EG4 Chargeverter Teardown & Overview 🔌 Testing the Capabilities of the EG4 Chargeverter!

แชร์
ฝัง
  • เผยแพร่เมื่อ 30 ก.ย. 2024
  • Introducing the Chargeverter 5000 from EG4 Electronics! In this video, we'll explore this innovative device, which takes the charging circuit from EG4's inverters and turns it into a standalone battery charger. It's a unique and highly practical device that's perfect for off-grid setups!
    One of the standout features of the Chargeverter is its ability to turn potentially dirty generator power into clean DC power, eliminating the need for complex power transfers and potentially saving you money on generator costs!
    The Chargeverter can also bring a fully depleated lithium battery back to life, making it incredibly versatile. Plus, it comes with a built-in 125 Amp DC circuit breaker, saving you the expense of additional fuses.
    And of course, we can't forget the teardown! You'll get an inside look at the Chargeverter's components, including the rectifier modules commonly found in the telecom industry. This reveals the device's robust and reliable design.
    We hope you found this video informative and enjoyable. Don't hesitate to leave your questions and comments below, and please consider hitting the thumbs-up button if you found this video helpful. Thanks for watching, and we look forward to hearing from you soon!
    🛒 Check out the EG4 Chargeverter: www.currentcon...
    #eg4 #Chargeverter
    ✅ Our Top Pick LiFePO4 Batteries by Voltage & Capacity: 🔋
    1️⃣2️⃣V Batteries: 🔋
    ▪️ Epoch Essentials 105Ah Battery - www.currentcon...
    ▪️ Epoch Essentials 300Ah Battery - www.currentcon...
    ▪️ Epoch Essentials 460Ah Battery - www.currentcon...
    ▪️ Epoch Pro 460 Ah Battery - www.currentcon...
    ▪️ EG4-LL 400Ah Server Rack Battery - www.currentcon...
    2️⃣4️⃣V Batteries: 🔋
    ▪️ EG4-LL 200Ah Server Rack Battery - www.currentcon...
    ▪️ EG4 LifePower4 200Ah Server Rack Battery - www.currentcon...
    4️⃣8️⃣V Batteries: 🔋
    ▪️ EG4 LL-S 100Ah Server Rack Battery - www.currentcon...
    ▪️ EG4 LifePower4 100Ah Server Rack Battery - www.currentcon...
    ▪️ EG4 Indoor WallMount 280Ah Battery - www.currentcon...
    ▪️ EG4 PowerPro Outdoor WallMount 280Ah Battery - www.currentcon...
    ✅ Our Top Pick Inverter/Chargers by Voltage: ⚡
    1️⃣2️⃣V Inverters: ⚡
    ▪️ Victron 12V Quattro-II 3kVA 2x120V - www.currentcon...
    ▪️ Victron 12V MultiPlus-II 3kVA 120V - www.currentcon...
    ▪️ Victron 12V MultiPlus-II 3kVA 2x120V (UL Model) - www.currentcon...
    2️⃣4️⃣V Inverters: ⚡
    ▪️ Victron 24V MultiPlus-II 3kVA 2x120V - www.currentcon...
    ▪️ Victron 24V MultiPlus-II 3kVA 120V - www.currentcon...
    ▪️ Victron 24V Quattro-II 3kVA 2x120V - www.currentcon...
    4️⃣8️⃣V Inverters: ⚡
    ▪️ Eg4 3000 EHV-48v Inverter/Charger - www.currentcon...
    ▪️ EG4 6000XP Off-Grid All-in-One Inverter/Charger - www.currentcon...
    ▪️ MidNite Solar Rosie 7048RE 7000W Inverter 120Amp Charger - www.currentcon...
    ▪️ MidNite TheOne - 11.4kW Hybrid All-in-one Inverter - www.currentcon...
    ▪️ EG4 12kPV 48V 8kW Hybrid All-In-One Inverter - www.currentcon...
    ▪️ Sol-Ark 15kW All-In-One Hybrid Inverter - www.currentcon...
    ▪️ EG4 18kPV | 48V 12kW All-in-One Hybrid Inverter - www.currentcon...
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 53

  • @joshg1244
    @joshg1244 ปีที่แล้ว +2

    I wish these existed when I built my first system as I would have moved up to 48V (small system)
    I also wish they made a 24V & 12V versions

  • @craigbourgeois437
    @craigbourgeois437 21 วันที่ผ่านมา

    Thanks for tear down mine did not have glue and one of the boards was out of place causing it to only put out 50 amps

  • @bhbaker220
    @bhbaker220 ปีที่แล้ว +1

    So, if you don’t use an EG4 inverter in pass through mode, you can use a non-inverter generator to charge the batteries? There’s no clean up of the dirty power in the chargeverter, it just guarantees that dirty power does not go through the inverters to the loads?

