REFRIGERANT COMPRESSOR | Gas Charging | Without Vacuum Pump | Technical Vlog : 049

แชร์
ฝัง

ความคิดเห็น • 23

  • @MechanicalEfficiency
    @MechanicalEfficiency 6 หลายเดือนก่อน +1

    ❤❤❤❤❤

  • @myatkyawchitthan5709
    @myatkyawchitthan5709 9 หลายเดือนก่อน

    Thank you very much. 😬

  • @thawaung8567
    @thawaung8567 ปีที่แล้ว +1

    Very nice video and good explanation.

  • @omerasan6084
    @omerasan6084 ปีที่แล้ว

    very informative

  • @mec6953
    @mec6953 ปีที่แล้ว +1

    nice voice.
    i also learned for my exam how to charge refrigerent.
    normally i prefer charging at high pressure side (liquid charging).
    charging point is after the receiver, near dryer/filter

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว +1

      Thanks Dear.
      Charging point depends upon types of the plant. Most of air conditioning plants, charging point is placed over the cover of dryer housing. In this type, dryer is exchangeable core type dryer.

    • @mec6953
      @mec6953 ปีที่แล้ว +2

      @@MoeMyintShein1987 sir, i learned from the book that for liquid charging i need to "incline" or "upside down" the refrigerant cylinder. but your video, it was upright. can you pls help?

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว +3

      @@mec6953
      Depend upon types of Refrigerant Cylinder. Cylinder with or without siphon tube. If cylinder has siphon tube, doesn’t require to upside down. If not, need to upside down the cylinder. Siphon tube is a tube which extend from the bottom of cylinder to the cylinder valve, top of cylinder. Sooner I will upload in COMMUNITY with photo. 😊

    • @mec6953
      @mec6953 ปีที่แล้ว +1

      @@MoeMyintShein1987 thanks🙏🙏

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว +1

      @@mec6953
      Uploaded in COMMUNITY, Bro.
      Check There. 😊

  • @thantzinaung6650
    @thantzinaung6650 8 หลายเดือนก่อน +1

    May I know something.
    Fully open the gas bottle valve and then slowly open the charging valve. At that time the compressor is running or stopping.?
    Thank you.

    • @MoeMyintShein1987
      @MoeMyintShein1987  8 หลายเดือนก่อน +1

      Compressor is going to run with LP cut in, when suction line pressure is rising up. LP cut out will happen when suction line pressure is lower than LP setting.
      Compressor running and stopping may happen alternatively. Thanks.

    • @thantzinaung6650
      @thantzinaung6650 8 หลายเดือนก่อน +1

      So, is the compressor in auto mode?

    • @MoeMyintShein1987
      @MoeMyintShein1987  8 หลายเดือนก่อน +1

      @thantzinaung6650
      Prefer Auto.

  • @dingsfishingtv5859
    @dingsfishingtv5859 ปีที่แล้ว

    hello Good day!
    maybe can you make a video about how to change crankcase oil of a reefer compressor?? thank you.

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว +1

      Going to release sooner.
      Keep in Touch. 😊

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว

      Dear Dings,
      I have uploaded about charging crankcase oil of refer compressor without vacuum pump. Hope u r going to catch something from that vlog.

  • @mec6953
    @mec6953 ปีที่แล้ว +1

    sir, after charging finish, where do i need to note it down?
    in log book or some other place?

    • @MoeMyintShein1987
      @MoeMyintShein1987  ปีที่แล้ว +2

      If your refrigerants onboard is Freon, which can affect the Ozone, we need to record in Ozone Depleting Substance Record Book. If other gases which cannot affect Ozone, doesn’t need to record in ODS record book. As Normal, we record in C/E Log Book and also Need to Substrat the charged refrigerant amount from monthly R.O.B at the end of month.

    • @mec6953
      @mec6953 ปีที่แล้ว +1

      @@MoeMyintShein1987 many thanks😍