This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me.
Aoa. Sir mery pass srt 5 kva Hy . Aur inverter hard ware kit fault Hy. Sari drives thek Hein aap k procedure se check kerne se. Sary igbt aur mosfets bhi thek Hy koi physical demage bhi nahi hy. Sir koi hal Bata dein
Asalamualaikum Wr.WB Sir, I don't have a SURT board. if I use a signal generator, what frequency and voltage do I use, can it be a square wave or must be a sine wave, thanks
I've tried this on two UPS now - SRT6K and SRT5K - with 02000 Event code 107 - in both cases all of the outputs read 17.xx volts when triggered with the 3VDC button cell. Do you think there is anywhere else worth checking? One of them seems slow to raise to 17.xx VDC. I am thinking to swap that and see.
@@upstrader Don't apply 3VDC directly on optocouplers input. Use 100 Ohm resistance in series with 3v cell. This is what I am sharing is not SOP OF APC but my shortcut to reduce time. Otherwise you will use signal generator, power supply and oscilloscope to check optocouplers. replace weak Optocoupler.
@@AKElectroTech OK I will repeat with the 100 Ohm resistor in series with the button battery. I love your signal generation setup. I will make a short video and send to you via whatsapp
Salam, Sir, i am repairing a APC symmetra Power Module Aray 4KV. I have repaired three module but after istalled in UPS its not working. Its still showing Red light indicated Error. In this UPS modal simplu showing error but not showing which error i a showing that's why I am not successfully repaired it.
@@AKElectroTech I think you're not understand... APC symmetra power module repair kr rha hn 4kv... Jo components burn hty h wo ma change kr deta hn but module khr b nhi chalta UPC ma lgaty h to fault error show krta h...
Us ma 3 board use ho rhy h ... Power board , Control board and Analog board... Ma in 3boards ko one by one lower da kr Kesy components ko test kr skta hn.. Ye tareeka mujy bta da please...
DMM sa hr ak component test krta hn ... But phr b fault resolve nhi kr pa rha ... I think so PMW IC ma issue ho skta h... Koi IC khrab h jis ki wja sa wo work nhi krta
In your case was there any physically visible sign of fault with the driver sub-board? Was it a broken resistor or diode? If so I could probably check the driver boards more quickly, and not needing to make a signal frequency. Thank you for your in depth video. Subscribed and liked.
No There is nothing physically damaged any diode or resistor. But I have done it for knowledge sharing. I think this is easy way to understand drive board.
Sir i have sa ups apc srt10va that is showing 02000 with an error log Output relay weld code 164. ..what is the possibility fault and how to repair it?
Output relay weld event code is 165 for SRT10kva ups. Now coming to Output relay weld. Output relay may be fault or drive of relay is misbehaving. Traic across relay may be short or drive of traic.
Pl see video carefully. Same fault with "Inverter Hardware Ckt Event code 107" First check IGBT and drives as shown in video. If problem remain then refresh EEPROm. I hope you will find solution
Abbas Khan As per your statement your UPS is dead and no response when switching on UPS. There are various conditions. Battery fuse F1 may be open. Resistors R212, R245, R246 and R247 all having 4.7ohm resistance connected in parrallel may be open. Q40 chopper switching transistor may be faulty. R71, R194 and R195 having 1ohm value may be open. IC12 UC3843 may be faulty. Q45 used to switching ON UPS may be faulty. Or Check "ON button". With ribbon cable. I hope you will find any solution regarding your fault for 4G 3KVA Pinto Tower UPS.
Assalamu'alaikum,Sir,Is there another solution, if we can't trigger pin number 2.4 on IC TC 4427? because I don't have a circuit board to trigger it, Can we make a simple circuit to produce high frequencies?
This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me.
asslamualikum Sir, video super sekali sangat membantu...
Thanks
Aoa. Sir mery pass srt 5 kva Hy . Aur inverter hard ware kit fault Hy. Sari drives thek Hein aap k procedure se check kerne se. Sary igbt aur mosfets bhi thek Hy koi physical demage bhi nahi hy. Sir koi hal Bata dein
WAS
Pl copy software in Description of video and reflash EEPROM
Asalamualaikum Wr.WB Sir, I don't have a SURT board. if I use a signal generator, what frequency and voltage do I use, can it be a square wave or must be a sine wave, thanks
@@aqilasyafamuthianingsih477
You can use 30khz to 50khz @ 15V signal.
@@AKElectroTech square Signal, Sir?
@@aqilasyafamuthianingsih477
Sine wave or you may apply sq wave
hello sir
is it normal to have flash arc from the back of the ups SRT10kva while doing ups test from the settings ?
No
HELLO ....
TELL ME PLEASE IF YOU CAN HOW TO RESET OR CLEAR THE : FAULTY ERROR STATE ? AFTER REPAIR ,AND THEN OPERATE TESTING UPS .
@@giorg6959
Repair hardware issue showing in log history, and clear alarms
@AKElectroTech THANK YOU .
I've tried this on two UPS now - SRT6K and SRT5K - with 02000 Event code 107 - in both cases all of the outputs read 17.xx volts when triggered with the 3VDC button cell. Do you think there is anywhere else worth checking?
One of them seems slow to raise to 17.xx VDC. I am thinking to swap that and see.
@@upstrader
Don't apply 3VDC directly on optocouplers input. Use 100 Ohm resistance in series with 3v cell.
