How Many 12V Batteries for 3000W Inverter

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 376

  • @cleversolarpower
    @cleversolarpower  3 หลายเดือนก่อน +28

    FREE diagrams: cleversolarpower.com
    UPDATE 1 : at 14:30 I used the wrong formula. It should be Capacity=Current/C-rate -> 250A/0.2C=1,250Ah.
    UPDATE 2: at 6:40 you should fuse every cable with a 200A fuse instead of one 350A fuse.
    My Best-Selling book: cleversolarpower.com/off-grid-solar-power-simplified
    Cables: amzn.to/3XbLfhn
    12V 100Ah Battery: amzn.to/3MgFdWw
    12V 200Ah Battery: amzn.to/3SYwtYI
    MRBF fuse holder: amzn.to/3X0bmqc
    MRBF fuse: amzn.to/4dXFNV5
    300A busbar: amzn.to/4dR4Zwj
    MEGA fuse: amzn.to/3AyrYht

    • @Romeo1800
      @Romeo1800 2 หลายเดือนก่อน

      I think there is still something wrong with calcs: 250A is the invtr max amps, C rate applies to batt amps not inverter amps: batt amps is 20A. So is it Inverter amps/C rate, or batt amps/C rate?

    • @Romeo1800
      @Romeo1800 2 หลายเดือนก่อน

      BTW, I am using 4- 6vdc Fullriver AGM batteries with a GoPower 3000W inverter. I installed the new AGM's yesterday, but was trying to chk, beforehand, if 4 batts would work with the 3000W inverter.

    • @jacobvastenhoud2456
      @jacobvastenhoud2456 2 หลายเดือนก่อน

      😊😊😊😊😊😊

    • @jacobvastenhoud2456
      @jacobvastenhoud2456 2 หลายเดือนก่อน

      😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊

    • @QuyHo-l8l
      @QuyHo-l8l หลายเดือนก่อน

      @@Romeo1800 kích 3000w 12v bao tien

  • @nobody1841
    @nobody1841 9 วันที่ผ่านมา +3

    Sailboat life (15 yrs) - my 329w hi output panel outperforms 500+ watt regular panels. I use 4 6v golf cart bats for total of 450 amp hrs. I often see the panel output 63+ volts and 20amp input from the Victron 30amp controller. I run a Victron inverter, and as a photographer I use calibrated monitor, computers, external drives, battery charging for many devices, etc.
    Add the frig, lights, 8 fans, a real hifi stereo, blender, water pumps, shower sump pumps and the batteries are usually floated back down by noon. Next time I'm going lithium, maybe add another panel. Maybe not. It's the high output panels that make it possible. Otherwise there would be many solar panels needed.
    If my sailing grounds weren't in FL, Bahamas, I would definitely need more panels, no doubt.

    • @johnconrad5487
      @johnconrad5487 3 วันที่ผ่านมา

      AMAZING... 4X 6v BATTERIES = 24V. Does your Victron Boost the voltage from 24V to 63+ Volts and you have all those other loads connected and running at the same time. Add the frig, lights, 8 fans, a real hifi stereo, blender, water pumps, shower, sump pumps??????????????

    • @nobody1841
      @nobody1841 3 วันที่ผ่านมา

      @johnconrad5487 Let's see if I can help understand this better. Goal is a 12v system. First concept in this is to double the volts. Then double the amps. Rule - when connecting batteries, we can either double the amps, or we can double the volts. We need to do both. We start w four 6v bats, 225amp each in this example.
      First, We want to connect two 6v bats in serial. We connect them pos to neg, which will create one 12v battery. Do the same w the other two batteries. Now we have created two 12v batteries at 225amps each. We have doubled the voltage but not the amps.
      Each set of two has one remaining pos post and one neg post.
      Next we connect them in parallel by connecting pos to pos and neg to neg. This has now doubled the amps to 450amps in a 12v battery bank.
      The charge controller manages the power input (solar panel). The panel can be 12, 18, 24, 36, 48 , whatever. Using the app, we tell the controller unit what our system voltage is. In my case it's 12v because my fridge fans and lights are all 12v. I hope this helps.
      Edit: The charge controller does more than manage the power coming into the system. It also manages the charging of the batteries so they don't over charge. These charge settings are peculiar to batteries by brand. The settings are obtained by visiting the battery brand website.

  • @toddstanley3619
    @toddstanley3619 6 วันที่ผ่านมา +3

    Overall this is a great video and very informative. Understanding types of batteries is important. Lead acid standard car batteries are not the same as lead acid deep cycle. Deep cycle batteries are used in heavy equipment, commercial diesel trucks, and marine applications.
    13 lead acid batteries is standard car batteries. If using marine or big truck 12 volt deep cycle the 4 is minimum 6 is good, 8 is best when talking about stored power. Deep cycle like LiPo discharges at a slower rate over time. Standard car batteries discharge quickly.

    • @cleversolarpower
      @cleversolarpower  4 วันที่ผ่านมา

      Indeed. Most people don't consider the c rates of different types of batteries .

  • @wilty5
    @wilty5 2 หลายเดือนก่อน +22

    As a beginner , I appreciate your your thorough and detailed explanation of the solar system setup. Thanks

  • @angrydutchman8590
    @angrydutchman8590 หลายเดือนก่อน +3

    Really awesome instructional videos . . . thank you! As a newbie to solar generated power, the 48v system you diagrammed in the video is very appealing. However, I am wondering if you might either, 1: add an addendum video on how to calculate needed solar panels to charge the EG4 battery, or 2: simply respond with the number needed and the calculation used to arrive at the required number.
    Thanks and keep up the great work!

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      i have made a video about how many solar panels you need.

  • @owolabiadeteye5919
    @owolabiadeteye5919 3 หลายเดือนก่อน +12

    Thanks for time taken to prepare and deliver this insightful lecture. Great one boss

  • @1GREATDANE
    @1GREATDANE 3 หลายเดือนก่อน +28

    RENOGY 3000 Watt Inverter is a Sour Purchase and Collects Dust here now, 4 RENOGY 200ah AGM Batteries barely Feeds It what It Needs with 4/0 Premium Wire and 300amp Buss Bars - I see Myself Selling It Soon and have opted for 24 Volt Victron Energy Inverters and Lithium Batteries now and in the Future.

    • @cleversolarpower
      @cleversolarpower  3 หลายเดือนก่อน +4

      Good choice 😉

    • @erroneouscode
      @erroneouscode 2 หลายเดือนก่อน +26

      I've been running the RENOGY 3000w inverter with 4x100ah RENOGY batteries in my 4x4 ute for over 2 years. When it's parked up at home it runs all refrigeration and computers in the house 24/7 and occasionally more when the suns out. I haven't had any issues with their gear. The batteries get charged via 2.6Kw of solar panels on the shed roof via Victron controllers. The batteries and inverter are wired much as Nick showed except the MRBF fuses are 100amp as with 4 batteries feeding a 3000w inverter they are never going to see 100amp drawn from a single battery.
      People wonder why some choose to stick with 12v particularly with recreational vehicles. The answer is simple. It's a pain in the backside trying to deploy enough solar panels out in the field with high enough VOC to charge a 24 or 48V battery system. Connecting multiple panels in series is impractical when camping. Then there is the huge expense of 12v-48v DC-DC chargers to take alternator current from a 12v system. Typically such DC-DC chargers are 3x the price of a 12v version. Or the alternative option of fitting a 24-48v alternator if space can be found in the engine bay. Then there's all the 12v camping appliances that now need buck converters. The 4/0 cable is only needed between the inverter, fuse for it, and Buss Bars. That's not a huge expense that those that advocate 48v continually bring out in discussions when compared to the additional cost of dedicated 48v gear and buck converters etc.

