Paano gumawa ng LOAD COMPUTATIONS para sa MAIN CIRCUIT BREAKER? |Basic knowldedge |Tagalog

แชร์
ฝัง
  • เผยแพร่เมื่อ 7 ก.ย. 2024
  • VLOG TITLE: Paano gumawa ng Electrical Plan? Power,Lighting Layout at LOAD SCHED. & COMPUTATIONS sa MAIN CB??

ความคิดเห็น • 250

  • @romeofabia9819
    @romeofabia9819 ปีที่แล้ว +13

    Khit cnabe mong hindi ka gaanong kagalingan ELECTRICIAN para sa akin the best ka ksi na i share mo ang nalalaman mo tapos napaka klaro ang xplain mo👍

  • @EduardoGeneta
    @EduardoGeneta หลายเดือนก่อน +1

    hindi ka lang electrician isa ka din mentor marami ako natutunan sa mga video mo salamat ng marami sayo

  • @benmaroliveros5227
    @benmaroliveros5227 2 หลายเดือนก่อน +1

    Thank you very much boss marami ka pang 😊matulungan katulad ko na sumusubabay sa vlog mo God bless you

  • @rizalinoagaran8258
    @rizalinoagaran8258 ปีที่แล้ว +2

    Salamat sir sa discastion..na refresh Ang kaalaalan ko sa building wiring

  • @AlCantre-bz7fh
    @AlCantre-bz7fh 4 หลายเดือนก่อน +1

    grabe ang galing talaga...malinaw anh explanation ,👏👏
    paano kapag single circuit breaker idol ...gusto kopo malaman ...

  • @gilpatez5766
    @gilpatez5766 2 ปีที่แล้ว +2

    Okay sir! para s'min Galing ka Talaga magturo. Direct to the point kaya madali sya maintindihan, Salamat sa pag share mo! ng iyong Talent Idol.

  • @edgardelacruz2363
    @edgardelacruz2363 7 หลายเดือนก่อน +2

    Ang galing nang explanation ,,thank you sa knowledge idol,❤

  • @gelouber7635
    @gelouber7635 ปีที่แล้ว +2

    galing idol. marming slmat. malinaw na malinaw paliwanag m. auto subscribe!!!!

  • @romtelpo4471
    @romtelpo4471 หลายเดือนก่อน

    Thanks for sharing your knowledges.. God bless you Boss..

  • @KennyJ-pf7pr
    @KennyJ-pf7pr 7 หลายเดือนก่อน

    Master.. thank u sa knowledge na sinishare mo.. magagamit ko ito pra sa application for Authorization accreditation ID ng lokal electric coop dto sa probinsya.. isa Po akong bubo sa math my pobya sa math gawa ng lagi Ako pinapahiya ng teacher ko sa elementary Kya hngng colege dala dala ko Ang takot sa mga furmula.. Ngayon ko lng naintindihan bkit Lalo sa trbhong electrical na mas efamilyar mo sarili mo sa computation Lalot di pwdi Ang ok na dapat alam mo ang dahil bkit ok na.. di pwdi bsta bsta gnyan lng Yan.. thank u master kc napawi Ang takot ko sa formula..

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  7 หลายเดือนก่อน +1

      Salamat po sa feedback Master. GODBLESS PO😊❤️

    • @KennyJ-pf7pr
      @KennyJ-pf7pr 7 หลายเดือนก่อน

      Master.. sa Dami ng blager Jan sa electrical ikw lng ang malinaw at to the point Ang xplanation.. sa tesda kc di Yan napapagusapan ika nga hndi lhat ng knowledge at dapat mo malaman isusubo nlng ni tesda.. Yan kc ang isa sa pansindak ng mga beterano na Sila matatalino at magaling sa skedule of load computaion.. sana next time 3phase naman master Lalo na sa MDP at Dp's riser at mga connections..