This is what I am sharing is not SOP OF APC but my shortcut to reduce time. Otherwise you will use signal generator, power supply and oscilloscope to check optocouplers.
replace weak Optocoupler.
@@AKElectroTech OK I will repeat with the 100 Ohm resistor in series with the button battery.
I love your signal generation setup. I will make a short video and send to you via whatsapp
@@upstrader waiting at 00923215717132 wattsapp
I need your help and your instructions. Thanks
What's up
@@AKElectroTech are you saying Whatsapp?
I give you Whatsapp number?
Salam,
Sir, i am repairing a APC symmetra Power Module Aray 4KV.
I have repaired three module but after istalled in UPS its not working. Its still showing Red light indicated Error.
In this UPS modal simplu showing error but not showing which error i a showing that's why I am not successfully repaired it.
Pl install one by one in casing and switch it ON. You will fund Which module is not working
@@AKElectroTech I think you're not understand...
APC symmetra power module repair kr rha hn 4kv...
Jo components burn hty h wo ma change kr deta hn but module khr b nhi chalta UPC ma lgaty h to fault error show krta h...
Us ma 3 board use ho rhy h ...
Power board , Control board and Analog board...
Ma in 3boards ko one by one lower da kr Kesy components ko test kr skta hn..
Ye tareeka mujy bta da please...
DMM sa hr ak component test krta hn ...
But phr b fault resolve nhi kr pa rha ...
I think so PMW IC ma issue ho skta h...
Koi IC khrab h jis ki wja sa wo work nhi krta
In your case was there any physically visible sign of fault with the driver sub-board? Was it a broken resistor or diode? If so I could probably check the driver boards more quickly, and not needing to make a signal frequency. Thank you for your in depth video. Subscribed and liked.
No
There is nothing physically damaged any diode or resistor. But I have done it for knowledge sharing. I think this is easy way to understand drive board.
@@AKElectroTech Hello! Did you simply swap the whole small board out?
You mean control card.
Sir, what frequency must we use for the oscillator..? The level is clear.! Thank´s a lot
You can use 30k to 50k for checking purpose.
Thank´s a lot ! Greetings from Argentina..@@AKElectroTech
Wellcome
Thank you for this .. love from Nigeria... Please do more videos for us on apc .. my notifications bell is on
Ok brother
Thanks
Can you provide a drawing of where the 24v feed and triggering the gate driver?, or tell how trigger?
Brother
Pl see full video. At the end of the video you can see drawing of video and circuit to apply 24V and triggering with full detail on page.
thank you very helpful video
Thanks
Sir i have sa ups apc srt10va that is showing 02000 with an error log Output relay weld code 164. ..what is the possibility fault and how to repair it?
Output relay weld event code is 165 for SRT10kva ups.
Now coming to Output relay weld.
Output relay may be fault or drive of relay is misbehaving.
Traic across relay may be short or drive of traic.
This fault is it on the inverter board or the pfc board ?
Inverter output relay located on inverter board
Sir optocoplor 3121 out put se igbt ke gate tak ka complet circuit par tapsil se bat kare
Ok pl wait
Sir apc srt5kxli error p13 event log inverter hardware ckt event code 107, how did repair
Pl see video carefully.
Same fault with "Inverter Hardware Ckt Event code 107"
First check IGBT and drives as shown in video. If problem remain then refresh EEPROm.
I hope you will find solution
I found that a line was broken due to corrosion, I have repaired it but the error is still the same
@@dimanaaja1910 pl wash your board to clear corrosion on board.
Sir mere pass PCB 4G 3KVA PINTO TOWER UPS ON NAHI HO RAHA TOTALLY
Abbas Khan
As per your statement your UPS is dead and no response when switching on UPS.
There are various conditions.
Battery fuse F1 may be open.
Resistors R212, R245, R246 and R247 all having 4.7ohm resistance connected in parrallel may be open.
Q40 chopper switching transistor may be faulty.
R71, R194 and R195 having 1ohm value may be open.
IC12 UC3843 may be faulty.
Q45 used to switching ON UPS may be faulty.
Or
Check "ON button". With ribbon cable.
I hope you will find any solution regarding your fault for 4G 3KVA Pinto Tower UPS.
Bhai iska serial number change karne ka tarika bata dein
@@babarsultan8167
It's only a repairing guide. No such facility is available at my side.
@@AKElectroTech bhai dhond dein 🚬😊me sudia se ho suna hai pak me huta hai iska serial number change me apko payment krwa do ga iski
Refurbished APC Symmetra Power Array 4kVA Power Module PN: SYPM
I am working on this module.
Pl install one module in UPS and check it. Repeat for all
@@AKElectroTech UPS old Waly use ho rhy h APC jis k display ma error show nhi hta bs Red light chal jati h Jo k faulty ko present krti h
Assalamu'alaikum,Sir,Is there another solution, if we can't trigger pin number 2.4 on IC TC 4427? because I don't have a circuit board to trigger it,
Can we make a simple circuit to produce high frequencies?
WAS
Yes of course
But your oscillating level would be between 0v to 15v
Sir pl share ur No and ur workshop Location. I have APC ONLINE USP SURT 10000XLI. SHOWS BYPASS RELAY FAULT.
04235778236
00923215717132 wattsapp
Lahore
Thanks sir for reply. I saved ur No. Thanks a lot
Wellcome