    • @1GREATDANE
      @1GREATDANE 2 หลายเดือนก่อน +3

      @@erroneouscode 4 RENOGY 200AH AGM Batteries was tried here with 1200 Watts of Solar and saw 50% Depth of Discharge way too often to Leave IT commissioned here on The Ranch

    • @erroneouscode
      @erroneouscode 2 หลายเดือนก่อน +2

      @@1GREATDANE Fair enough. But curious what made you even consider using AGM these days, especially with a 3000w inverter? What did you find wrong with the inverter?

    • @1GREATDANE
      @1GREATDANE 2 หลายเดือนก่อน +1

      ​@@erroneouscodeIt was Hungry and AGM Batteries are Best above 50% DOD and a Whole Ranch Kitchen was more than It could Handle at Night, TV and Internet Router, and few lights and Well Pump. Going 24 Volt I was able to Double My Solar Array and using 4 - 280ah CHINS LiPo4 with 200ah BMS paired up in 24 Volt Packs Works well with Victron Battery Balancers and Buss Bars and Correctly Fuses and 4/0 Cables to WZRELB 24 Volt 3000 Watt Inverter.

  • @perlarsen3645
    @perlarsen3645 หลายเดือนก่อน +9

    Wauw. A very instructive video, explained even so dummies like me understand it. Thank you

  • @dleon0902
    @dleon0902 หลายเดือนก่อน +3

    Is it not the load is the one that dictates the power needed? If the Load is a 700W Microwave, then a 100AH, 12v battery is sufficient. If your load will require 3K Watts, yes, then more batteries are needed like you stated.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      Yes, the load indicated the power draw. But if you have a 3000W inverter, you have to wire and fuse for a 3000W load.

  • @a64738
    @a64738 2 หลายเดือนก่อน +3

    With 4 100Ah 100A lifepo4 batteries and my 3000w 24v inverter I can use an electric oven with 2 cooking plates and electric oven with all 3 at full power at same time. And I can keep it running like that until the batteries is empty which will take 1,5 to 2 hours as I do not know the exact power usage of the electric oven. LifePo4 is the way to go for high power usage.

    • @claver99
      @claver99 2 หลายเดือนก่อน

      @a64738 how do you connect your battery bank reason being I have 4x12v 100ah lithium batteries and a 3000w 24v inverter.So I wondering if you would like to explain how you did it.

    • @burningbright5039
      @burningbright5039 หลายเดือนก่อน

      @@claver99you have to connect all your batteries to each other…you have solar panels and a controller unit too??
      Yeah they make tiny cables to connect the batteries to each other

  • @alwardslab8732
    @alwardslab8732 2 หลายเดือนก่อน +2

    nice, but i miss time in the ecuation... most uses are solar, so they will need an 8h buffer for the night, which means more batteries, also account for bad weather as in fog days, where batteries do not replenish.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      I have videos about that. Search my channel for load analysis.

  • @paulywally1957
    @paulywally1957 หลายเดือนก่อน +1

    I see what you're saying and how it looks like it all adds up but I have been running a 200 amp hour battery Bank lithium and a 3000 watt pure sine inverter to run my induction cookware my induction oven and every other appliance and have never had an issue. I even run an air conditioner that is an indoor one for my RV that vents out the window and it runs that fine too.

    • @stahpit1971
      @stahpit1971 หลายเดือนก่อน

      Pretty sure he's giving recommended usage. You are always free to burn your stuff up just make sure children and pets can be rescued safely.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      You can even use a 5000W inverter on a 12V battery, but that doesn't mean it's good design choices. I'm making people aware that there are better design options.

    • @JimSmith-q4o
      @JimSmith-q4o หลายเดือนก่อน

      How long will your system run of the battery’s?

  • @realToby
    @realToby 3 หลายเดือนก่อน +1

    I have the same 3000w 12v renogy inverter but i am limited to the 3 AC outlets which are Max 1800w(or 120v 15A) combined i think.
    I would need to use the hardwire output with at least 12awg cable to achieve the full 3000W.

  • @khieusovannara2281
    @khieusovannara2281 11 ชั่วโมงที่ผ่านมา

    It's well explaint and love to watch it but I'm not electrician, very little understand about wire and connection

  • @olbluetundra881
    @olbluetundra881 หลายเดือนก่อน +2

    The higher the input voltage on your unit the better. I run 48vdc input on my eg6. I also have 4 480w 48v solar panels on the roof. Built my own 48vlto batteries with 200amp bms. My batts are 245ah each. I even built a buzzer for when my voltage gets down 11.9 volts. This way i never really completely drain my lto. It's in my 8x12 portable shop trailer. This sits on top of my old champion 4550 gen that's been converted to run on propane. Mind you it's need a couple more batteries. Especially when I run the rooftop ac. Lights, cordless tool chargers and even my pancake compressor has no issues keeping up. Im building a capacitor bank to install and try out on the bigger loads to see if will help out.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      Yes, increasing the voltage of the battery bank has many advantages. I made a video about 12V,24V or 48V. Increasing the voltage of the solar panels as well as it reduces voltage drop over long distances (up to max input voltage of the mppt).

  • @Detour4it
    @Detour4it 3 หลายเดือนก่อน +16

    You know your science, and your videos are detailed and a great help.👍

  • @camielkotte
    @camielkotte หลายเดือนก่อน +1

    I installed a 24v (8 x eve 280k blocks) with fcao 3000 watt inverter. I go up to 2500watt, never Max out your system. Keep the overhead. The c rate of my battery is 0.5C meaning i can draw half of the 280 amps continuously which is 140 amps at 24 volt. The c rate is specified by the manufacturer. Not by TH-camrs.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      Standard charge/discharge for LF280K is 0.5C, Continuous charge/discharge is 1C, pulse charge/discharge is 2C. Check the datasheet for your cells. Also depends on the BMS you have.

  • @UmpTSquat
    @UmpTSquat หลายเดือนก่อน +2

    Nick, I am late watching this. I learned quite a bit from you in this video. Thank You. You explained things in a very easy to understand video. I have watched hundreds of hours of videos. I don't remember seeing it explained in this manner. Thank You again. I have subscribed. I'll go back and watch your other videos.

  • @Detour4it
    @Detour4it 2 หลายเดือนก่อน +2

    Been waiting patiently and it arrived today! What an amazing book(.) You've managed to put together a presentation of solar that (so far, from what I've read) is the best explanation on paper that I've experienced, and I've read through alot of books. Well worth the money. People contemplating solar will find this book 99% of the make it happen. Love it. 🫵👍👊

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      Thank you kindly!

    • @timkat630
      @timkat630 2 หลายเดือนก่อน

      The book is excellent !!

