Chiller VSD Replacement York YCIV Air Cooled Chiller

แชร์
ฝัง
  • เผยแพร่เมื่อ 13 ก.ย. 2024
  • This York chiller VSD failed, had a SCR short out and a capacitor blow. Replacing the full power assembly. HVAC technician should get a lot of use from this as a hvac training videos. Chillers are just one big air conditioner doing what AC do.
    hvactimetx.com
    You can contact me at Hvactimetx@gmail.com
    Support the channel through,
    venmo.com/code...
    Zelle @ Hvactimetx@gmail.com

ความคิดเห็น • 113

  • @christophermerritt6436
    @christophermerritt6436 ปีที่แล้ว +1

    I don't know how you do it but your wealth of knowledge and how to troubleshoot is this so extensive

  • @allanfernando5358
    @allanfernando5358 3 ปีที่แล้ว +7

    your doing such a big help to HVAC family throughout the world. we family's of HVAC whole world thank you so much.

    • @jollyscaria1922
      @jollyscaria1922 2 ปีที่แล้ว

      Allan allan ferandopower full jobe doing such big jobes famliey not jobe ony side whole world all unit no only shreing song helpunfull big tankyou sir

  • @sivalley
    @sivalley 2 ปีที่แล้ว +4

    The safety fuses blew because of the drive failure, not the other way around. They are designed to react faster than the circuit breaker to prevent electrical fires caused by an arc fault that a breaker cannot react fast enough to prevent. Breakers are for protecting wiring from overheating, not to protect equipment.

  • @jamesjames9394
    @jamesjames9394 3 ปีที่แล้ว +2

    Recently moved from Marine Industrial to Commercial and familiarizing myself with equipment. Huge thanks, bro!

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +4

      Always, thats why I'm here. Everyone has a opportunity at a great life with just a little info to get them another step further.

    • @zaydkamari3882
      @zaydkamari3882 3 ปีที่แล้ว

      instablaster.

  • @andrewedis9907
    @andrewedis9907 3 ปีที่แล้ว

    I don't see this kinda system very often so thankyou for the videos Sir.

  • @pomonabill220
    @pomonabill220 3 ปีที่แล้ว +4

    Another job of the input reactor (choke) is to keep the switching noise from the inverter from going OUT of the drive onto the line input.

  • @HassanHassan-cg7hn
    @HassanHassan-cg7hn 3 ปีที่แล้ว +1

    Firstly, thank you for this useful video, and I see you working with confidence and this is very good. I hope that in the next video, you will explain to us how to change the oil of the compressor and take out the oil from the oil separator and bye until you watch this video

  • @MrBerniebling
    @MrBerniebling 3 ปีที่แล้ว +1

    Great Job explaining the technical side of the drive, thanks for uploading

  • @arifminhaj6521
    @arifminhaj6521 3 ปีที่แล้ว +2

    I am watching all your videos.lot of knowledgeable keep updating

  • @ziaarnie3694
    @ziaarnie3694 4 ปีที่แล้ว +1

    Nice video as always. Thanks. Kindly make video on water chiller complete parts along with power and control wiring

    • @HVACTIME
      @HVACTIME  4 ปีที่แล้ว +1

      Ill see if I can get one together soon.

  • @allanfernando5358
    @allanfernando5358 2 ปีที่แล้ว +1

    sir can you explain about VSD how it works and how to trouble shoot

  • @LionelLiftsVegas
    @LionelLiftsVegas 3 ปีที่แล้ว +1

    Great Video for sure. A lot of knowledge.

  • @rabeaezzategypt561
    @rabeaezzategypt561 4 ปีที่แล้ว +2

    Great job and very nice

    • @mohamedali-ur7op
      @mohamedali-ur7op 4 ปีที่แล้ว +1

      Yes brother its amazing can learn to installation method.

  • @Bluecollarrebel
    @Bluecollarrebel 4 ปีที่แล้ว +4

    I thought my job looked tough👍

  • @jasoncarver9
    @jasoncarver9 3 ปีที่แล้ว +3

    Great video

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      Thank you!

