York Chiller Refrigeration Cycle - YCIV & YVAA AC

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ก.ค. 2024
  • UPDATE: I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only.
    In this hvac training I explain the refrigeration cycle of a York chiller. YCIV & YVAA are great hvac system for any building air conditioner. This hvac training videos goal is to help hvac technician better understanding these AC systems.
    Check out Merch Store! my-store-b413f9.creator-sprin...
    You can contact me at Hvactimetx@gmail.com
    You can also follow me at,
    Instagram
    / hvactime
    Facebook
    / hvactime
    Support the channel through,
    venmo.com/code?user_id=316085...
    Zelle @ Hvactimetx@gmail.com
    #refrigerationcycle #chiller #hvactrainingvideos #york #ac #hvac #hvactechnician
    00:00 Intro
    00:24 Visual Explanation
    05:56 Main Panel Readings Explanation
    09:38 YCIV Drawing Explanation
    20:38 Evaporator Design Changes
    22:38 YVAA Drawing Explanation
    28:44 Closing & Tech Support

ความคิดเห็น • 77

  • @pinoyhvacrtech_australia
    @pinoyhvacrtech_australia 3 ปีที่แล้ว +7

    Eductor part is wrong mate.. illustration should be 1 from liquid goes to eductor, 1 line from buttom of the barrel or evaporator and 1 line back to suction line.. this kind of oil management is almost the same of rtac unit. Oil from buttom barrel then back to compressor

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +9

      Thank you, after I finished it and released it I realized I made a mistake on that part. What I will have to do is make a separate correction video doing a better job on that.

    • @pinoyhvacrtech_australia
      @pinoyhvacrtech_australia 3 ปีที่แล้ว +1

      @@HVACTIME yvaa has some changes depends on coil either copper coil or micro channel. Copper condenser coil the drain valve control by liquid level sensor at evaporator whereas with micro channel coil they dont have liquid level sensor at evaporator. I have few yvaa unit that i maintain here in the island

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      All of mine have micro channel.

    • @brianwolf9860
      @brianwolf9860 2 ปีที่แล้ว

      Economizer opens based on comp frequency. Our YVAA now does not have check valves in the econ pipe, because our newer software allows for Economizer backflow control.

    • @pinoyhvacrtech_australia
      @pinoyhvacrtech_australia 2 ปีที่แล้ว

      @FILIPINO WONDER'S yvaa sir?

  • @HVACTIME
    @HVACTIME  3 ปีที่แล้ว +6

    I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only.

    • @Drak7282
      @Drak7282 หลายเดือนก่อน

      I was going crazy looking for that thing lol. Glad I came to comments

    • @HVACTIME
      @HVACTIME  หลายเดือนก่อน

      Lol my bad

  • @rudrapratapsingh367
    @rudrapratapsingh367 2 ปีที่แล้ว +3

    after watching this video, my basic dx chiller cycle clear , thanks a lot HVAC time

  • @wata_laf
    @wata_laf ปีที่แล้ว +1

    Love the video! Everything was perfectly explained but I would like to add, there is not a “DRAIN VALVE” on the flash tank leaving line to evap. Now there is a shut off but not an eev device.

  • @EA91HVAC
    @EA91HVAC 3 ปีที่แล้ว +2

    You posted this at a perfect time for me ! I just finished going over a few yvaa’s with my journeyman this past couple days. Love the videos keep it up!

  • @lauderdalechad
    @lauderdalechad ปีที่แล้ว

    Ran into a yciv today for the first time. I'm used to working on rack refrigeration, needless to say I was all kinds of turned around. This video made it all so clear to me now. I'll be working on it again later this week... Atleast I'm armed with some knowledge now. Thanks a ton! 🍻

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 ปีที่แล้ว +1

    I hope to one day understand and be proficient at troubleshooting equipment like this. This type of equipment is what i get up and get going for. I love this trade

  • @perryjeff77
    @perryjeff77 2 ปีที่แล้ว

    Bro thank you so much man. I just got a job as a facilities engineer and this stuff is hard for me to fully grasp. Thank you for breaking this down.

