่แล้ว +2

      John taught me more than college!

  • @richrowley8355
    @richrowley8355 ปีที่แล้ว +9

    I didn't wire the Quintec box on the last job, but i watched you do it perfectly. I'm feeling your pain.

  • @jamieblatantsparky
    @jamieblatantsparky ปีที่แล้ว +14

    You see how he hit that valve , that’s what a pro sparky looks like , established the problem and then proved his thoughts and walks away knowing exactly where the issue was with use of drawings his experience and test equipment, new to the trade people would do well to follow that advice not just be a parts changer or a “call a plumber” merchant

    • @corymac
      @corymac ปีที่แล้ว

      Thanks mate!

    • @glenndyer9967
      @glenndyer9967 ปีที่แล้ว

      Hope you didn't charge them? ☺️

    • @iLoveAppl3947
      @iLoveAppl3947 ปีที่แล้ว

      @@glenndyer9967 you have to. Who pays for fuel insurance?

  • @joe2395
    @joe2395 ปีที่แล้ว +18

    inside the fixed part of the valve is a short arm which has a small rubber ball which covers or opens the flow of water,i have changed quite a few due to the rubber ball deteriating and breaking up and getting lodged in the arm

    • @TheNockPlumber
      @TheNockPlumber ปีที่แล้ว +1

      Came here to just say this exact thing. Joe is 101% correct

  • @HATCHETHAS
    @HATCHETHAS ปีที่แล้ว +2

    I think you are being very generous with whoever installed that outside light fitting!

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      Cory is a generous guy 😂

    • @HATCHETHAS
      @HATCHETHAS ปีที่แล้ว

      @@artisanelectrics except when the Pringles are on offer!!

  • @olly7673
    @olly7673 ปีที่แล้ว +3

    That was a very entertaining half hour Cory, thank you for that. I have had an electric screwdriver for years and always got the mickey taken out of me on site but like you say, it saves your wrists and gets things like second fixing done in no time. Keep up the good work.

  • @terrystephens1102
    @terrystephens1102 ปีที่แล้ว

    Another excellent job(s) Cody, you’re the man 😁👌👌👏👏👏❤️

  • @ianlove3
    @ianlove3 ปีที่แล้ว

    Great job Cory as always.

  • @iantaylor6858
    @iantaylor6858 4 หลายเดือนก่อน

    So professional

  • @petershores
    @petershores ปีที่แล้ว +2

    Excellent video - makes me want to watch more regularly again!

    • @corymac
      @corymac ปีที่แล้ว +1

      Thanks Peter!!!

  • @paul_smith66
    @paul_smith66 ปีที่แล้ว +4

    Excellent video. I really like the logic behind the fault finding.

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      Cheers Paul!

    • @vambo1980
      @vambo1980 ปีที่แล้ว +1

      I hope lots of young sparks watch the channel, wish I had you tube when I was young!! Excellent tips and I must say very well presented considering you're actually doing the job.

  • @chrisholt2474
    @chrisholt2474 ปีที่แล้ว +11

    Glad to see Cory is back and on form again, I was beginning to think he had disappeared for good.
    They said he had been doing more pricing up jobs and site surveys etc, but I wasn’t convinced.
    Hope all is well Cory, still the best. 👍👍👍

    • @corymac
      @corymac ปีที่แล้ว +1

      Cheers Chris, I appreciate it 😎👍🏼

    • @alexbabcock1880
      @alexbabcock1880 ปีที่แล้ว +1

      @@corymacmarry me

  • @asamitchell7948
    @asamitchell7948 ปีที่แล้ว +3

    Love the link you have for the r1+r2 I have the same link off the guy on ebay.
    Only thing I wish was if the drill bit was longer for crabtree rcbo's as it has a deep line terminal.
    Also I would c2 the the spot lights in the kitchen as it does not pose an immediate danger but is likely to cause a danger in the event of a fire.

  • @eamonnohalloran2254
    @eamonnohalloran2254 ปีที่แล้ว

    Cory . Again your a star.

  • @rupertm2542
    @rupertm2542 ปีที่แล้ว

    One of the best videos for a while. Great to see the nitty gritty!

  • @normasuxxex2852
    @normasuxxex2852 ปีที่แล้ว

    Welcome back keep up the good work

  • @intercity125
    @intercity125 ปีที่แล้ว +3

    That particular style of socket protector you can often actually get a wire down in the gap where the pins click in... making live parts more accessible than not having it!