  • @titotiks1971
    @titotiks1971 2 ปีที่แล้ว +12

    Sir napansin ko lang po, yung minultifly nyo sa demand factor is yung total load nyo, di po ba dapat ang kuhaan nyo nang demand factor ay yung rating nang breaker? Para di sya mag overload for example
    Lighting Circuit Breaker rating is 15A, so 15Ax230v =3450va x.80=2760VA ang max load nyo sa lighting. But its okey konti lang naman ang load.
    Sa Outlet Circuit Breaker rating is 20A x230v=4600va x.80=3600va yang po ang max load nyo sa convenience outlet.
    Sa calculation nyo po, yung actual load nyo po ang minultifly nyo sa demand factor, hindi na po kasi mababago yun eh, sa pagkakaalam ko po kasi yung load carrier ang kukuhaan nang demand factor para safe sya sa continous operation at tumagal ang life span nya.
    Like for example a transformer with a 100kva rating, 100,000va *.80= 80kva it means 80kva lang ang pwede nyo I load in this transforner.
    Please correct me if I'm wrong po.

    • @ronnienavarro6688
      @ronnienavarro6688 2 ปีที่แล้ว +1

      Bro hndii na ng reply sau. Hahaha..natulala na sa pinakita mo formula. Hahaha .. tinanong ko nga kung gumagawa xa ng ATS WITH GENERATOR AUTO START.. DI YTA ALAM.. PANG BUILDING WIRING LANG XA.. MANUAL TRANSFER SWITCH LNG ALAM ..

    • @titotiks1971
      @titotiks1971 2 ปีที่แล้ว +2

      @@ronnienavarro6688 oo brod, dapat tanungin din natin sya, kasi kung mabasa nang ibang di pa din masyado nakakaunawa, maliligaw, maige ma discuss, kung tama talaga sya. Para everybody is safe.

    • @jeosamcastv8457
      @jeosamcastv8457 2 ปีที่แล้ว +7

      Ang dapat kung my comments tayo...sa tamang pamamaraan lang para hindi mapahiya...kung tatangapin nya ang komento...mas makakabuti sa kanya...wag tayong mapagmataas dahil ayaw ng Diyos yan....Godbless to all...

    • @lovefive5326
      @lovefive5326 2 ปีที่แล้ว +5

      @@jeosamcastv8457 tama kapo diyan. ang gusto lang naman ni sir ay mamahagi ng kaalaman niya kung meron mang mali ay sabihin ng maayos at hindi nagtotono na mapagmataas. Panigurado ako na kahit si sir ay nagtuturo ng kaalaman niya gusto niya rin naman na may matutunan siya sa bawat taong nakakanood ng video niya.

    • @gugmaseka
      @gugmaseka ปีที่แล้ว +1

      pwede naman ang gawin is:
      Amp * 1.25
      so sa nakuha niya ay 1.73 * 1.25 as per PEC
      makukuha lang ay 2.16Amps meron tayong 6amps na breaker subalit,
      as per PEC ay 15A nga ang minimum na breaker.
      so 15A x 0.80 = 12Amp lang ang pwedeng gamitin
      or A*V = 12 * 230 = 2760VA lang ang pwedeng gamitin.

  • @noelpante1631
    @noelpante1631 2 ปีที่แล้ว +1

    good eve..thanks for sharing your project..good job👍more Power.GODBLESS🙏🙏

  • @littlemiss9183
    @littlemiss9183 2 ปีที่แล้ว +4

    thank you dahil natulungan mo po ako sa final exam ko :)

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +3

      Salamat po sa feed back master! MERRY CHRISTMASS and HAPPY NEW YEAR TO YOUR FAMILY! GOBLESS!!❤❤
      Greetings From: Electrical Pinoy Tutorial TV