  • @RogueOntheRoad
    @RogueOntheRoad 2 หลายเดือนก่อน +1

    What I discovered is to supply enough current it is good to use the battery in parallel. The current rating using lifepo4 battery is greater than the actual available current rating. My battery is rated at 200 amps BMS but it can only provide 150 amps continuous. By placing equal battery in parallel The current available will be 300 amps.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      If you have been sold a 200A BMS and only get 150A out if it, you have been scammed 😬. Which brand?

    • @javaman2883
      @javaman2883 2 หลายเดือนก่อน

      So you actually have a 150A BMS which allows for a short term "peak current" of 200A. The BMS is rated at continuous current. Anything higher, like peak current or other short term current specification is just there because marketing likes bigger numbers.

  • @Sylvan_dB
    @Sylvan_dB 2 หลายเดือนก่อน +2

    Inverters also have a surge capacity, and if your batteries and wiring are inadequate you won't get the promised surge capacity.
    I also would not plan to run the batteries at their maximum amperage. I recommend a 25% margin for every battery added in parallel. (75% of each means 2 can do 150% of one, 3 can do 225% of one, etc)

    • @einfelder8262
      @einfelder8262 2 หลายเดือนก่อน +1

      If your inverter has surge capacity and your battery(s) also can handle the surge, you would blow your fuse if you use the fuse size specified in the video. Unfortunately, as good as the video is, no mention was made of this very real issue.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      No, wires can handle the surge capacity for a few seconds. While they are not sized for the surge it is no problem for them to handle a surge of a pump. If factories had to size their cables to the surge current then it would be much more expensive. It's not done this way. I worked as electrician a in a factory.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      No, there is a difference between surge capacity of a fuse and the short circuit current of a fuse. Mega fuses can handle many times their rated current for a few seconds. This is called the time-current curve. They are called slow blow fuses, used for starting inductive loads. You also have fast acting fuses for circuitry.

    • @Sylvan_dB
      @Sylvan_dB 2 หลายเดือนก่อน

      @@cleversolarpower wires can handle it, but with low voltage DC the voltage drop becomes critical even with short cables. 1v drop might be too much.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      @@Sylvan_dB Voltage drop is something else. It can happen. That means you are running too much power from your battery. Solution -> more capacity.

  • @javaman2883
    @javaman2883 2 หลายเดือนก่อน

    The purpose of the fuse is to protect the wire, which it may not do with two feed wires. If one wire gets a loose connection, gets damaged, etc, then all the current will go through your second wire. Since the 350A fuse will not blow, the 300A going through one 205A rated wire will cause excessive heat and potentially fire.
    Your two feed wires from the bus bar to the inverter should each have a fuse, say 180A, to protect that single wire.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      Yes, thats a mistake on my end when drawing the diagram. I will update it in the description.

  • @dangeary2134
    @dangeary2134 2 วันที่ผ่านมา

    Interesting.
    I was a trucker, OTR.
    Made my own coffee in a standard 12 cup coffee maker.
    Four commercial 12v batteries had enough juice, with the truck shut off, to make an entire pot off of a 3500 watt inverter, and still have enough juice in the batteries to start the truck.
    Knowing this, four batteries on a different setup, with a 10 amp charger was more than enough to make the coffee, and keep the batteries charged I had a second 3500 watt inverter to power a mini fridge.
    Since that was intermittent, I didn’t have to worry about the batteries running dry.
    I also would run a 750 watt microwave once or twice a day in this setup.
    I could charge these batteries by the charger on a land hookup, by the engine, or by a small 1200 watt generator holed up to the charger.
    The 1200 watt generator was enough to power a small window air conditioner, which cooled the small RV quite handily.
    2 ga wires in parallel were more than enough to hold all this current, but each of the inverters had their own wires.
    I should have tried solar panels to see if I could have used the panels without an outside source of power to see if it was sustainable.
    I didn’t use a whole lot of power, so it should have been enough to keep things going.

    • @cleversolarpower
      @cleversolarpower  วันที่ผ่านมา

      It depends on the load that is attached to the batteries. If your inverter is 3500W, but the load is only 1000W then it's different. This video is about showing how many batteries you need with a 3000W load.

  • @PraiseDog
    @PraiseDog หลายเดือนก่อน

    He did leave one thing out in my battery manual. For parallel the batteries are also cross connected as well as having a cable to the bus bar. Why I could only speculate, but I expect there is a reason for it.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Parallel is all positives together and negatives together. No crossing. I wonder what battery brand you have.

  • @maxheadroom8677
    @maxheadroom8677 2 หลายเดือนก่อน +1

    Hello Nick, this channel has great videos thanks. I have a question please. When you size battery/solar panel & charge time what happens if the load is on & used when the battery is being charged? I thought calculations are based on 'no load' conditions but with an off-grid system, it is used even when the battery is being charged. Can you please explain how using the load will or will not impact the charge time. I appreciate your response please.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +3

      If you have 100W coming in from solar, and you have a 200W load, then 100W will be coming from the battery. In off-grid design we do not calculate it that way. We have total daily power going in the battery and total daily power going out of the battery, then with 3 days of autonomy. Meaning that the battery has to last for three days without any power coming in.

  • @RubenWalsh-iv5ik
    @RubenWalsh-iv5ik 22 วันที่ผ่านมา +1

    I dnt think anyone will use 3000w at once. Maybe a fridge and some lights at most. Expecially in an offgrid setup. Do you do any solar setup consulting?

    • @cleversolarpower
      @cleversolarpower  21 วันที่ผ่านมา

      Indeed, but you still need to size for it. I do consulting, but I'm sold out for the moment. You can find it on my website.

    • @noturbizz1
      @noturbizz1 16 วันที่ผ่านมา

      Ideally, id design a system to use 90% of the rated power of an inverter most of the day. This is called clipping, most efficient. I would have a second inverter in parallel to deal with surge capacity and higher loads. I plan to live off grid on my land without a lack of power for less money than it would cost for power lines installed. I have to assemble the equipment though.

  • @mikehammond5248
    @mikehammond5248 หลายเดือนก่อน

    Below Update 2, you state we could use 200 a. fuse in lieu of 350 a. single fuse at the two parallel conductors. So use 200 a. fuse for each separate wire or could I use a 200 a. two pole conduct with both wires connected?
    This parallel conductors helps so wire is smaller and easier to work with.
    A 200 amp two pole / phase breaker could also be used for both wires connected to (12 v. DC)?
    I think I have watched all of oyur videos more than once. They are so educational, informative & easy to follow!!!
    Thanks for all you have done and continue to do for us off griders! The book helps a lot too!
    Mike

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Hello Mike, you need two 200A fuses. One for every cable. Thanks for your support! 🙏

    • @allangibson8494
      @allangibson8494 23 วันที่ผ่านมา

      Circuit breakers are superior to fuses in all applications.
      The issues are they drop 1V at full load and they need to be rated for DC load breaking.

  • @i-love-space390
    @i-love-space390 7 วันที่ผ่านมา

    An if you use 3000W for your devices, it will last less than an hour and totally drain the batteries. So for more capacity or power time, you will need a multiple of this equivalent to the number of hours you want to supply power.

  • @allangibson8494
    @allangibson8494 23 วันที่ผ่านมา

    Depends on the size of the battery…
    Earthmovers use a pair of 1500Amp/hr 12V batteries for starting.
    (The diesel fire pumps where I work also use two of them on each of the two redundant start circuits (and they are replaced every three years)).
    Your cable sizing calculations are wrong too because the current flow is not evenly split between two cables - 75% is the recommended assumption.
    BTW 120mm2 cables is easily available from welding supply stores…

    • @cleversolarpower
      @cleversolarpower  22 วันที่ผ่านมา

      Starting batteries are not the same as solar (deep-cycle) batteries.