  • @stlbrian33
    @stlbrian33 3 ปีที่แล้ว

    Thank you for these videos. HVAC Gold.

  • @mischieftommy1252
    @mischieftommy1252 2 ปีที่แล้ว +1

    Thank you very sir, really fantastic explanation, could you please provide more theatrical explanation , how FD working and collect oil from the cycle.

  • @hvacr3519
    @hvacr3519 3 ปีที่แล้ว

    very useful information, thank you very much.

  • @Mybusiness1978
    @Mybusiness1978 2 ปีที่แล้ว

    Thanks for really informative video.

  • @simohvac9222
    @simohvac9222 3 ปีที่แล้ว

    great explanation

  • @michaelgonzalez1824
    @michaelgonzalez1824 2 ปีที่แล้ว

    Great Video!

  • @bobparrott8130
    @bobparrott8130 3 ปีที่แล้ว

    Great info thank you 👍

  • @ramitbajrawar
    @ramitbajrawar 2 ปีที่แล้ว

    Very useful information

  • @smptbachu155
    @smptbachu155 ปีที่แล้ว +2

    need a separate video on edector system

  • @fathmasameer7523
    @fathmasameer7523 3 ปีที่แล้ว

    Great video the chiller I have seen Model YVAA fix orifice instead drain valve (EEX)

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      You know I'm glad you said something, I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only. I will need to make that correction some how.

  • @michaelhadera3024
    @michaelhadera3024 9 หลายเดือนก่อน

    Amazing video man

  • @yup735
    @yup735 3 ปีที่แล้ว

    good job

  • @mikefrantz8398
    @mikefrantz8398 2 ปีที่แล้ว

    Good stuff

  • @salehhamid
    @salehhamid 2 ปีที่แล้ว

    Most helpfull ,,, Thanks very muck

  • @mahendrachoudhari9598
    @mahendrachoudhari9598 ปีที่แล้ว

    my best dear techar for my life great vidio for me.

  • @michaelh3142
    @michaelh3142 3 ปีที่แล้ว

    It would be awesome to see a video on a daikin screw. In particular how the capacity slides valves work in detail.

    • @donwilkes536
      @donwilkes536 2 ปีที่แล้ว

      it may be superheat which controls the slide valve which is typically what loads a screw compressor

  • @nathandaubis819
    @nathandaubis819 2 ปีที่แล้ว

    after watching all the chiller videos on you tube, you have found where the BEAR SHIT IN THE WOODS...thank you. great VIDEO.

  • @shahidawaisee
    @shahidawaisee 2 ปีที่แล้ว +2

    Pls. Look into enhancing the video lighting. Thanks

  • @ahmedalameendiy
    @ahmedalameendiy 2 ปีที่แล้ว +1

    Awesome vedio :) i think the stupid thing in this system it dont have feed back in valve position

  • @sreejithks625
    @sreejithks625 ปีที่แล้ว

    Nice video brother...My VSD assembly in YVAA got burned. What could be the reason

  • @chiller-on
    @chiller-on หลายเดือนก่อน

    hi. do you have a video on the channel on how to properly replace the oil on the York YVAA chiller?

  • @anwarahmadkhan4469
    @anwarahmadkhan4469 11 หลายเดือนก่อน

    How to remove suction line from the barrack or cooler can u explained me pls

  • @rdheatingandair6973
    @rdheatingandair6973 ปีที่แล้ว

    Can you change the EXV motor on these chillers without removing the Freon

  • @fredrosas2575
    @fredrosas2575 3 ปีที่แล้ว

    Hey, great video thanks for taking the time to do them.
    Question. if I'm understanding right the drain valve is the metering device?

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      At its core yes, It is the final flash point that is controlling evap superheat. But the feed valve also plays a critical role in that as well.

    • @fredrosas2575
      @fredrosas2575 3 ปีที่แล้ว

      @@HVACTIME I understand now. Thanks for the quick response!