  • @teofiloperanjr
    @teofiloperanjr 2 หลายเดือนก่อน +1

    ok idol clear ang explanation madali ma gets tnx

  • @kuyanokofficial0523
    @kuyanokofficial0523 2 ปีที่แล้ว +2

    Dami kung natutunan sa mga video mo master more video godbless

  • @edilbertsimela506
    @edilbertsimela506 ปีที่แล้ว

    God bless you master meron nanaman kaming natutunan sayo... kagaya ko na bagohan pa lamang po

  • @ivydiano4529
    @ivydiano4529 ปีที่แล้ว +1

    Sir galing mu mag paliwanag at malinaw un camera lang masakit sa Mata kasi Malabo ung kuha Ng camera.sana sa susunod malinaw kasi para mas ma ayus at di masakit sa Mata Mang hula kung Anu naka sulat. More power sir 👍

  • @eugeneestrellado9131
    @eugeneestrellado9131 2 ปีที่แล้ว +1

    Thanks for sharing idol. Shoutout idol Estrellado family ng luisiana lag. Good luck sa mga project mo

  • @rauljacla8015
    @rauljacla8015 2 ปีที่แล้ว +1

    Shout out po thank you po IDOl kc madami aq natutunan say God bless po

  • @kuntingkaalaman6747
    @kuntingkaalaman6747 2 ปีที่แล้ว +5

    As per PEC,,
    1 gang Co 180va
    2 gang Co 180va
    3 gang Co 180va
    4 gang (90*4 = 360va)

    • @rosper797
      @rosper797 ปีที่แล้ว

      Yes, tama po kayo. Malaking tulong para mas accurate ang computation

  • @sannybarcial5884
    @sannybarcial5884 6 หลายเดือนก่อน

    Malaking bagay Yan idol sa mga nag aaral ng electrical n2.

  • @JanFrancisDeCastro
    @JanFrancisDeCastro 7 หลายเดือนก่อน +1

    Thank u sir salamat po sa Dios salamat sir

  • @lagrosaartchi9470
    @lagrosaartchi9470 2 ปีที่แล้ว +1

    Ok po sir,,, salamat at may matutunan po ako sa tutorial mo po,,, sana may fb page po kayu,,

  • @johnfernandez2722
    @johnfernandez2722 2 ปีที่แล้ว +1

    Ito ang pinka gusto ko ng mg tutorial

  • @yasser1072
    @yasser1072 2 ปีที่แล้ว +1

    meaty! ang daming matutunnan dito pare

  • @viannox5171
    @viannox5171 2 ปีที่แล้ว +1

    mahusay!

  • @jomelmaribojoc2198
    @jomelmaribojoc2198 2 ปีที่แล้ว +1

    Salamat idol sa pag turo mo

  • @japormstamayocollado4196
    @japormstamayocollado4196 2 ปีที่แล้ว +1

    Ang lupit Ng knowledge mo idol
    Electrical engineer kna yata

  • @marionloyola506
    @marionloyola506 2 ปีที่แล้ว +1

    Ayos master idol,dagdag smarties na Naman ito as ever.priceless tutorials thanks alot SA generosity mo.keep up the ingenuity you can share to every interested people.hurray!,shout out bro from Antipolo city,n thanks!

  • @patrickadriandivino5797
    @patrickadriandivino5797 2 ปีที่แล้ว +5

    Suggest ko lang Sir, always provide 2 minimum spare CB to size up your main CB. Tapos isali sa schedule of loads ang spare para masali rin sa calculations.

  • @antonmedina2379
    @antonmedina2379 2 ปีที่แล้ว +1

    Nice explanation

  • @reydsting1030
    @reydsting1030 2 ปีที่แล้ว +1

    Nice bro,,,,God bless

  • @Mimi_1430
    @Mimi_1430 2 ปีที่แล้ว

    MARAMING SALAMAT IDOL ANG LAKI NG TULONG SAKIN NITO

  • @rodelgtv4227
    @rodelgtv4227 2 ปีที่แล้ว +1

    Always keep safe idol

  • @norbertromero1732
    @norbertromero1732 2 ปีที่แล้ว +2

    Sir diba dapat po kung ang total load nyo ay 111.65 hindi na dapat i multifly by 80% yon kasi po yun na ang computation. Sa tingin ko po ang kailangan ay 140A main breaker, 140Ax80%= 112A so pasok po don yung 111.65 of load computation nyo.