    • @allangibson8494
      @allangibson8494 22 วันที่ผ่านมา

      @ These are so large that the difference is irrelevant… 20Amps is a trickle charge to these batteries.
      Deep cycle batteries also aren’t designed for mobile applications…(less shock resistance).

  • @g-whiz286
    @g-whiz286 2 หลายเดือนก่อน

    Not that it changes your calculation much (+6.25%), but I would have used 12 volts instead of 12.8 volts because a LiFePO battery can produce lots of power at 12 volts (3v/cell) for quite a long time before it knees over and dies. This increases the maximum current from 260 amps to 278 amps, but you have enough margin in your wire and fuse selection to accommodate this.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      Indeed, that would have been better.

  • @krslavin
    @krslavin 2 หลายเดือนก่อน

    I would use 12V (fully discharged) as the nominal battery voltage - you may want to run the inverter until that voltage is reached. So the power is greater or equal to 1200W per battery.

    • @javaman2883
      @javaman2883 2 หลายเดือนก่อน

      Right, to supply the output power, the input current will go up as the charge level voltage goes down. It is good design to size input wires based on that higher current draw when charge is low.

  • @davecarter34
    @davecarter34 หลายเดือนก่อน

    2 x 135ah in parallel on my 3000w inverter works well, even better now i have 000awg 400amp cable from battery bank to inverter, the old 100amp cable would warm up and inverter beep when running heat gun on high

    • @cleversolarpower
      @cleversolarpower  29 วันที่ผ่านมา

      The voltage drop over the small cable was likely too high for the current, so resistance increases = heat. The inverter would have sensed the lower voltage and turned off. All inverters have a min-max voltage range they operate on.

  • @garyprice5375
    @garyprice5375 หลายเดือนก่อน

    Hi thanks for sorting my issues for working out how to run my Renogy 3000w inverter with all the wires,Can you help me with how to Power the Batteries, I have a 200w solar panel that works great through the day as long as it is bright enough. I need to know how to charge the batteries to keep them from going below the 12v and stopping the inverter from shutting off . Thanks Gary.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      I have made a video on sizing the charge controller. I also recommend checking out my video about sizing a solar system. That will help you choosing the right amount of solar panels.

  • @uupyerkilt
    @uupyerkilt 2 หลายเดือนก่อน +1

    Thank you so much as this is exactly the system I have been looking to install in our small travel trailer.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      Then I failed trying to explain that a 3kw inverter on a 12V system is not ideal.

    • @uupyerkilt
      @uupyerkilt 2 หลายเดือนก่อน

      @@cleversolarpower My trailer is already wired with 12-volt solar, It has 1 100-watt panel and 1 75-ah lead acid battery.
      I am removing the lead acid and installing 2 lithium LI Time 100ah batteries and adding 2 more 100-watt panels.
      The travel trailer is only 16 feet long, so to go to 48v seems like more money and not necessary.

  • @SqueekyBums
    @SqueekyBums 3 หลายเดือนก่อน +2

    I've got this exact inverter. Should have researched by better / seen this before buying.
    Running off two 130 leasure batteries, and you get to microwave one meal before the low battery alarm sounds.
    Useless in a motorhome setting 😢

    • @cleversolarpower
      @cleversolarpower  3 หลายเดือนก่อน +4

      Indeed, something i forgot to mention. If a large load is placed on lead-acid batteries, the voltage will drop. The inverter will shut down because it thinks the batteries are empty. While in fact, the load is too large for the batteries.

    • @a64738
      @a64738 2 หลายเดือนก่อน

      With 4 100Ah 100A lifepo4 batteries and my 3000w 24v inverter I can use an electric oven with 2 cooking plates and electric oven with all 3 at full power at same time. And I can keep it running like that until the batteries is empty which will take 1,5 to 2 hours as I do not know the exact power usage of the electric oven. LifePo4 is the way to go for high power usage.

    • @SqueekyBums
      @SqueekyBums 2 หลายเดือนก่อน

      @@a64738 Agreed. 24v is better as the cable gauge can be reduced. Lithium can be run flat, unlike lead acid, but the price! Looking at a 12v 280ah lithium from eco-worthy for £500.
      I'll be selling the inverter and buying a 1000w. Hardly use it anyway, and mainly to charge laptops etc. My inexperienced thought was, 'if buying one, may as well have the extra watts just in case'.

  • @JohnBraman413
    @JohnBraman413 หลายเดือนก่อน +2

    nice breakdown on how many batteries to use a 3000w inverter. now next video should be how many solar panels to maintain those batteries.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Checkout my video about sizing a solar system.

    • @JimSmith-q4o
      @JimSmith-q4o หลายเดือนก่อน

      @@cleversolarpower

    • @Bazza1968
      @Bazza1968 หลายเดือนก่อน

      Or what to get to grid/mains charge them if used without solar as a house backup system?

  • @NedumEze
    @NedumEze 2 หลายเดือนก่อน

    Thanks for the Video.
    Sorry, could you share what the c-rating for the Lithium battery is? Please.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      Usually 1. But it depends on the BMS. Most BMS have 100A rating. In case of 12V 100Ah, this is one c. But if you have 12v 200Ah, then with a 100A BMS, you can still draw 100A max. Some companies have larger battery bmses called plus.

    • @NedumEze
      @NedumEze 2 หลายเดือนก่อน

      @@cleversolarpower
      Thank you very much sir.

  • @kennedy67951
    @kennedy67951 26 วันที่ผ่านมา

    Thanks for sharing your experience and knowledge with me. You didn’t mention using Diodes and fast actings resettable FUSES Either.😮Why?

    • @cleversolarpower
      @cleversolarpower  24 วันที่ผ่านมา

      I don't like resettable fuses for DC. Most of them are trash. I do like breakers for AC though from respectable brands. Why would you use diodes?

    • @kennedy67951
      @kennedy67951 20 วันที่ผ่านมา

      @ Diodes would stop any power from shorting your system out. It’s for just more safety in the system.

  • @Zelaznogsiul-63
    @Zelaznogsiul-63 22 วันที่ผ่านมา +1

    Can you plug it to your car and start the engine?

  • @SomeCrazyVids
    @SomeCrazyVids 2 หลายเดือนก่อน

    Thanks for the video. At 9:45 you mention that each battery should be fused before it's connection to the bus bar.
    I have a victron MPII 3KVA (2400w) 48v inverter with 2x 5kw 100Ah batteries in parallel, using 50mm2 cable.
    Currently not using a bus bar, but instead connecting from the positive of the top (first) battery and the negative of the bottom (last) battery to a dual pole 125a NH gBat fuse (both the position and negative cables) which then connects to the inverter.
    I know this isn't optimal in comparison to your examole of using a bus bar, such as the lynx power in.
    But my question is this:
    Must I install a 125a fuse from each battery to the bus bar? As you said that this prevents a current shift in the event of one of them failing.
    Then, install another 250a fuse after the bus bar (between it and the inverter) accounting for the 100ah from each battery x2 + 25% safety?