  • @CommercialGasEngineerVideos
    @CommercialGasEngineerVideos ปีที่แล้ว +1

    Honeywell app is a winner for diagnosing these issues.

  • @scottsparky1
    @scottsparky1 ปีที่แล้ว +2

    the Bosch go2 screwdriver is brilliant but there 1 problem with it, is that it's round. when you put it down on a side it rolls off.

  • @timothyn4929
    @timothyn4929 ปีที่แล้ว

    13:46 a book on fish 🤣. Just after the fish comment

  • @imark7777777
    @imark7777777 ปีที่แล้ว +3

    Plug covers are actually quite dangerous in the UK with the shuttered outlets it's something that has drifted across the pond. I forget It was a John Ward thing or some safety video I ran a crossed.

  • @tommahoney7940
    @tommahoney7940 ปีที่แล้ว

    Good fault finding mate.

  • @MarkDurbin
    @MarkDurbin ปีที่แล้ว

    The Tamioelectrics are a nice find, thanks :)

  • @RichardArblaster
    @RichardArblaster ปีที่แล้ว

    Great video Cory 😎

  • @train4905
    @train4905 ปีที่แล้ว

    Exelent

  • @StaleEHuse
    @StaleEHuse 4 หลายเดือนก่อน

    You need starting to use the type of connection / switch boxes we use in rest of Europe and "sikringsskap" as in Norway

  • @tobysherring1369
    @tobysherring1369 ปีที่แล้ว +2

    Fire-rated downlights, while they're an excellent upgrade, are not required when the room above is part of the same dwelling. The ones installed here were approved and (assuming the ceiling isn't insulated) there's plenty of room for air to circulate. The greater risk comes when they're above an upstairs room and covered with insulation, with no air circulation. The lamps overheat and fail prematurely, and there's a fire risk. So possibly C3 but I'd put it in notes advising energy saving advantages of upgrading.

  • @tceng9449
    @tceng9449 ปีที่แล้ว +5

    8:18: a stiff valve *shouldn't* (though anything is possible) burn out the motor.
    The motors are designed to spend most of their life stalled. On a single port valve, they run to the end of travel and just sit there with current running through them desperately trying to push the valve more open, but alas in vain.
    Like the wind turbine service boats that just sit there rammed against the base of the turbine.
    The motors are a common enough failure that you can pick up replacements and knock-off replacements everywhere.

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว +1

      Great insight there thanks for sharing your wisdom and knowledge with us

  • @philipsmith0752
    @philipsmith0752 ปีที่แล้ว

    well done Cory

  • @Dontmindme__
    @Dontmindme__ ปีที่แล้ว

    Glad I’m not the only qualified spark with a screenshot of John wards wiring diagrams 😂

  • @stenningelectrical1205
    @stenningelectrical1205 ปีที่แล้ว

    What did you code the flex just stabbed in the front of that three gang switch ?

  • @mikethemask1525
    @mikethemask1525 ปีที่แล้ว +2

    They might be fire rated fittings what makes you think there not??

  • @gaffey12345
    @gaffey12345 ปีที่แล้ว

    great video.. what bag do you use for your tester?

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      Velocity Rogue 7.5 Tester Bag - th-cam.com/video/AB3Gcv7F0qs/w-d-xo.html

  • @EdthePlumber
    @EdthePlumber ปีที่แล้ว

    Cory I think the tanks too hot for the valve to work. need to check the if there a 240v on the brown (from cylinder stat)
    Probably dont butter no parsnips!

  • @joecalder1998
    @joecalder1998 ปีที่แล้ว +2

    Waiting for a new upload to get my artisan fix 🤓😚

  • @OHYEAHGAMEVIDEOS
    @OHYEAHGAMEVIDEOS ปีที่แล้ว +4

    Zone valve failure is very common. If heating or hw are on when not being called for you can almost guarantee its a valve at fault

  • @leshackett3687
    @leshackett3687 ปีที่แล้ว

    Nice video cory

  • @jackhutchinson4073
    @jackhutchinson4073 ปีที่แล้ว +4

    You’ve got 2 zone valves. 1 working 1 isn’t. Check wiring. Then confirm what you already know by swapping working zone valve over to the non working zone valve. Absolutely no need to faf about dissecting the unit if you claim you’re trying to save the customer coin.