    • @kuyakuyztv6619
      @kuyakuyztv6619 2 ปีที่แล้ว

      Yun din sir pagkakaintindi ko sir kasi FLC na yung 111.65,dapat di na bawasan ng 80% ,tama ata kayo

    • @benjiebucog4128
      @benjiebucog4128 ปีที่แล้ว +1

      tama k jan master dapat ung total multiply mo xa ng 125%....111.65x1.25=139.56 gamit k 150Amp. n cb wala nmn kc 140amp....150amp.multiply mo xa ng 80% ... llabas 150x.80=120amp... pasok ung 111.65amp n total current...

  • @fernando3rdalcantara814
    @fernando3rdalcantara814 2 ปีที่แล้ว +1

    Add natin yong double throw switch para sa gen. set pati na rating o laki ng gen se

  • @romytayamora5688
    @romytayamora5688 2 ปีที่แล้ว +1

    Sana naman sir mai share mo sa iyong youtube chanel ang carrying capacity ng bawat wire kung ilang watts sa bawat wire na gina gamit nating sa pag wiring installation

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      sure master noted na poh, yan,
      Salamat po sa feedback GODBLESS PO💜💜💜

  • @fernando3rdalcantara814
    @fernando3rdalcantara814 2 ปีที่แล้ว +1

    Sama natin ang administration panel.kasi may common load sa hagdanan Ilaw dappat Meron ding sub meter baka Meron din water pump na lahat ay gagamit kàya ang circuit Nyan ay sa oadmin panel

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Yes po nasa admin panel po ang top ng water pump masted d ko na cnama sa vlog para d malito ang viewers. Salamat po sa feedback master godbless lo

    • @fernando3rdalcantara814
      @fernando3rdalcantara814 2 ปีที่แล้ว +2

      @@ElectricalPinoyTutorialTV salamat sa mga sharing mo maraming natutulungan Nyan .God bless you tóo.

  • @ernestopobladormosquera6336
    @ernestopobladormosquera6336 ปีที่แล้ว +2

    Yes na yes more tutorial on-line all always looking your beautiful vloggs live video unlimited signals streaming online watching again and again in all 3 x a day in 24 hours in all 12.+ million ofw Pilipino Maharlika migrants working abroad international professional jobs watching again and again in all ❤❤❤❤❤❤❤❤❤😊😊❤😊❤😊❤😊😊❤😊😊❤😊😊

  • @benjiemiguel3050
    @benjiemiguel3050 ปีที่แล้ว +2

    di po ba sa mga largest motor is 100%df sya imumultiply?

  • @abnerdelcampomacalino8576
    @abnerdelcampomacalino8576 2 ปีที่แล้ว

    Engr. Po kayo sir o RME?? GALING NIYO PO SIR...NICE EXPLANATION DAMING BENIFITS😇

  • @sfc1312
    @sfc1312 2 ปีที่แล้ว +1

    Good video sir. Tanong ko lng po kung 2.0mm2 ang mga ggmitin na wire para sa mga ito:
    - Lighting to breaker
    - Lighting to switch
    - Switch to breaker

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +3

      yes po tamah po yan. 2.0mm2 po ang required natin gamitin para sa ilaw dapat 15amperes lang po ang inyong cb.
      Salamat po sa feedback master GODBLESS PO💜💜💜

  • @ulquiharra
    @ulquiharra 2 ปีที่แล้ว +1

    boss ang 1/2 na pvc is 20mm
    at yung 15mm na nakalagay jan i think is pra sa imc.
    tapos yung sa riser napansin ko dapat hindi conected yung room 1 and 2 sa linya galing sa mts .bka ma mis interpret ng viewer dapat nakaconnect lang siya mismo sa mdp mo boss.