  • @khushimohammad5357
    @khushimohammad5357 8 หลายเดือนก่อน

    How to change York chiller reciprocating oil heater old compressor

  • @aircooledchilleralltypes4938
    @aircooledchilleralltypes4938 3 ปีที่แล้ว

    Sir chiller displays show vsd communication failure fault what is the problem

  • @ziaarnie3694
    @ziaarnie3694 3 ปีที่แล้ว +1

    Amazing video brother, kindly explain same to Trained cvhe or cvhf water cooled chiller . Thanks

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +2

      Coming Soon!

    • @ziaarnie3694
      @ziaarnie3694 3 ปีที่แล้ว

      @@HVACTIME thanks

  • @shoaibmallabadkar3947
    @shoaibmallabadkar3947 ปีที่แล้ว

    Sir how to change oil in YVAA fladed chiller

  • @HH-oi8hn
    @HH-oi8hn ปีที่แล้ว

    Hi please there is leaked in evaporater. How can I repair it only in Cerkit 1 thanks

  • @Tamilsongs2813
    @Tamilsongs2813 ปีที่แล้ว

    Pls how do oil charges this chiller pls make explain sir

  • @SombraLocs
    @SombraLocs 3 ปีที่แล้ว

    Great video! Where did get training on these? I know York doesn't offer training to none JCI technicians.

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +2

      School of hard knocks and manuals lol

  • @bryangillis2515
    @bryangillis2515 2 ปีที่แล้ว

    Can you explain exactly what the economizer valve does? Is it cooling the compressor or reducing compression ratio?

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว +1

      Its pulling flash gas to reduce pressure on the flash tank.

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 ปีที่แล้ว

      That was what i was thinking as well

  • @travisburks628
    @travisburks628 2 ปีที่แล้ว

    Have you had a oil separator on a YCAV start to plug up?

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว

      No haven't ran into that one

  • @jaymz0074
    @jaymz0074 2 ปีที่แล้ว

    Wouldnt happen to have a York YCUL080 air cooled service manual you could email could you?

  • @axltv3873
    @axltv3873 ปีที่แล้ว

    I have same unit YCIV micro channel cond coil.im facing problem in drain valve not giving the exact position when I put manually put it to 100% open and 0% closed,when it run it having alarm low suction limiting and unusual sound of the compressor.i suspect the stipper motor module so I tried to swap from other unit but still problem occur.unit shutdown low suction pressure. Any advice

    • @HVACTIME
      @HVACTIME  ปีที่แล้ว

      Extremely common for the exv gears to where out and stick causing it to get out of calibration. Recommend replacing exv.

  • @allanfernando5358
    @allanfernando5358 3 ปีที่แล้ว

    Sir i have carrier chiller with water cooled condenser is it possible to convert to air cooled condenser.

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +3

      I would heavily advise not to try

  • @fathmasameer7523
    @fathmasameer7523 3 ปีที่แล้ว

    Hello brother how to reset alarm on this chiller

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      You do it through the system switches menu

  • @aircooledchilleralltypes4938
    @aircooledchilleralltypes4938 3 ปีที่แล้ว

    Sir need help

  • @hvacr3519
    @hvacr3519 3 ปีที่แล้ว

    where the supper heat sensor installed?

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      There is a thermistor on the suction pipe.

    • @hvacr3519
      @hvacr3519 3 ปีที่แล้ว

      @@HVACTIME thanks

  • @scottymcneill6516
    @scottymcneill6516 2 ปีที่แล้ว

    Holden, the beginning is too dark, we can't really see components.

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว +1

      Sorry did the best I could at the time.

    • @scottymcneill6516
      @scottymcneill6516 2 ปีที่แล้ว

      @@HVACTIME I know brother

  • @ferdinandbergonia6053
    @ferdinandbergonia6053 2 ปีที่แล้ว

    How to drain the oil for YVAA? please for your advise.

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว

      At the oil service valve

  • @mahamudulhasan2149
    @mahamudulhasan2149 2 ปีที่แล้ว

    Picture not so clear