  • @oswaldmosley6179
    @oswaldmosley6179 6 หลายเดือนก่อน

    My generator as a NEMA L5-30R 120v 30A output in Sine wave, do I need an adapter of some kind and if so what one?

  • @HenkBronkhorst-c8c
    @HenkBronkhorst-c8c 5 หลายเดือนก่อน

    your not even talking about 20 % from users the other 80 % using simply single phase

  • @peterking1134
    @peterking1134 ปีที่แล้ว +2

    Can one power supply be connected to multiple batteries?

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว

      Yes, for example if you have multiple batteries in parallel

  • @nicholasthon973
    @nicholasthon973 7 หลายเดือนก่อน

    Does this work with a Tesla Powerwall?

  • @AdamDeLay07
    @AdamDeLay07 ปีที่แล้ว

    Thanks for sharing! I didn’t know they modified the unit to slowly ramp up. The original units used to just discharge full power as soon as they were turned on. Also good to see they resolved the loose module issue, albeit kinda messily, but still resolved it.

  • @obd6HsN
    @obd6HsN ปีที่แล้ว +1

    Can we please have these in Europe???

  • @hmtechsvc
    @hmtechsvc ปีที่แล้ว +1

    could you please consider making a video with more details on how battery activation works? nobody ever talks about that - but it seems all bms work that way (you have to activate it in some manner) - i'm just looking to understand how it all works - where did this method come from - idk - just very very grateful for your content and channel!

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว

      Check out this video that we made, it could be what you're looking for: th-cam.com/video/TJ_Klwp-JyM/w-d-xo.html

  • @colormaker5070
    @colormaker5070 ปีที่แล้ว +1

    Great timing I was just about ready to make an adapter plug for use on 120VAC. With Idalia at my doorstep it will get a good workout. EG4 nailed this design it was like they read my mind on what I was looking for in a high current charger.

  • @rongray4118
    @rongray4118 8 หลายเดือนก่อน

    I am actually on the phone (on hold) with Signature Solar right now. I would like to know why this charger is limited to Lithium Battery Banks. I do not understand why it cannot be used for Glass Mat Based Battery System. Would you have any thoughts in regard to why? I am interested in hearing your thoughts. We have (2) 48 volt ABSOLYTE GX Battery Banks @ 2,000 Amp Hours Each and I don't think that this could ever over power the banks but I could be wrong. If it is charging parameters this could be compensated with the same manner of adjustment that is being done with your generator, correct? Or am I completely wrong in my thinking?

  • @RonKatz
    @RonKatz 8 หลายเดือนก่อน

    Nice, but no electrical approval. Not UL listed or CSA approved. Big issues with electrical safety.

  • @shaunnightfire8269
    @shaunnightfire8269 7 หลายเดือนก่อน

    Could you get the full 100a output with dual 120v generators using a parallel kit. Seems each module is just 120v and 240v is not actually needed for full power.

  • @marek8928
    @marek8928 11 หลายเดือนก่อน

    Can this Chargeverter be supplied by 120V 400Hz generator or 120-200V DC?

  • @HippocratesGarden
    @HippocratesGarden 10 หลายเดือนก่อน

    I've got one of these on the shelf I've not yet installed, but think I need to. My intermediate setup is a full stack of 6 of the LL Batteries and an EG4 3k/48v all in one. I was trying to charge the battery from a 2k inverter/generator via the AC-IN on the all-in-one and wasn't getting more than 500-600W with zero loads. Could not find a setting that would bring it even to 1k. Seeing this can ramp the amps down, I'll hook it up and find a sweet spot to run the inverter/generator most efficiently and see how that does. Thanks.

  • @goodcitizen4587
    @goodcitizen4587 ปีที่แล้ว +1

    $400, cool. Thanks for opening it up.

    • @billykulim5202
      @billykulim5202 9 หลายเดือนก่อน

      so basicaly it just 2 telecom 50a powersupply whic on parallel connection and add a module to control the output interface?, and those telecom powersupply you can get $50 each used???

  • @RussellHogan
    @RussellHogan ปีที่แล้ว +1

    So can hook this directly to the top and bottom of my 25K SOK server rack battery bank?

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +1

      Yes, or if you have a bus bar that the rack hooks to, the charger can feed to that bus bar as well.

    • @RussellHogan
      @RussellHogan ปีที่แล้ว +1

      @@CurrentConnected Mahalo!!!

  • @GG-sj2wg
    @GG-sj2wg 7 หลายเดือนก่อน

    Had one since they first came out. Love it.

  • @Sylvan_dB
    @Sylvan_dB ปีที่แล้ว

    The "silver boxes" look more like two server power supplies.

  • @LarryRichelli
    @LarryRichelli 11 หลายเดือนก่อน

    In the USA these cost $400 but in Asia they are $80.....makes one wonder what is going on!