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      I don't think it's required by code, but it's something I would add. In your case I would suggest using an MRBF fuse on the terminal of each battery. They are quick to install.

    • @SomeCrazyVids
      @SomeCrazyVids 2 หลายเดือนก่อน

      ​@@cleversolarpowerI watched your section about the MRBF fuses in th-cam.com/video/OmYYdlU5qdA/w-d-xo.htmlsi=hRJwc4ROpT1yb7KB. However you state that they should not be used in a 48V system which mine is

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      @@SomeCrazyVids The Icc (short circuit current capacity) of an MRBF is 2000A @48V. It should not be used in high current systems as a main fuse. But since you will fuse every battery separate, the ICC will be limited to 100Ah*10=1,000A Icc. Which the MRBF fuse can handle. It could even handle both of your batteries because they will have: 2x100Ah*10=2,000A short circuit current. But that would be on the edge. Hope this makes it clear.

    • @javaman2883
      @javaman2883 2 หลายเดือนก่อน

      Yes. When dealing with batteries with high current capacity, it becomes important safety precaution to use a fuse on each wire. Would you rather use a $10 fuse on each wire or have a fire?

  • @Kelly198749
    @Kelly198749 18 วันที่ผ่านมา

    I have a 25w solar panel, what size battery/invertor should I use?

  • @MasterChief4U
    @MasterChief4U 6 วันที่ผ่านมา

    One problem with using buss bar to combine all the batteries. You don't get the benefit of combining the BMS. As you can take 2x 100ah batteries with 100a BMS and get 200a BMS. Just by using the negative off one battery and the positive off the other to complete the circuit..

    • @cleversolarpower
      @cleversolarpower  4 วันที่ผ่านมา

      I don't recommend series for this reason as well. I have a video about it coming soon. Parallel with higher voltage battery is preferred.

    • @MasterChief4U
      @MasterChief4U 4 วันที่ผ่านมา

      @@cleversolarpower Not what I posted. If you're running 2x 12v 100ah BMS.. And using a 2000 watt inverter. You need to run negative off one battery and the positive off the other. To combine the 2 BMS to create one 200ah BMS.. If not the Inverter will shut down of blow a fuse.
      This rule only applies to 2x 12v 100ah Batteries with 100ah BMS. As 200ah Batteries come with a 200ah BMS already. Some cheaper ones are 150ah BMS which I would avoid..

  • @gavgene371
    @gavgene371 12 วันที่ผ่านมา

    After watching this i followed with an instant subscription, thank you easy to follow and very informative 👍

  • @MarkButler-rb8cz
    @MarkButler-rb8cz 21 วันที่ผ่านมา

    most people don't use 3k watts and the 1s that do have a 6k watt inverter so a 3k watt inverter only needs 2 lithium 12 volt batteries to run 1.5-2k watts if you run more than that I would double up to 4 12 volt batteries. lead acid deep cycle you need 4 for 1.5k to 2k watts any more than that double up so 8 for 4k+watts

  • @rl5271
    @rl5271 2 หลายเดือนก่อน +6

    Great explanation and much appreciated!

  • @cabdiibraahim
    @cabdiibraahim 27 วันที่ผ่านมา

    Can I connect 2 different voltage batteries building 12v
    Eg.
    I have 200v and 150v
    Only I want add the Ah which means 350Ah

    • @cleversolarpower
      @cleversolarpower  27 วันที่ผ่านมา

      You got things switched up. It's not volts it's capacity or amp hour. You can add different capacities in parallel. I have made a video about it as well.

  • @brycelexiskalima3930
    @brycelexiskalima3930 หลายเดือนก่อน

    Good day sir so how many lithium batteries for 24 volts 3kva hybrid inverter and how many panels 450VDC?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      3000W/24V=125A. You need two 12V 100Ah in series with a 100A BMS each. But i don't recommend having batteries in series. So buy two 24V 100Ah batteries and wire them in parallel.

  • @adedoyinadetunji2078
    @adedoyinadetunji2078 14 วันที่ผ่านมา

    i have a 24v 200ah battery for a 3000w inverter and i only use 1. Is that enough?

  • @perunut4656
    @perunut4656 2 หลายเดือนก่อน

    How can I tell the input voltage of my Inverter (chinese Suyeego 2000w). The instructions say 12/24, but I somehow doubt it? Currently runs off 12 battery but would prefer 24v, would it work?

    • @randylynn1268
      @randylynn1268 2 หลายเดือนก่อน

      Most inverters will run off of 12 or 24 volts the higher end inverters will run off of 48 volts be sure that you use a charge controller that can accommodate the input

  • @AudieX2x
    @AudieX2x หลายเดือนก่อน

    Hi
    Can I use a 12v battery with a 24v inverter? Thank you for your answer.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      No, not possible.

    • @francismickey
      @francismickey หลายเดือนก่อน

      @@cleversolarpowerwhat about two twelve volt batteries?

  • @sphillips6357
    @sphillips6357 หลายเดือนก่อน

    Hi, I'm still very new at this. I undrstand (I think) how to calculate the batteries and wire needed if I know the rating of the inverter. But what inverter do I need to run a 1500 watt 120vac load from sundown to sun-up?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      1500W/0.9=1666W at inverter input * 8 hours = 13,333Wh per day. Off grid design says 3 days of autonomy, 13,333Wh*3days=40,000Wh or 40kwh battery = 8 server racks (48V). Recharge the battery in one day: 40,000Wh/3 sunhours on average = 13,333W of solar panels. cost of batteries: $10k+ $6.6k solar = $16.6k for batteries and solar add an EG4 off grid inverter 6000XP ($1400) + additional charge controller $500. so expect to pay $20k for this.

  • @scrappydont2478
    @scrappydont2478 หลายเดือนก่อน

    car stereo amp kits have 00 cables with very fine cpper wires and fuse holders and crimp on connectors but lead acid batteries have one advantage is they can handle heat and cold l ion can't a lot of off grid people have their battery bank outside so heat and cold is a factor .

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      True. Now there are lifepo4 batteries with low temperature protection and integrated heating pads to keep the battery above freezing.

  • @martyn52
    @martyn52 2 หลายเดือนก่อน

    Wow great video.
    Had me baffled most of the time. Not done any of this stuff before.
    How can I get the chart for cable sizes please. I have 2 48 volt lifelong batteries. They were on a pallet truck. I want to use these on a solar system. Any words of advice. Would be much appreciated.
    Thanks Martyn

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      I have linked the cables in the description. You can find the table in the product images of the linked cable. These are manufacture specific, so do not use these for other cables.

  • @chaswarren7239
    @chaswarren7239 2 หลายเดือนก่อน

    Thank you for the careful explanation. I have just subbed, because my Physics degree is nearly half a century old now.
    Can I ask you too questions ?
    1) I have a 3000 W invertor to power a washing machine on my boat. It is fed by two 115 Amp/hr Deep Cycle lead acid batteries. I only run the washing machine when the engine is running so that the alternator takes up the load. Is this reasonable ?
    2) Would it be worth installing a much smaller invertor to supply low power items like laptops to reduce the efficiency loss when running small load items?
    Many thanks.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      1) yes, that's a good solution to the large current draw of a washing machine. Otherwise your batteries will degrade fast.
      2) The difference would be minimal, so no need to add necessary costs.