  • @abdulKarim-ol4hg
    @abdulKarim-ol4hg ปีที่แล้ว

    Nice job sir

  • @keithgigabyte4189
    @keithgigabyte4189 ปีที่แล้ว

    Gret video. Not sure where you buy your parts but its cheaper to rebuild...save in the tens of thousands to rebuild vs new unit. I have rebuild SCR/IGBTs and capacitors in the drives identical to this one and spent around $3,000 for parts

  • @salvadorbernardino7558
    @salvadorbernardino7558 2 ปีที่แล้ว +1

    Excellent Sir

  • @borisflores4818
    @borisflores4818 3 หลายเดือนก่อน

    Saludos. Tengo un problema, cuando conecto el modulo variador se activa se apaga el equipo por proteccion externa.

  • @allanfernando5358
    @allanfernando5358 3 ปีที่แล้ว

    Thank you so much bro for explaining.

  • @moideenyousaf3757
    @moideenyousaf3757 2 ปีที่แล้ว +1

    great job

  • @spencermacdonald5762
    @spencermacdonald5762 4 ปีที่แล้ว +1

    Awesome video

  • @chillhouse7418
    @chillhouse7418 3 ปีที่แล้ว

    Hopefully it's helpful for my future thanks 👏

  • @jackbauer4612
    @jackbauer4612 2 ปีที่แล้ว

    Awesome video. Like hearing the explanation of what your steps are. How long does something like that repair take. Looks pretty evolved.

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว

      A full day

  • @jarredallen
    @jarredallen 3 ปีที่แล้ว

    yeah.. digging through those scr are pain in the ass.. specially at 39C in the middle of the day. but unfortunately for me, I have done so many yvaa replaced with shorted or open scr or if im lucky the igbt's.

  • @azharmehmood4188
    @azharmehmood4188 5 หลายเดือนก่อน

    I want to ask you a question, dear, after how much time is there a chance of it getting damaged, this is the gate driver and the module power capacitor.

  • @bobbyghaz7257
    @bobbyghaz7257 ปีที่แล้ว

    Very infomative video..
    chiller york ykfdfrq75clgs - faulty
    VSD-HIGH DC BUS VOLTAGE
    Do you have video tu solve this faulty

  • @perfectodxc
    @perfectodxc 2 ปีที่แล้ว

    Buenas tardes,
    Mano le tengo una pregunta, en vista que un chiller dónde he Sido llamado para chequearlo, me he encontrado que se llevaron todo la parte de control y electrónica.... Pero el cliente necesita saber si los motores ventiladores y compresores es Buenos, por lo tanto; me gustaría saber si es posible alimentar solo el compresor directo, al menos como prueba, para saber que está comprimiendo.... Está prueba se hará en vacío, sin carga y sin conexiones de tuberías....
    Es decir; la pregunta es:
    ? Puedo energizar el compresor con voltaje directo sin el variador, solo para pruebas de funcionamiento.... Saludos y espero sus comentarios.

  • @TechnicalBrainHVAC
    @TechnicalBrainHVAC 3 ปีที่แล้ว

    Very informative video
    How we know the coolant level for the drive

  • @paulmcelvaney4148
    @paulmcelvaney4148 ปีที่แล้ว

    Great video, do you have the torque settings for the main fuses and the compressor harness leads?

  • @sheikhismailamin8866
    @sheikhismailamin8866 2 ปีที่แล้ว

    Nice job 👍

  • @aramabwbakr8300
    @aramabwbakr8300 2 ปีที่แล้ว

    Thanks again...

  • @muhammadmunir6447
    @muhammadmunir6447 3 ปีที่แล้ว +1

    how to set the fluid level control for yvwa york pack type chiller .. from system module ?? 🙏

  • @Archie2060
    @Archie2060 2 ปีที่แล้ว

    Nice video presentation , would like to know more about IGBT gate drive fault what to look for.?

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว

      First thing to verify is control plug. Make sure pins are properly pushed in.

    • @SombraLocs
      @SombraLocs 2 ปีที่แล้ว

      @@HVACTIME is there a service manual on how to properly troubleshoot this? Incase the customer doesn't want to go with the whole replacement.

  • @craigdcosta5214
    @craigdcosta5214 3 ปีที่แล้ว

    This is a fantastic video!
    Thanks a bunch
    What series of York Chiller is that?
    Looks like one of their YVAA line

  • @stlbrian33
    @stlbrian33 4 ปีที่แล้ว +2

    Who is the guy asking you all the questions in the video ?

    • @HVACTIME
      @HVACTIME  4 ปีที่แล้ว

      Customer watching job and helping film.