  • @rizaldebuenaventura5432
    @rizaldebuenaventura5432 10 หลายเดือนก่อน +1

    boss thank you sa explain tanung ko ang sana kung mga ilaw ko e 24 watt lang seperate ko ba cya ng spare o di na consider ko na 100 watts kc mga pin light at pls advice

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  10 หลายเดือนก่อน +1

      Consider nyo nlang master ng 50watts. Salamat po sa feedback master godbless po. ❤️😊

  • @geraldabayan9779
    @geraldabayan9779 2 ปีที่แล้ว +2

    sir base po sa nabasa ko yun isang outlet po yata kahit ilang gang po nasa 180 parin

  • @regiebanate8379
    @regiebanate8379 2 ปีที่แล้ว +1

    Go LNG idol

  • @samanthajerag.netario6869
    @samanthajerag.netario6869 2 ปีที่แล้ว +3

    sir paano po kung may ref, washing machine at water heater bawat isa po ba jan may sariling breaker? or isang breaker na lang po sya at tatlong outlet na lang tas taasan na lang po ba ampere ng breaker?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Hindi po pwede basta po kapag mga appliances nyo mga spo natin is seperate po yan ng breaker as per required by PEC. Kc heavy load po yang mga yan. Salamat po sa feedback godbless po

    • @samanthajerag.netario6869
      @samanthajerag.netario6869 2 ปีที่แล้ว +2

      @@ElectricalPinoyTutorialTV bali sir dagdag po sa magiging branches ng breaker?

  • @luisjrcorpuz7972
    @luisjrcorpuz7972 2 ปีที่แล้ว +1

    sir sample naman ng 3 floors ay mayroong 3 Panel Boards (per floor)
    pero iisang Metro lang

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      cge master pag may project na po. tayo. Salamat po sa feedback master GODBLESS PO💜💜💜

  • @RRR-zh6hm
    @RRR-zh6hm ปีที่แล้ว +1

    sir kung yung mga outlet at mga ilaw ko magkakasama sa isang line at ginamit ko puro wire#12 pero ang computation ko is mahigit 11amps lang. pwede ko bang gamitin ang 20amps na breaker para kung sakaling magdagdag pa ng outlet at appliances ang may bahay? magtrip ba sya bago masunog ang wire? sa line lang kasi ng outlet kumuha ng supply ang ilaw. salamat po

  • @owmaygad7507
    @owmaygad7507 2 ปีที่แล้ว +1

    Sobra sobra nga kaalaman mo mga Electrical engineer design lang sila pero sa actual hindi mo sila maasahan.

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Salamat sa feedback , GODBLESS

    • @patrickadriandivino5797
      @patrickadriandivino5797 2 ปีที่แล้ว +1

      Eh hindi naman kase designated ang mga EE to do the actual works. Kaya nga meron tayong mga Electrician at contractors to do it. :)

  • @DP-zt5vb
    @DP-zt5vb 9 หลายเดือนก่อน +1

    Sir magandang araw.. Tanong lang san makikita sa pec yung pag 1 gang is 180 then pag two gang is multiple by 2?

  • @jenzenguinospotlight
    @jenzenguinospotlight ปีที่แล้ว

    sir parequest po kung pano gumawa ng riser diagram thank you kasama total load at size ng wire na gagamitin sa main load thank you god bless

  • @titotiks1971
    @titotiks1971 2 ปีที่แล้ว +2

    May tanong lang po ako sa MTS nyo, kasi yung Generator nyo as a back up power, will substitute the normal power which will pass through the same circuit, after nyo ma switch sa back up, may metering po ba ang generator nyo aside from electric cooperative metering? How do you meter the consumption of power from the generator?

    • @Leelee-rm5gu
      @Leelee-rm5gu ปีที่แล้ว

      Ako na lang sasagot lol,parang wala ata.