    • @chaswarren7239
      @chaswarren7239 2 หลายเดือนก่อน

      @@cleversolarpower Thank you, that is really helpful !

  • @CarlJBier
    @CarlJBier หลายเดือนก่อน

    Great video - Thanks. Question: can you recommend a solar controller? I have (3) 12/100V batteries in parallel, as you outlined in the video. and (2) 400 watt pannels. What controller would you recommend?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Victron is great. Otherwise Epever makes good controllers as well.

  • @a64738
    @a64738 2 หลายเดือนก่อน +1

    I needed 4 LifePo4 batteries that can provide 100A each to run a 3000w inverter at full power at 12v or 24v or 48v....

  • @peterchang7646
    @peterchang7646 26 วันที่ผ่านมา

    I'm thinking about building a 4s3p LiFePO4 battery with 25Ah cells. These are Topband Prismatic cells and have a 3C continuous discharge rating, 5C - 10 second rating.... This would make a 12.8V 75Ah battery with a max continuous discharge of 225A. This would give a max discharge of 2880Watts. I am hoping maybe to use it with a 2000W inverter. These cells were originally designed for a electric forklift. Does that C rating seem plausible?

    • @cleversolarpower
      @cleversolarpower  24 วันที่ผ่านมา

      I recommend getting he regular 280Ah 3.2V cells. I recently got a quote for $45/piece. 1C with this cell is 280A. I don't recommend having cells in parallel because it wont get balanced properly. The C-rating can be plausible, however i don't know because you didn't tell me the name of it.

  • @skippysquirrelly
    @skippysquirrelly 2 หลายเดือนก่อน

    I have LiFePO4 12.8V 200Ah Plus batteries. Would I still require two 300A busbars, or would something larger be required? Thanks a bunch and great video!!

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +1

      300A busbars is sufficient.

  • @Anointed_Bone
    @Anointed_Bone 2 หลายเดือนก่อน

    I have a 24v 3,000 watt inverter and two 250 ah lead acid batteries. If I were to switch to 100 ah LiFo 4 batteries, how many would I need

  • @johnsemrau6412
    @johnsemrau6412 3 หลายเดือนก่อน

    Ok I've got a 3000 watt 12V inverter 60 amp Mppt charge controller and four 280 Amp hour lithium batteries 🔋 so i could have more reserve power?

  • @jefflucas_life
    @jefflucas_life หลายเดือนก่อน

    11:18 48v/100a, just what i needed for my AIO 3500W example.

  • @SAIOSesay-f1c
    @SAIOSesay-f1c 17 วันที่ผ่านมา

    Brother how are you doing thank you so much for your effort.i want to use 10 tvs and playstations and Xbox how many inverter and battery i need.i have a playstation center that runs everyday so i want to use solar this time

  • @Purinelz
    @Purinelz 2 หลายเดือนก่อน +1

    thank you very much for taking time and answering that question. for the pure Factor you took time to answers questions I have just subbed into your Channel

  • @saudgr
    @saudgr 4 วันที่ผ่านมา

    Thank you very much. I learned a lot watching this video. 🌹

  • @uupyerkilt
    @uupyerkilt 2 หลายเดือนก่อน

    I have a small trailer already equipped with one 100-watt solar panel and one 75-ah lead acid. I am replacing the battery with 2 100ah lithium and 2 more solar panels. Is it worth going to 24 volts as cable runs are very short.

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      depends on the load you want to run. If you have a small load, tick with 12V, if the load is larger use 24 or 48V. Checkout my video about 12,24 or 48V battery systems.

  • @EmmanuelDimgba-f7c
    @EmmanuelDimgba-f7c 3 หลายเดือนก่อน

    👍
    Kindly direct me Sir.
    In order to respect the battery's C-rate using leadacide batteries. You said in your previous video that four 12v,100ah lead acide batteries should be connected in parallel to match a12v 1000w inverter.
    That is,
    1000w ÷ 12v =83A &
    4 x 100ah x 0.2c = 80A.
    My Question:
    I believe that the amount of current that's being pulled from the battery or batteries by an inverter should be dependent on the load that's being plugged in ~instead of the capacity of an inverter.
    Won't it be okay to use 12v 3000w inverter with 220ah leadacide battery and maintain loads that's not greater than 528w (while, 220ah x 0.2c x 12)?

    • @cleversolarpower
      @cleversolarpower  3 หลายเดือนก่อน +1

      If your loads are not larger than 500W, then you will still get the expected lifespan out of your batteries.

    • @EmmanuelDimgba-f7c
      @EmmanuelDimgba-f7c 2 หลายเดือนก่อน

      Thank you very much Sir.

  • @Ralphm64
    @Ralphm64 4 วันที่ผ่านมา

    Great video and extremely useful! Thank you 🙏

  • @Chris-ut6eq
    @Chris-ut6eq 2 หลายเดือนก่อน

    What is the source of wire current draw rating?
    Also, with the two wire system, what happens if one of the wires has an issue and is not able to handle the intended load? As an extreme example, let's say it was not properly crimped and was disconnected (or someone forgot to hook it up when servicing the system).

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      The current ratings of the cables can be found on the sellers page which i have linked in the description. Ideally you will have to fuse every wire separately.

    • @Chris-ut6eq
      @Chris-ut6eq 2 หลายเดือนก่อน

      @@cleversolarpower Thank you for the information.
      Something to keep in mind that the vendor's ampacity numbers are far greater the US NEC (National Electrical Code). Perhaps there are standards for industrial cabling that allow this. The only claim this amazon maker states is SAE J1127, but the cables do not state a J1127 insulation type and there are no markings stamped on the cable shown in the picture.
      Also keep in mind J1127 seems to be for vehicle starter battery cables and not for sustained amperage in uses like an inverter. Starter battery use case is very short duration, high amperage vs inverter use case of high amperage for extended times.
      If I had to guess this is welding cable and while the description claims J1127 it's not backed up in anyway by evidence. Also the max amp numbers seem grossly overstated. The only reference I could find for max amps is on the mcmaster-carr site for J1127 cables. I do not have access to the standard itself as it costs $$.
      While these welding cable may work for the application, they seem non-conforming to any standards so they are unknowns without more data and proof of certification. These feel like rebranded imported cables being sold by a US company. I did look at manufacturers website and no additional info found.

  • @jcicho
    @jcicho 17 วันที่ผ่านมา

    What happens if theoretically I had the said 3000w Renogy inverter but put 4 or more 12V 100AH batteries together. Would that change the fuses and wire AWG ?

    • @cleversolarpower
      @cleversolarpower  15 วันที่ผ่านมา

      No, the inverter decides the current draw, so adding more batteries does not change the current draw.

  • @glynnjenkins1026
    @glynnjenkins1026 2 หลายเดือนก่อน

    what about the charge controller?

  • @JeremiahNtale
    @JeremiahNtale 2 หลายเดือนก่อน

    my panal is 570w
    invarter is 5000VA
    battery is 384/300ah
    how many panals do need for my unit

  • @BrentLeVasseur
    @BrentLeVasseur 2 หลายเดือนก่อน +1

    The problem is that all transformers are symmetrical, which means you can only have a maximum theoretical efficiency of 100% where the maximum output is equal to input power minus losses. However, with an asymmetrical design, it is theoretically possible to have more output power than what you put into it. This isn’t ‘free energy’ but good design, as all energy for everything, including the grid comes from the zero-point vacuum. Without that energy from the vacuum, there would be no electrons and no protons and no neutrons. They would simply stop spinning and cease to exist. That fact that electrons never lose their charge and never stop spinning, is proof that vacuum energy exists.