  • @tomkirkland
    @tomkirkland ปีที่แล้ว +1

    Fault finding on a stuck valve. Power off, does the level move back? If not either stuck valve, worn motor or broken spring. Pop the head off, if the lever returns it’s the valve, if not it’s the motor or if your really lucky a springs come off.

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      Great simple steps to follow there thanks for sharing

  • @shaunconnor7525
    @shaunconnor7525 ปีที่แล้ว

    If that is put in recent there is a bad batch of honeywell valves atm would tie up with it it good work cory 👍

  • @stevenjohnson6082
    @stevenjohnson6082 ปีที่แล้ว +1

    if there is power to the brown wire and motor does not move to open position it is faulty motor. you can change sycron motor or replace head you dont need to take sycron motor off

  • @Bob_Burton
    @Bob_Burton ปีที่แล้ว

    Why wasn't the valve motor working when the unit was apart ?

  • @memergamer5324
    @memergamer5324 ปีที่แล้ว +1

    Did iti (industrial training institute)from India what should i do now ?

  • @bells1969
    @bells1969 ปีที่แล้ว +2

    Excellent as they say Knolwedge is power and this lad is top dollar 👍👍

  • @angellino1
    @angellino1 ปีที่แล้ว

    This way you look like an Al Capone lokking for waking someone🤣🤣🤣🤣

  • @gyasikrasineb4808
    @gyasikrasineb4808 ปีที่แล้ว +4

    Too much length on those conductors Cory admit it the guy who put up that fitting should have tailored the conductors to the available room within the fitting rather than leaving all conductors long and then cramming them all in before making a quick get away. They've simply dropped the ball there on this one.

  • @NibblestheHamster
    @NibblestheHamster 2 หลายเดือนก่อน

    For the unvented cylinder
    If the hot water is constantly on and won’t switch off
    Check if there is a demand for hot water
    If there is and the zone valve is free then that’s operating correctly
    If you close the demand off then you should feel resistance, if you do then the zone valve is operating correctly also
    If the zone valve is continuously open and causing the boiler to repeatedly fire up to heat the hot water then the likely issue the the cylinder thermostat.
    If the cylinder stat is at 65 degrees it’ll cause the boiler to fire much more times than it would if it’s at 60 degrees
    Something as simple as turning the cylinder stat down slightly can have a big impact and the above can be checked within 5 mins

  • @epocock
    @epocock ปีที่แล้ว

    Hay where can I buy one of them yellow panel test leads very handy 👍

    • @mikegmarshall
      @mikegmarshall ปีที่แล้ว

      eBay chap - search for R1R2 lead (link) I have one - magnet is not great but it does the job

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      There is a link in the description of the video I believe

  • @jamieblatantsparky
    @jamieblatantsparky ปีที่แล้ว

    And he hates child socket covers , what’s this feeling IS IT LOVE

  • @tc6907
    @tc6907 ปีที่แล้ว +2

    Great video Cory! Still blows my mind your early 20s 🤣
    Non fire rated downlights above a bedroom… C2 all day in my eyes

    • @tc6907
      @tc6907 ปีที่แล้ว +1

      With that testing link, is that the one with a pz2 and crocodile clip? Do you remove your cpc from th bar when doing R1+R2?

    • @corynoahmac
      @corynoahmac ปีที่แล้ว +4

      Could be a fake passport and I’m actually from Bolivia and 36….

    • @tc6907
      @tc6907 ปีที่แล้ว +1

      @@corynoahmac a reply from the man him self, I can die happy now

    • @BenCos2018
      @BenCos2018 ปีที่แล้ว

      @@corynoahmac haha

    • @2Balint
      @2Balint ปีที่แล้ว

      You mean under a bedroom…

  • @ukbullylife7968
    @ukbullylife7968 ปีที่แล้ว

    Bosch go a god send for testing will save the gangrene on the wrists

  • @stevejagger8602
    @stevejagger8602 ปีที่แล้ว

    Heating wiring centres are the biggest ballache because they are often not installed by electricians, who finish up in some hot and cramped space, fixing someone else’s lousy work.
    Lunch breaks are compulsory - you need time out - otherwise your blood sugar level drops dangerously low and you finish up working in panic mode.

  • @brianhewitt8618
    @brianhewitt8618 ปีที่แล้ว

    👍

  • @neil6438
    @neil6438 ปีที่แล้ว

    My bosch driver failed within 2 years I only used it half a dozen times.

