APC 10KVA ON OFF fault | APC SURT UPS ON Off Fault | APC 10KVA UPS Repairing
ฝัง
- เผยแพร่เมื่อ 25 ส.ค. 2023
- #apc #ups #upsrepairing #apcups
APC 10KVA ON OFF fault | APC SURT UPS ON Off Fault | APC 10KVA UPS Repairing
apc 10kva ups
apc 10kva online ups
apc ups repair
apc ups not powering on
apc ups
apc ups not turning on
apc ups not starting
apc ups on off
apc ups fault
apc
ups repair
online ups repair
apc surt 10000 xli
apc surt
#apc #ups #upsrepairing #apcups #repairing #electronicsrepair - วิทยาศาสตร์และเทคโนโลยี
Allah sabko kamyabi ataa farmaye... 🙏🙏🙏🙏
Ameen
❤️@@AKElectroTech
Control card me logic supply ka fualt bta dain please
IC59 and IC58 are used for logic supply fault
Ji thank you so much Mai try krta hu
Greeting Sir, If this issue occur in SURTD3000XLI model then the component number (Q65, R578, R579) is same or different, if different then please state the component number. Thanks in advance
Then it will be Q18, R167 and R168
@@AKElectroTech Thanks
If the UPS battery reads 0%, what should I check?
Ups model 10kva
Pl mention model and brand of UPS
Location please
Lahore
Sir suitch py 11.25 v aa rhy hain or Q65 b thek ha resistors b thek hain on ni ho rha , msla or kya kya ho sqta h plz gaiude
Supply cards be faulty. Check Q703 and 706 on supply card.
Sir both Q703 &706 mosfets are ok volatge 11.35 on switch same . Not power on . Plz help
Dr asl iski ic 3843 burn hoe thi or 10 ohm ka restor Throug hole wala
@@user-kf2lt1ii2g
Then also check Q704 and IC with attached components
Aoa sir ap repair bhi kerte han
WAS Yes