    • @myinterests5573
      @myinterests5573 หลายเดือนก่อน

      Zero point energy is at best only a theory, at worst a total scam.

  • @BrianG612
    @BrianG612 2 หลายเดือนก่อน

    Really appreciate your explaining how all this works. However, I have one question. In your example, you are assuming the inverter is drawing 325A of current from the batteries including the 25% safety margin. Yet the link you provided for the bus bar is for one rated for only 300A max. Is this an issue or is this somehow considered sufficient. Can you explain why this is ok?

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน +2

      It's okay, the safety margin applies to cables. The busbar is not going to see more current than 300A.

  • @wandelendetak12
    @wandelendetak12 หลายเดือนก่อน

    Thanks for the video! Just one question @cleversolarpower, I have a 280AH battery with a power of 3584Wh and a maximum discharging current of 200A. Does this mean I should have another battery installed if I want to run the renogy 3000W invertor (because of the maximum discharging current) or will one battery be enough (because of the battery power)?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      3000W/0.9=3.333W max draw from the batteries.
      3.333W/12V=277A
      Your battery BMS will shut down when you reach a current higher than 200A if there is no surge capacity on the BMS.

    • @wandelendetak12
      @wandelendetak12 หลายเดือนก่อน

      @@cleversolarpower what do you mean with “no surge capacity on the bus?” (I’m not an expert)

  • @michaeldill7620
    @michaeldill7620 หลายเดือนก่อน

    Agm batteries? Same as lead acid? Two 100 amp hour?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Yes, they fall under the same type. AGM and GEL.

  • @SagieGanasen
    @SagieGanasen หลายเดือนก่อน

    Assuming I draw let's say 600 watts of power , do I still need 3300w at the input.

  • @hoodiedee4828
    @hoodiedee4828 18 วันที่ผ่านมา

    Thank you very much for your time and information. Have a blessed day and don't forget to Enjoy Life

  • @luismontesinos3054
    @luismontesinos3054 21 วันที่ผ่านมา

    Very good explanation if I use a 24V 3000W inverter should I divide everything by 2?

    • @billykulim5202
      @billykulim5202 7 วันที่ผ่านมา +1

      for a longterm use of the inverter should never use more loads than 60% the rated inverter power, if keep using 90% of the inverter power everyday, it will go kaput

  • @user-chris_zervakis
    @user-chris_zervakis 20 วันที่ผ่านมา

    simple rules explained well in this video
    thanks

  • @alexsummers4985
    @alexsummers4985 หลายเดือนก่อน

    I have a 6000W inverter. I currently only have 4 batteries (12.8V / 100Ah). I intend to connect them in a 2S2P configuration so that I have a 24V 200Ah battery bank. If I understand the math correctly, that will not supply 6000W of power (I think it's closer to 5120) but is there any downside to connecting the battery bank with that configuration to the inverter aside from the fact that it can't fully supply the 6667W that would be ideal? (Really great video by the way. Very clear and easy to follow. You earned a new sub.)

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      No problem. If you pull exactly 6000W, the BMS will possibly turn off. But no problem if you keep under 5120W. Some BMS'es have surge capacity, so you could possibly reach 6667W. Thats why you have to size your cables according to 6667W @ 24V.

    • @alexsummers4985
      @alexsummers4985 หลายเดือนก่อน

      @@cleversolarpower Awesome. Thanks!

  • @MasterChief4U
    @MasterChief4U หลายเดือนก่อน

    There is one myth about 24v and 48v systems.. The cost of wiring is offset by the need to buy 2-4 batteries. Then you need a 24v-48v transformer to reduce the voltage to 12v for 12v appliances. Not to mention the extra cost for the inverter and batteries. So you saved nothing...
    So unless you are using 120v or 240v only. You should add that into the formula and use chart.

    • @cleversolarpower
      @cleversolarpower  29 วันที่ผ่านมา

      Not really. First you have to do a load analysis. That will give you a certain amount of Wh of battery you need. From there you decide the voltage of the battery. For example, you need 10kWh of battery. You can either use 8x 12V 100Ah batteries for a 12V system, 4x 24V 100Ah batteries, or 2x 48V 100Ah batteries. So it won't be more expensive because you need to meet your required Wh of energy. after knowing the required Wh, you decide the voltage. If you are winging it like your example, then yes, you need to add more batteries in series and it will be more expensive. Point is that using a proper load analysis, the voltage doesn't matter because you have to reach your required Wh, be it 12V, 24V, or 48V.

    • @MasterChief4U
      @MasterChief4U 29 วันที่ผ่านมา

      @@cleversolarpower I get that. But I'm running into these 24v-48v systems in an RV with only 800 watts of solar or less. They have no idea they created a power loss effeminacy to 79%. As they have to install a 12v transformer back down to 12v. This is counter productive. And it adds more cost to the system.
      Why I said. Unless you're producing huge amounts of Solar above 2k+ watts. You're just spinning your wheels. As the wire cost savings vanished. Not to mention higher voltage of 150v charge controllers for larger series arrays. This cost adds up if you're in an RV.
      So if you're in an RV with 1k solar or less. Just use 12v systems. You will pay more for some wire. But the system is simple to maintain, upgrade and repair. As 12v systems are everywhere, Cost less and more choices. Not to mention 12v appliance are a dime a dozen..

  • @taniagollan
    @taniagollan หลายเดือนก่อน +1

    Perfect video for me! I need to see the math written out to fully understand it. Thank you!!

  • @bobhearn7402
    @bobhearn7402 หลายเดือนก่อน +1

    So the question is you're saying, 2 batteries will give you 3000 W. How many amp hours does it give you? So does it will that allow the battery to run for 12 hours or 4 hours or 6 hours? You don't know how many batteries do you need to run for 48 hours steady with the 3000 What load?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      2 12V 100Ah batteries in parallel will give you 200Ah. An inverter doesn't give you Ah though. I have made videos about how to calculate battery runtime, check them out on my channel.

    • @edussantoz9034
      @edussantoz9034 23 วันที่ผ่านมา

      The 3x lithium will give you 1 hour running 3000w load, and the 13x lead acid will give you 2.5 hours if you do not want to push it to the danger zone of discharging lead acids, but it can deliver 5 hours until discharge, where i live its cheaper to build the 13x lead acid bank than the 3x lithium about half the price for the whole bank, it may last half the time of the lithium but it will give at least 2.5 times the power, also lead acid is the real green battery with full return chain and i coud have a 10% discount in return on the next time i buy a new bank, lithium is not realy easy to recycle and where i live i need to pay for it to be disposed, yep it will not be recycled it will go in a landfill

  • @geraldocarvalho6
    @geraldocarvalho6 19 วันที่ผ่านมา

    I'm getting the book. Great video, thank you

  • @jamesrevell6475
    @jamesrevell6475 หลายเดือนก่อน

    I hooked up my Renogy 3000W to (3) 12 LiFePO4 batteries. With everything turned off I closed my garage and walked away. The next day while outside I could here a beeping sound coming from my garage. I opened the garage door and the Renogy 3000W was beeping with a red light blinking. My batteries were all well above 12V and my solar system was performing optimally. I read the manual to troubleshoot but could find no explanation for the audio alarm and red light. I disconnected the 3000W and never hooked it up again.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Is there a voltage at the output of the inverter? Did you reset the inverter? So many things could have gone wrong. Have you tried contacting renogy?

