Ice-O-Matic ice machine fan not working and flashing red light

แชร์
ฝัง
  • เผยแพร่เมื่อ 24 มิ.ย. 2024
  • Piggyback Spade Connectors
    amzn.to/4cg7LL1
    Alligator Clips
    amzn.to/4bjTBas
    This ice-o-matic ice machine kept shutting off. The fan was not working. The machine would over heat and shut off. There was a flashing red light in the front. After troubleshooting it and talk to iceomatic tech support I found the the fan cycle switch was not working properly. I fixed this iceomatic ice machine by bypassing the fan cycle switch.

ความคิดเห็น • 23

  • @jarad0714
    @jarad0714 27 วันที่ผ่านมา +3

    Thank you for the video definitely learn something every time you post one. Thoroughly enjoy learning more more.

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา

      You’re welcome. I’m glad you’re enjoying the videos.

  • @azheat23
    @azheat23 26 วันที่ผ่านมา +1

    You got a hold of product support on the first ring!! I usually have to have him call me back 2 hours later and I'm not at the job

    • @IceMachine411
      @IceMachine411  25 วันที่ผ่านมา

      Yes same here. I was surprised. Hopefully that’s the new normal.

  • @calvinthompson5398
    @calvinthompson5398 26 วันที่ผ่านมา +1

    That tech support seemed really excited lol

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา +1

      He didn’t want to be at work. lol.

  • @MightyMeehow
    @MightyMeehow 26 วันที่ผ่านมา +1

    piggyback terminals are awesome, didnt realize they are so cheap. Deff gonna get some for those ECM rescue motors with multiple directions! only thing i would have done differently would be to just wago or wire nut those together instead. Otherwise ive done the same thing on smaller U/c style icemakers with the same issue! I wire the CFM to the water pump since during harvest the smaller units dont use water assisted harvest, and you can do a quick fix that will be pretty reliable for the long run assume ambi temp is climate controlled

    • @IceMachine411
      @IceMachine411  25 วันที่ผ่านมา

      Using the wire nut is definitely one of my go to moves. I have the Piggyback so I might as well use it.

  • @harrydickson4575
    @harrydickson4575 26 วันที่ผ่านมา +2

    Nice job 👍👍👍

  • @zekenzy6486
    @zekenzy6486 26 วันที่ผ่านมา +1

    Great video. Thank you for sharing. May I ask, is fan control switch was bad and bypass fan control switch ?

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา

      Bypassing the switch is a good way to fix the machine. The fan does need to cycle on/off in cold temperatures so that the high side pressure doesn’t fall too low.

  • @calvinthompson5398
    @calvinthompson5398 26 วันที่ผ่านมา +1

    Do any ice machines have variable speed fan motor controls?
    I’ve seen some look slow. I never thought the cycle switch could slugging.

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา

      Im not sure. I know the iceomatic fans start off slow and pick up speed as they run.

    • @calvinthompson5398
      @calvinthompson5398 26 วันที่ผ่านมา

      @@IceMachine411😮

  • @thastinger345
    @thastinger345 26 วันที่ผ่านมา +1

    What do you do for the units that use R404 if something like a compressor needs to be replaced? Retrofit or 100 bucks a Lb 404?

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา +2

      I don’t think 404 is a $100 bucks a pound.

  • @Yumiko577
    @Yumiko577 26 วันที่ผ่านมา +1

    I'd rather work on an Avantco ice machine than work on a crap-o-matic. I've had customers have evap plates separate after only 2 years.

    • @IceMachine411
      @IceMachine411  26 วันที่ผ่านมา

      Ice-O-Matic has had some struggles recently. Ive seen the same thing unfortunately. They keep making upgrades to the machines and I think they are headed in the right direction.

  • @thesilentonevictor
    @thesilentonevictor 26 วันที่ผ่านมา +1

    Easy one

    • @IceMachine411
      @IceMachine411  25 วันที่ผ่านมา

      Im gonna have to find something a little more difficult for you sir.

    • @thesilentonevictor
      @thesilentonevictor 25 วันที่ผ่านมา +1

      @@IceMachine411 lol why don't you come fix some chill water system with me and troubleshoot the mortuary when it's down

    • @IceMachine411
      @IceMachine411  22 วันที่ผ่านมา

      Oh heck no! I refuse to go to a mortuary.