  • @jimboynuer5898
    @jimboynuer5898 หลายเดือนก่อน

    Idol may tanong po ako about sa power riser, Single breaker lang po ba ito (100A) which nasa loob ng Nema 3 enclosure at which i brabranch yung feeder line sa bawat panel board or ginamitan mo pa ng Distribution panel yung 100A at nakaplug yung 5 40A CB which nakabrach ulit sa 40A main breaker ng PB? Bali 5 40A sa DP at 5 40A sa bawat PB

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  หลายเดือนก่อน

      Yes po. Naglagay lang po ako ng MDP. Salamat po sa feedback master godbless po❤️😊

  • @mr.yhuztv5886
    @mr.yhuztv5886 2 ปีที่แล้ว +1

    Sir tanong ko lng kng ilang amps Ng cb ang pwede sa 200amp na welding machine.? Salamt po

  • @edgarjose2192
    @edgarjose2192 2 ปีที่แล้ว

    tnx po sainyo s ads nowledge

  • @jessicaaledo1574
    @jessicaaledo1574 2 ปีที่แล้ว +1

    Salamat idol copy ko paliwanag mo malinaw .Tanong lng po Yung MTS po natin 100 amperes din PApunta sa main ?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Yes po both 100A na cb ang gagamitin para sa MTS.
      Salamat sa feedback , GODBLESS

  • @farlieraylozada2001
    @farlieraylozada2001 19 วันที่ผ่านมา +1

    Okay lng po ba na 5.5 lng Ang feeder line se 40 amps na breaker?

  • @paanovlog3296
    @paanovlog3296 2 หลายเดือนก่อน +1

    boss sna masagot po EE student po ako tanong kopo sana magkano napo sa manila rate ang singilan sa MCB,MTS and MDP single phade po 230v ,sna masagot po for canvasting project po for my research slamat po

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 หลายเดือนก่อน

      Per cb. Sample MTS. 2 cb yan. Singil ko dyan 1200 kasama termination plus install ng panel board 500 abot ng 1700 to 2k. Salamat po sa feedbacl master GODBLESS po😊❤️

  • @user-ek2uf7dx2t
    @user-ek2uf7dx2t หลายเดือนก่อน

    Curious lang about electrical, tanong ko lang po sir ang ibig po ba sabihin ng 1gang co 180va, ang maximum limit po ba na ipaplug sa isang co ay 180watts? Paano po ung mga gamit lagpas ng 180watts tulad ng plantsa? Mga electric kettle di ba pwede isaksak sa co?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  หลายเดือนก่อน

      Yes po. Pag electic kettle bukod na ng cb. Salamat po sa feedback master godbless po❤️😊

  • @ismaelgarcia5966
    @ismaelgarcia5966 6 หลายเดือนก่อน +1

    Paano.po.magagawan ng load computation plan ang mga appliances

  • @AntonioTajos-rk3zk
    @AntonioTajos-rk3zk 9 หลายเดือนก่อน +1

    Magandang Araw Bos,Paano mag c0mpute ng wire sa main?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  9 หลายเดือนก่อน +1

      Pag babasehan po ninyo master ung main cb.
      Salamat po sa feedback master godbless po❤️😊

  • @eduardojrisideriodecatoria4999
    @eduardojrisideriodecatoria4999 ปีที่แล้ว +1

    Bakit 80% lang? Diba nakalagay sa PEC 2017 yung 80% is for the maximumum Load capacity of the breaker?.
    Therefore yung load mo will be multiplied by 125%

  • @rizaldebuenaventura5432
    @rizaldebuenaventura5432 10 หลายเดือนก่อน +1

    yung LED cove light ilang watts cya

  • @HEOMIXVIEWSportPh
    @HEOMIXVIEWSportPh ปีที่แล้ว +1

    Idol, yung SPO po ba pwede ba isama na dyan lahat ang Rice cooker, heater,ref,washing machine, at aircon?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  ปีที่แล้ว +1

      Hindi po tig iisa po cla ng cb. Bawat appliances nyo po gamit po kayo ng tig 20amps bawad appliances.