  • @Rajajaber1977
    @Rajajaber1977 2 ปีที่แล้ว

    Excellent boss

  • @mirarsheed2275
    @mirarsheed2275 3 ปีที่แล้ว

    great vedio man

  • @saahilraeen7590
    @saahilraeen7590 ปีที่แล้ว

    Hello sir I want to know how to clean heatsink in YK chiller pls inform me!!!!

  • @silvinopagdanganan2537
    @silvinopagdanganan2537 ปีที่แล้ว

    hello bro.. what might be the solution for having a VSD run relay in all system? recurring fault

  • @sajeedhussain3192
    @sajeedhussain3192 3 ปีที่แล้ว

    Sir Can u explain about glycol how to fill and how to check level.

  • @dazzykhan786
    @dazzykhan786 2 ปีที่แล้ว

    For me the same chiller vsd capacitor blast 💥 what is the reason can you please explain me.
    Thanks

  • @gaminidissanayake5465
    @gaminidissanayake5465 2 ปีที่แล้ว

    dear i have YVAA chiller IGBT drive replacement. could you send some tips on YVAA chiller IGBT replacement. thx

  • @Rajajaber1977
    @Rajajaber1977 2 ปีที่แล้ว

    Very very information

  • @thisaranilupul904
    @thisaranilupul904 3 ปีที่แล้ว

    nice job

  • @blacksmith8642
    @blacksmith8642 3 ปีที่แล้ว

    Sir! Kindly how can test by multimeter of IGBT good or definitive

  • @NguyenQuan-ul8hs
    @NguyenQuan-ul8hs ปีที่แล้ว

    please let me know how to handle when the resistor on the DC bus cannot fully discharge below 50V.Im from Việt Nam

    • @HVACTIME
      @HVACTIME  ปีที่แล้ว

      It needs new bleed resistors. You can use a meters with a built in resistor to bleed it down.

  • @senthilkumar-yc2ot
    @senthilkumar-yc2ot 2 ปีที่แล้ว

    Please send more videos sir

  • @joelam2160
    @joelam2160 4 หลายเดือนก่อน

    Have you ever replaced a YORK PCB GATE RESISTER INV BOARD

    • @HVACTIME
      @HVACTIME  4 หลายเดือนก่อน

      Yes, what you working on?

    • @joelam2160
      @joelam2160 4 หลายเดือนก่อน

      @@HVACTIME Thanks for a respond. I have this part and want to know which unit this part belong to(Johnson Controls PCB Gate Resister INV Consair (240) 031-03052-001) . Thanks Joe

  • @johnfilardi
    @johnfilardi 3 ปีที่แล้ว

    Do you have a video on how to change out the resistors, I have a rental I have to do Monday

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      No, not specifically but its very easy to do.

  • @ashpaktechnicalsupport
    @ashpaktechnicalsupport 4 ปีที่แล้ว +1

    Hallo sir,
    If in VSD assembly capacitor is getting smoke & smell then need full VSD Assembly should br change or only capacitor need to be change.. what is the reason for capacitor getting

    • @HVACTIME
      @HVACTIME  4 ปีที่แล้ว +1

      If all the other components check good then you can just do the capacitors.

    • @ashpaktechnicalsupport
      @ashpaktechnicalsupport 4 ปีที่แล้ว +1

      @@HVACTIME Thanks you very much Sir...

    • @ashpaktechnicalsupport
      @ashpaktechnicalsupport 4 ปีที่แล้ว

      @@HVACTIME Sir,
      Alarm Showing ( Precharge - DC Bus Voltage Imbalance )
      And after clear the alarm start the chiller after 2-3 minutes little smoke comes near Capacitor so what should be problem and what should be change...
      Pls. Help and reply...
      Thanks a lot...

    • @HVACTIME
      @HVACTIME  4 ปีที่แล้ว +1

      First stop resetting the chiller. Sounds like you definitely have a capacitor issue and possibly a SCR issue. You need to get someone on site who knows that drive and can fix it.

    • @ashpaktechnicalsupport
      @ashpaktechnicalsupport 4 ปีที่แล้ว

      @@HVACTIME Thanks a lot ...Sir...

