This is the best video I have ever seen better than a trainer. Very well explained step by step backed up by evidence and pictures. Sound quality is excellent You are a Legend ❤❤❤❤
I had same problem However British Gas had been servicing the boiler 7 years prior. Never taken the case off. The electrodes worn out, gasket on heat cell disintegrated ! The top baffle had blown! And bottom baffle stuck ! Also reset gas valve too. Same process as yours just about adjusting gas valve to suit But we’re putting a new heat cell in next
Unfortunately big companies don't live upto their names when it comes to standard of work. If the work is carried out according to correct procedures. Maintenance would be easy and a lot less hassle. BTW. Did you have that main hx put in?
Hi F Raj brilleant video now we know how to turn minnimum and maximum totally off and 3 and half turn and 2 and half turn for minnimum to atleast keep the boiler going Do u know how to do it with vaillant and baxi 2 which flue analyser would u recomend not happy with anton need to buy different one Thaanks
Hi. Thanks for your kind message👍. I've tried this, on Vaillant's EcoFit pure. I'll try and make a video sometime. Haven't tried on other models or Baxi. I've mostly used Anton and worked fine for me. Have used Kane Abalyzer's older models. Does the job well but was chunky. Not sure about newer models.
Was at one of these today greenstar 15ri the data badge said co2 9.6%/8.6% the only manual I could find said 9.8%/9.2% so which do I go by? Any info by anyone would be greatful thanks
Hi. It is in the little document, shown in the video. Time is 12min 44seconds. This document usually comes with a new gas valve for several worcester models.
This is the best video
I have ever seen better than a trainer.
Very well explained step by step backed up by evidence and pictures.
Sound quality is excellent
You are a Legend ❤❤❤❤
Wow.. Very kind words 🤩. Made my day 😎👍
Good presenter. Very clear presentation.
Very helpful video, explained really well and clearly 👍
Thanks 😎👍
Better than WBosch training I can assure you - thank PaaG
Thanks. Very kind 😌
Nice one Raj...
Also if the adjustments on the valves don't work you need to check the bearing plate washer..
Love your work as always, mate. You are one of the best on TH-cam I watch. Keep on making em
I had same problem
However
British Gas had been servicing the boiler 7 years prior. Never taken the case off. The electrodes worn out, gasket on heat cell disintegrated ! The top baffle had blown! And bottom baffle stuck ! Also reset gas valve too.
Same process as yours just about adjusting gas valve to suit
But we’re putting a new heat cell in next
Unfortunately big companies don't live upto their names when it comes to standard of work.
If the work is carried out according to correct procedures. Maintenance would be easy and a lot less hassle.
BTW. Did you have that main hx put in?
Quality video 👍
Thank you 🫶
Nice one.. had to do this a few times, keeping the burner lit on minimum can be tricky, especially on the 12 and 15KW models.
12 n 15kw ones can be a pain to adjust
very well explained. Well done. thanks
Thank you 🫶
brilliance
Thank you 👍
Great video
Thanks 👍
Hi F Raj brilleant video now we know how to turn minnimum and maximum totally off and 3 and half turn and 2 and half turn for minnimum to atleast keep the boiler going
Do u know how to do it with vaillant and baxi
2 which flue analyser would u recomend not happy with anton need to buy different one
Thaanks
Hi. Thanks for your kind message👍.
I've tried this, on Vaillant's EcoFit pure. I'll try and make a video sometime. Haven't tried on other models or Baxi.
I've mostly used Anton and worked fine for me. Have used Kane Abalyzer's older models. Does the job well but was chunky. Not sure about newer models.
Was at one of these today greenstar 15ri the data badge said co2 9.6%/8.6% the only manual I could find said 9.8%/9.2% so which do I go by? Any info by anyone would be greatful thanks
Data badge is on the appliance. I would say go with that
Can I ask where you got the 3.5 turns and the 2.5 factory reset information from please ?
Hi.
It is in the little document, shown in the video. Time is 12min 44seconds. This document usually comes with a new gas valve for several worcester models.