    • @HEOMIXVIEWSportPh
      @HEOMIXVIEWSportPh ปีที่แล้ว

      @@ElectricalPinoyTutorialTV thanks

  • @aaronsantos9551
    @aaronsantos9551 2 ปีที่แล้ว +2

    boss diba from main distibution panel na may 100 amperes may 4O amperes na breaker per branches papunta sa bawat room? tapos pagdaan ng submeter papunta sa panel ng bawat room, maglalagay ba uli ng 40 amperes na pang main breaker ng panel ng bawat room?salamat sa response idol

  • @roberthilario1047
    @roberthilario1047 2 ปีที่แล้ว +1

    Sir gusto kp lang po malaman kung Kinonsider po nyo yung Addl load para sa Future example like AC unit sa Bawat Floor or Photo Copy machine or Electric Oven Maraming Salamat po

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Yes po. May spare na po tayo 4r the future expansion.
      Salamat sa feedback master godbless po.

  • @cedrickmarkravelo4503
    @cedrickmarkravelo4503 2 ปีที่แล้ว

    idol gawa ka ng load computation para sa refrigerator..

  • @warrdudez25
    @warrdudez25 ปีที่แล้ว

    hello po pwd po ba size 8 thhn wire sa 60a circuit breaker po? dba 48a ung max load nya po?

  • @arjayreano88
    @arjayreano88 2 ปีที่แล้ว +1

    Idol parang may mali' hnd po ba dapat sa breaker na gagamitin' ka kukuha ng 80% load capacity nito para safe cya at hnd magtrip... hnd kana magbbawas doon sa overall computation mo ng amperahe kc un na ung total mo... Kaya mas mabuti na taasan mo pa ung amperahe ng breaker na gagamitin mo doon sa total computation mo'
    hnd na dapat cya bawasan' kc magttrip na un...
    Tama po ba???
    ✌️✌️✌️

    • @Roger-jp5ro
      @Roger-jp5ro 2 หลายเดือนก่อน

      nalito din ako sa computation nya ng main cb nya.nagbase cya total actual va at sa ampere total tapos multiply sya ng 80 percent.parang binawasan nya ang computed ampere at va

  • @yahyaiskak.channel
    @yahyaiskak.channel ปีที่แล้ว

    Boss pano kng ang isang bahay may 30am na breaker don na laht ng L.O C.O freezer water pump bali may tatlong aircon na may kanya kanyang breaker wala lng main breaker ok lng ba?

  • @user-le4de3pm1j
    @user-le4de3pm1j 2 ปีที่แล้ว +1

    Tanong ko lang po kung ilang watts/hp ang para sa outlet ng mga washing machine at pag spare outlet po ba need pa bang lagyan ng va per circuit? Thank you po!

  • @bertjhensaturinas8959
    @bertjhensaturinas8959 2 ปีที่แล้ว +1

    Boss. Sana yong malapit sa camera para mabasa Namin Ng malinaw. Para miron kami basihan. MGA baguhan Boss. Sana gawa kayo ulit boss.thanks

  • @roberthilario1047
    @roberthilario1047 2 ปีที่แล้ว +1

    Ask ko lsng po kung saan ang pinaka malapit na source at gaano kalayo siya muls sa MCB na sinasabi mo Thank you po

  • @noelrivera7477
    @noelrivera7477 2 ปีที่แล้ว +1

    kaya ba ng single cb 30 amps ang 10 ilaw at isang 1 hp motor pump?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      kaya po. kaya lang for safety seperate po dapat ng cb ang ang 1hp na motor pump.
      Salamat po sa feedback GODBLESS PO💜💜💜

  • @lawrencedelmendo-pi6pl
    @lawrencedelmendo-pi6pl ปีที่แล้ว +1

    Panu sir ung cable kailangan ba color coded

  • @yahjra4514
    @yahjra4514 2 ปีที่แล้ว +1

    Sir tanong ko lang. 280amp kc computation ko sa lfl sa 5 door apartment multi dwelling.ilang amp ba dapat ilagay na pinaka main cb?