  • @noelburke6224
    @noelburke6224 ปีที่แล้ว

    The switch is only auxiliary to bring on the boiler, it's called boiler interlink the wrong guy was called to fix the problem. Next time call a heating engineer

  • @ELECTRICLIFE4U
    @ELECTRICLIFE4U ปีที่แล้ว

    👍👍👍👍👍👍

  • @kingkeygear
    @kingkeygear ปีที่แล้ว

    He's good isnt he

  • @XeonXR6
    @XeonXR6 ปีที่แล้ว +3

    Where penetrating the fire barrier between habitable floors, it would be a C3.

  • @Impulse5596
    @Impulse5596 ปีที่แล้ว

    I can't believe when tenants leave there houses in such a state and don't leave a clear and safe environment for you to work in. Working in enclosed spaces is difficult enough without having to deal with that. I think I would request the area be fully cleared of all obstructions prior to starting work or perhaps I am wrong?

    • @thesteelrodent1796
      @thesteelrodent1796 11 หลายเดือนก่อน

      In Denmark it's customary to clear out the area around whatever you want to have fixed, no matter it it's electrical, plumbing, or something else, as the techs who show up have the right to refuse the job if they don't have easy (or as easy as possible) access to everything they need to work on. This is also why everywhere in Europe now have strict regulations for where you can install things like the electrical main board. Post-Covid it's also become the norm for many companies to demand you clean and sterilize as much as possible, and to give the techs plenty of distance to do their job

  • @stephencarter6634
    @stephencarter6634 ปีที่แล้ว

    👍👌

  • @apmullen
    @apmullen ปีที่แล้ว +3

    Just replace the sycromesh motor it's replaceable part, test at the joint box!

  • @Tryingtimes007
    @Tryingtimes007 ปีที่แล้ว +2

    It’s a type ‘A’ RCD, however you will need to test as if it’s a type AC, this is why IET wiring regs is “non statutory” 🤷🏼‍♂️

  • @KoScosss
    @KoScosss ปีที่แล้ว

    Holy shit
    That upgraded box of controllers is annoying

  • @Edsbar
    @Edsbar ปีที่แล้ว

    John Ward has a very different style to Big Clive, both top chaps.

  • @m.s.8112
    @m.s.8112 ปีที่แล้ว +1

    Concerning the first job, I don't understand how a hot water system could be installed without any pipe insulation at all. What a waste of energy! And in 12:51 the light was flickering when the DB cover flew off. Didn't you notice that? Looked like there must be a loose connection.

    • @Matt-td9wx
      @Matt-td9wx ปีที่แล้ว +1

      The board cover could of just knocked the breaker switch as it flew off would explain the timing of it flickering then staying on again. Its happened to me many times

    • @tobysherring1369
      @tobysherring1369 ปีที่แล้ว

      It's quite common to have uninsulated pipes running throughout a property. Generally there's no point insulating the small amount you can get to, if you're not going to dobthe full run. Some of mine, from a shower pump, go into the attic and back down, and they're fully insulated. But the CH pipes are like underfloor heating!

    • @m.s.8112
      @m.s.8112 ปีที่แล้ว +1

      @@tobysherring1369 IMHO, it makes sense, in cases without hot water circulating even if only the first metres are done because as long as the hot water is not flowing through the pipse, the energy losses are decreasing with increasing distance to the boiler/tank. In those cases where the hot water is circulating, a proper insulation throughout the full length is crucial.

  • @ashbashbaby2
    @ashbashbaby2 ปีที่แล้ว +2

    Since you had it in bits might as well fitted a new motor

    • @stephenjones9153
      @stephenjones9153 ปีที่แล้ว +1

      I would have fitted a new motor or complete valve. Save the customer calling out a plumber.
      Especially if it was a old age pensioner, or a hard up family 👪.
      Sorry but I've always been like that.😉😊

  • @emilgemc8913
    @emilgemc8913 ปีที่แล้ว

    The manufacturer of those Metal Back Boxes needs to made them on that way is better
    Saving time no need to by them separately

  • @aclarke0100
    @aclarke0100 ปีที่แล้ว

    I did that I put the r1 + r2 link on a live circuit I won’t do that again 😳

  • @George-kj6bm
    @George-kj6bm ปีที่แล้ว

    This is why you pay for a pro. 10 checks in 5s that would take you ten days if your weren't familiar. Happily pay and hour for that 5s of pro looking and diagnosis.