  • @308dad8
    @308dad8 21 วันที่ผ่านมา

    Hold on. Seeing as 12V batteries will allow 12-16 Volts of electricity flow then the batteries needed rely on amps which lead acid is the standard for starter batteries which use a LOT of juice so they clearly can dump it, so the number of batteries will depend on cranking amps and amp hours. 13 of the batteries you have? Maybe. 13 of what lead acid batteries and for what purpose?

    • @cleversolarpower
      @cleversolarpower  21 วันที่ผ่านมา

      We don't use starter batteries in solar applications because they won't last long with a low current, long discharge time as is typical with solar. You can in an emergency. Lead-acid is a bad choice for off-grid electric anyways. Deep cycle lead acid batteries has a c-rate of 0.2C is described in the video. Can you discharge them with more current? Yes, but they will get hot and their lifespan will decrease. So not a good idea if you want them to last long. So following the methods described in this video is what you need to run your system efficiently.

  • @troydorame890
    @troydorame890 2 หลายเดือนก่อน +1

    Thank you you're an excellent instructor

  • @rensonmajor4105
    @rensonmajor4105 15 วันที่ผ่านมา

    Please send me everything for the 440 set up thank you

  • @ITSREALLYNOTYOURFAULT
    @ITSREALLYNOTYOURFAULT หลายเดือนก่อน

    If i have two 12.8V 150ah batteries which have a BMS of 120A (25.6V x 120A = 3072) is that enough for a CLAIMED 95% efficiency 3000W inverter (3000 / 0.95 = 3,158) ? Or is the given calculation given in this video critical. What problems might i have for not reaching the recommended 3,158W battery power, and being less than 100 watts short? I suspect it will be ok, but why not ask :-) Cheers.

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน +1

      It's going to be okay. The BMS can handle a little more in peak power (most of the times). You will seldomly use all of the 3000W.

    • @ITSREALLYNOTYOURFAULT
      @ITSREALLYNOTYOURFAULT หลายเดือนก่อน +1

      @@cleversolarpower Thank you!

  • @wilfredopicos3812
    @wilfredopicos3812 5 วันที่ผ่านมา

    Grasias muy informatibo tu video

  • @livinganddyinglizzie
    @livinganddyinglizzie หลายเดือนก่อน

    Can I use one 200ah and one 100ah? Or, do I need to get three 100ah? Is there a difference?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Check my video about parallel batteries different capacity.

  • @stephenssali5925
    @stephenssali5925 2 หลายเดือนก่อน

    250A X 0.2C = 1,250 Ah as totaly confused me bz according simple mathematics its 50Ah , kindly help otherwise appreciate your lessons!

    • @cleversolarpower
      @cleversolarpower  2 หลายเดือนก่อน

      Sorry, that was a mistake. It should be: 250A/0.2C=1,250Ah. Take a look at the formula above, if we re-arrange the formula (I=capacity*c-rate) to find out the capacity we get: I/C-rating=capacity

  • @jimnunya1253
    @jimnunya1253 หลายเดือนก่อน

    3 lithos = 13 la 😮😢
    Interesting.
    I have 2x 100Ah, each is currently on separate inverters.
    1x has a 2kw inverter, the other a 400w.
    The 400w inverter I use for smaller stuff that doesn't cause it's fan to start running and it's just used more as backup and cellphone charging.
    The 2000w inverter is for everything, but I bought it to run my microwave, but I haven't run my fat wires yet nor am I ready to add my microwave in yet either!
    😅
    It's not easy to work on this stuff inside of a vehicle when you're already living in it completely.😢

    • @cleversolarpower
      @cleversolarpower  29 วันที่ผ่านมา

      You don't need an inverter for cell phone charging. You can use a 12VDC to 5VDC USB converter.

  • @bobhearn7402
    @bobhearn7402 หลายเดือนก่อน

    You can use 1 12 0 battery and still use an inverter, but you can only use it for maybe 20 minutes, that's it. You gotta understand how many batteries you need to get 24 hours. You will need 24 batteries 241 hour. Batteries is all you're gonna get is 1 hour out of each battery and then they're completely dead. It doesn't matter how many batteries do you need to run? 4:24 hours on a 3000 W inverter, using a furnace 24 hours a day. How many batteries do d n you need

  • @Jesussavesyouandme
    @Jesussavesyouandme หลายเดือนก่อน

    I heard car batteries good for wells cause of amp draw

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      No, don't use car batteries for energy storage.

  • @garyhansen57
    @garyhansen57 หลายเดือนก่อน

    How many 12 volt car generators would it take to get 3000 watts?

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      I assume you mean alternator. An alternator should only deliver 30-50% of its rated current. So probably 30-50A. It's best to drive and not stationary run it because the moving air will cool the alternator. Checkout my video about dc to dc charging and alternator charging.

    • @garyhansen57
      @garyhansen57 หลายเดือนก่อน

      @@cleversolarpower ok thanks

  • @kevinm7523
    @kevinm7523 หลายเดือนก่อน

    It's interesting that this video popped up now, I'm with 5 other people dealing with hurricane Helene, after a few days, 1 of the guys who doesn't understand ANYTHING about electricity went out and bought a 3000w inverter from tractor supply. His reasoning: it was expensive, so it must be good. He had 1 old 24v lead acid battery, it worked for a few minutes to run a TV, but then the battery ran out so he thought the inverter was bad, he returned the inverter and spent nearly 30 minutes complaining the second inverter was bad also. I had to stop him and attempt to explain basic electrical theory

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      Indeed, bigger isn't always better. Great case study, just because they make such an inverter doesn't mean you should buy them. Then inverter should support the load.

  • @wilfredopicos3812
    @wilfredopicos3812 4 วันที่ผ่านมา

    Ola en tu libro sale esta tabla de los cables

  • @subsonicreviews1835
    @subsonicreviews1835 2 หลายเดือนก่อน

    on my calculator when i do 250Ax0.2C i get 50. how do you get 1,250?

  • @charlesd9688
    @charlesd9688 หลายเดือนก่อน

    Please help ... Did not know what i was doing ... so i will take the shame and start over. He seems to be saying 48v system is best so i will go with that. I think I can keep my 480w solar panels ... What big size 48v inverter to go with my two 300 (600 ah) Redodo batterys. THANKS

    • @cleversolarpower
      @cleversolarpower  หลายเดือนก่อน

      I recommend watching my video about 12V,24V or 48V battery systems. Advantages and disadvantages. With 480W of solar panels 12 or 24V is ok as well. Voltage also depends on the inverter size.

    • @charlesd9688
      @charlesd9688 หลายเดือนก่อน

      One of the biggest problems with the whole thing is me at nearly 80. I will watch the videos and maybe I can keep the 12v system and the 12v 3000w inverter and victron 100/50 charge controler. What started this search is why i can not get my new 600ah batt to full charge ..abs/float (14+) but i can only get them (13+). Do u have a video on (victron) settings. THANKS MÜCH