  • @senthilkumar-yc2ot
    @senthilkumar-yc2ot 2 ปีที่แล้ว

    Sir vsd high passplate temperature what problem sir please send video sir

  • @angelosemilla2804
    @angelosemilla2804 4 ปีที่แล้ว +1

    Hi Sir you have video to remove the SCR ?

  • @papichulo1934
    @papichulo1934 2 ปีที่แล้ว +1

    YOU MAY ASK TO THE CAMARA GUY- IF THE INVESTMENT IN A CHILD SCHOOL 🏫 IN A GUEST 30K OR MAY NE MORE- HE ASK QUESTIONS TYPICAL A OFFICE GUY WHO PROTECT THE MONEY FOR OTHERS-OTHERWISE HE GOT FIRE 🔥- SHOW HIM BRO 😎 HOW WE DO IN THE FEEL- LUCKY HIM THAT WAS YOU -LMAO-
    I HOPE THEY MAKE THE CHECK AT THE SAME SPEED WITH NO OTHER QUESTIONS

  • @georgekolos5255
    @georgekolos5255 2 ปีที่แล้ว

    Only about 4 grand more for entire assembly and 90 day warranty irregardless!

  • @juanrestrepo3155
    @juanrestrepo3155 2 ปีที่แล้ว

    hola hermano ecesito ayuda con un ycav

  • @HassanHassan-cg7hn
    @HassanHassan-cg7hn 3 ปีที่แล้ว

    For YCIV Model

  • @darekcieslik6838
    @darekcieslik6838 2 ปีที่แล้ว

    Do you do any medical chiller work ?

    • @HVACTIME
      @HVACTIME  2 ปีที่แล้ว +1

      Yes, variety of them.

    • @darekcieslik6838
      @darekcieslik6838 2 ปีที่แล้ว

      @@HVACTIME I work for KKT Chillers technical support. Nice work you do .

  • @Noypihvac
    @Noypihvac 3 ปีที่แล้ว

    What is the possible cause on yvwa screw 171hz demand but the compressor amps is 40%FLA. Thanks

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      Im not understanding your question

    • @Noypihvac
      @Noypihvac 3 ปีที่แล้ว

      @@HVACTIME we have trouble york yvwa model chiller the problem we found is compressor stays at 40%FLA only even if the vsd demand is already at 171 hz. Even if vsd demand decrease still stay 40%

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      To be clear no matter what speed it runs the FLA doesnt change from 40%?

    • @Noypihvac
      @Noypihvac 3 ปีที่แล้ว

      @@HVACTIME the alarm is low discharge superheat. But base on system parameters all other inputs are good except those compressor amps not increasing. Thanks

    • @Noypihvac
      @Noypihvac 3 ปีที่แล้ว

      @@HVACTIME yes correct.. what are possible cause?

  • @MohammadAli-zx6bs
    @MohammadAli-zx6bs 2 ปีที่แล้ว

    Hi How Are you sir

  • @blake_edwards
    @blake_edwards 2 ปีที่แล้ว

    Is it just me or did the audio and video get out of sync?

  • @sazzadhossain4372
    @sazzadhossain4372 3 ปีที่แล้ว

    sir York YMC2 Magnetic Chiller VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE PROBLRM Please solved the problem

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      Have you done a full inspection of the drive?

    • @sazzadhossain4372
      @sazzadhossain4372 3 ปีที่แล้ว

      @@HVACTIME yes sir over and over same problem

    • @sazzadhossain4372
      @sazzadhossain4372 3 ปีที่แล้ว

      please sir give your whatsapp number

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      @@sazzadhossain4372 has the motor been megged and what are your input voltages?

    • @sazzadhossain4372
      @sazzadhossain4372 3 ปีที่แล้ว

      @@HVACTIME NO SIR

  • @user-zr5qc3im2z
    @user-zr5qc3im2z ปีที่แล้ว

    Arabic
    The new Schiller York What is wrong? I need help. I am an Arab national and I work in the state of Kuwait, where the burning sun is👇👇alarm
    UNIT FAULT :
    VSD COMMUNITCATIONS FAILURE

  • @michaelstephen9111
    @michaelstephen9111 2 ปีที่แล้ว

    Rookie. No need to drain the coolant system.

    • @sman3079
      @sman3079 2 ปีที่แล้ว

      He handled his questions with pazzaz

    • @sivalley
      @sivalley 2 ปีที่แล้ว

      Might have been required for warranty validation on the new module.