  • @michealplater9007
    @michealplater9007 ปีที่แล้ว

    That give me the shits, when you do a tidy job and the next bloke does not care. Maybe that's the best he can do.

  • @nf1955
    @nf1955 ปีที่แล้ว

    Please ask Cory where he got his Apple Watch strap

  • @danielelise7348
    @danielelise7348 ปีที่แล้ว +1

    The main earth is still in the bar,lucky thing, grab me a pint🍺🍻😁🔌⚡

  • @DanWooller
    @DanWooller ปีที่แล้ว

    Shades are fine, pink festival wristband not so much...

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      PIP fest Oslo - amazing family festival, caught Jose Gonzales and Tom Odell under one roof…. No regrets 😎

  • @stuartthespark
    @stuartthespark ปีที่แล้ว

    You had a busy day, with no breaks and a camera man looming over you. All the jobs are live testing and your under pressure to complete the work, present a vlog and sell the latest product for Artisan. I'm not having a go at you Cory, as a fellow electrician we are at most risk of elecutracution due to complacency and the nature of the job.
    I wonder how all these TH-cam electricians would fair if an accident happened, HSE would no doubt scrutinise the channel content against the job RAMS, tool box talks and whomever is the lead electrician on site.

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว +1

      Very true - it’s so easy to become complacent. Thanks for sharing

  • @gctelectrical5555
    @gctelectrical5555 ปีที่แล้ว

    Non fire rated downlights with room above... C2 as per Codebreakers

    • @sdgelectronics
      @sdgelectronics ปีที่แล้ว

      Only C2 if the ceiling forms a fire barrier. Unlikely in a standard 2-storey house.

  • @duncanmast
    @duncanmast ปีที่แล้ว +1

    The customers know their property is being filmed so why on earth do they not tidy up a bit and put all their day to day living crap and stuff away and at least clear the area around where work needs to be done. Some of the places you go to look an absolute dive excluding the ones under refurb obviously.

    • @mikeypc3592
      @mikeypc3592 ปีที่แล้ว

      Give it a rest you old woman🤣

  • @willywonka5796
    @willywonka5796 ปีที่แล้ว

    Whoever has done the soldering on those joints needs to go back to college ...

  • @dmarriott9701
    @dmarriott9701 ปีที่แล้ว

    No offence Cory but why is an electrician fault finding a water flow problem?

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      The original call was a suspected boiler fault.

    • @dmarriott9701
      @dmarriott9701 ปีที่แล้ว

      @@artisanelectrics As a retired plumber/heating engineer I’m surprised that the first port of call for such a problem was an electrician rather than a plumber/heating engineer. After being self employed for just over 50years I’m pretty sure most of my customers would have contacted me before an electrician. I’m sure that if this job was at one of your customers then that is the reason for you getting the call. Love Cory’s sense of humour, (rumour has it that Pringles manufacturers have had to set up another shift to fulfill his appetite.)

  • @JohnCap523
    @JohnCap523 ปีที่แล้ว

    Honeywell zone valves suck.

  • @tobysherring1369
    @tobysherring1369 ปีที่แล้ว

    That quinetic box is so ugly! Hard to know what else you could do though.

    • @artisanelectrics
      @artisanelectrics  ปีที่แล้ว

      Yeah at least it’s hidden in the utility room

  • @waynenrich
    @waynenrich ปีที่แล้ว

    Aww brew up lad
    Breaking the rules and regs tut tut

  • @lewistempleman9752
    @lewistempleman9752 ปีที่แล้ว +1

    Fake natty

  • @songhaihu3968
    @songhaihu3968 ปีที่แล้ว

    请不要过多拍摄他的脸,他不是好莱坞电影明星!这是教学视频请多拍摄他做的主要工作和电器

  • @victor-hn1bh
    @victor-hn1bh 8 หลายเดือนก่อน

    Complete new valve is best especially if body is stiff and motor faulty, fotget all that stripping down nonsense sorry but heating engineer is best for this job👎

  • @gmeadowcroft84
    @gmeadowcroft84 ปีที่แล้ว

    Embarrassing moment, I been using fluke tester for the last 2 years and never knew you could put a crock clip on the end of push button prob 🫢. Thanks Cory

    • @corynoahmac
      @corynoahmac ปีที่แล้ว +2

      You’re welcome!