    • @otm646
      @otm646 8 หลายเดือนก่อน +1

      Where are you finding them for $80?

  • @icarus901
    @icarus901 ปีที่แล้ว

    Can't wait for the baker's dozen test. Thanks for doing a breakdown on these units!

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +1

      th-cam.com/video/OHAXydKthXM/w-d-xo.html Here ya go!

  • @acinfla9615
    @acinfla9615 11 หลายเดือนก่อน

    I got mine when they first came out and it has worked great.
    I can charge with a small generator or a large one without damaging the charge controller.

  • @randallmarshall3603
    @randallmarshall3603 ปีที่แล้ว

    Too bad it's only good for 48v batteries. I would love a 36v version. I use the EG4 36v charger which gets the job done but slowly.
    And you mentioned 208v AC input which makes me think 3-phase but I don't see this mentioned in the manual. Did you mean 220v / 240v split phase?

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +1

      The output voltage can go down to 42v, so, if that's within the upper charge limit of your 36v batteries it can theoretically work.
      We tested running it on 208v (two lines of a 3 phase system) and it works just as well as at 240v!

    • @uselesseater5916
      @uselesseater5916 5 หลายเดือนก่อน

      @@CurrentConnected 36v lead acid usually charges to 43v

  • @andreaskoumides9599
    @andreaskoumides9599 ปีที่แล้ว

    Will these work on a European grid, 230Vac 50Hz? I saw that the sticker on the psu you removed in the video is rated from 100-250V and 45-65Hz @ 8:42

  • @NukeFPV
    @NukeFPV 11 หลายเดือนก่อน +1

    Would have been nice to see the output on an oscilloscope .... So we can see the DC ripple etc and confirm it is actually clean output. Without that..... we're just taking their word for it. But thanks for another great video on a new product ;)

  • @JonOffgrid
    @JonOffgrid ปีที่แล้ว

    That nice but man it alot of $$$$

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +3

      Feel free to share what can do the same as this at a better price point. We will add it to our catalogue.

    • @otm646
      @otm646 8 หลายเดือนก่อน +2

      There is nothing close on the market that can do voltage and current control while delivering 100 amps at 48v for $400.

  • @gf3803
    @gf3803 ปีที่แล้ว +1

    Anybody know what gauge wire the unit uses on the DC side that connects to the battery?

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +1

      25 mm2 (which is around 4AWG)

    • @gf3803
      @gf3803 ปีที่แล้ว

      thank you!

  • @GoodmanMIke59
    @GoodmanMIke59 9 หลายเดือนก่อน

    You were recommended highly by Will Prowse, but PLEASE ... at 0:44 Never EVER say "to the next level!" ... SOOOO "millennial!" 😂
    Actually a little bit shy of using LFP batteries (SOOOO Boomer) because my grid tie, battery backup system is flooded lead acid, the last 12 years. I also operated a WW2 Victory Ship that could make turns without a candlepower of light ... So definitely geezer time.
    Off-grid cabin will have a 48 volt system charging to DC equipment, just enough solar to keep it floated. Likely AGM with this Chargeverter.
    Or not....
    th-cam.com/video/JOlaQwy7i9c/w-d-xo.htmlsi=qEIZrUNGshvPHsRR
    th-cam.com/video/Rp8Hspi4BC4/w-d-xo.htmlsi=cZ2UUAOjnuzPHDe6
    Build up from there ... Just comfort level for now. Possibly a hand truck system like Will Prowse built. THEN I'll use LiFePo4.
    Very good video.

  • @bill2292
    @bill2292 ปีที่แล้ว

    Nice video, great information, very educational! Am I correct that I can use this with 220 single phase?

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว

      That’s correct. Also on 120v, no problem.

  • @offgridmgtowhomestead2520
    @offgridmgtowhomestead2520 ปีที่แล้ว

    My friend got this, and it failed within 2 days. And now they have been silent in getting back to them.

    • @CurrentConnected
      @CurrentConnected  ปีที่แล้ว +2

      Well, that's an advantage in buying through us! If you need support we are available to help.

    • @BenBrand
      @BenBrand ปีที่แล้ว +1

      Through Signature Solar? I had to go through six units to get two working ones. And it took months through Signature Solar and their awful service. Right after that Current Connected started carrying them and I noticed that the two I finally got that were good were a second revision with changes that fixed some but not all of the issues. Hopefully that's why Current Connected stocked them later and Signature Solar was selling out of the original units that never should have left the prototyping bench.

    • @HighTechLab
      @HighTechLab ปีที่แล้ว +4

      @@BenBrand I just installed 12 for my parents on an 80kW generator. No problems on a single one. I’m posting a video on my channel tomorrow.

    • @CRsolar
      @CRsolar ปีที่แล้ว

      Hey that video is gone . Did you have an issue... I like your testing this stuff for me. Be honest now.