    • @yahjra4514
      @yahjra4514 2 ปีที่แล้ว +1

      Bale tinotal ko kc ung 5 panel board is 280amp po. Ano pede kong gamitin sa pinaka main

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      300A. Na po master. Salamat po sa feedback godbless po.

  • @shandygaralde4593
    @shandygaralde4593 2 ปีที่แล้ว

    Sir ask ko lang po Pag Yung main breaker mo s loob ng bahay eh ganun din ba Ang breaker mo s labas s nema 3r

  • @tamagochivlog914
    @tamagochivlog914 2 ปีที่แล้ว +1

    Sir pano po pag dalawang refrigerator ang gamit sa 2 gang na C.O. anong wires at circuit breaker ang dapat gamitin para sa dalawang refrigerator

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Seperate po ng breaker po cla dapat sa standard natin. Minimum is 20A cb at #12 na wire po ang gagamitin natin. Salamat sa feedback master godbless po.

  • @joshuagepulle7911
    @joshuagepulle7911 2 ปีที่แล้ว +1

    Sir pano naman sir kung walang mga cxtv at fire alarm
    Taposga gamit ay 5 heavy duty sewing machine saka ac and reff

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Bali ganun din po. Ang computation. Bali kukuhin nyo lang po ung FLC ng bawat load. Natin. Seperate po yan ng mga cb kc mga heavy load po yang mga yan.
      Salamat po master sa feedback godbless po.

  • @imjirecord
    @imjirecord 2 ปีที่แล้ว +1

    Idol tanong lang po. hindi ba 8.0mm2 ung wire sa 40 amp. breaker?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว

      8.0mm2 na po ang ginamit natin para sa feeder line.
      Salamat po sa feedback master GODBLESS PO

  • @jayaresperanza8658
    @jayaresperanza8658 2 ปีที่แล้ว +1

    40A main breaker sa 5.5mm wire mag trip po ba yan if overload? Prang undersize po ata.

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      5.5mmm2 THHN po ang gagamiting nating wire sr. Na kaya nyang ihandle ang 40A na ampacity ng cb. Na hindi po masusunog ang wire .

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Ang THHN po kc ai may ampacity na kayang i handle hanngang 90°C. Kaya kung 5.5 ang wire na gagamin hindi masusunog hanngang 40A. Ang dumadaan na current sa ating linya

  • @rhondarenzvidad7546
    @rhondarenzvidad7546 2 ปีที่แล้ว +1

    Pano po computation pag may aircon and shower heater? Pwede po bang same lang?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      hindi po mag babase po kc tayo hp ng acu at wattages nman ng shower heater. nakasulat nman po un sa label kung gaano kataas ang load nila. Salamat po sa feedback master GODBLESS PO💜💜💜

    • @robaduba8095
      @robaduba8095 2 ปีที่แล้ว

      Ayun po sa PEC pag may motor yung susuplyan mo dapat total ampere × 125% ng full load ampere ng motor. Kunyari may 1hp ka 647 watts/220v = 2.94a yung total current eh times mo pa yan sa 125% so 2.94a × 125% = 3.67a.... kaya po ganyan kasi mataas ang current pag nag start up ang motor tapos unti2 na baba kapag running winding na ang gumagana

  • @anthonyevangelista3280
    @anthonyevangelista3280 2 ปีที่แล้ว +1

    Gud day sir ask ko lng if 3gang outlet 3 din po ba ang bilang nun sa load schedule?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Hindi na po. Salamat po sa feedback master godbless po.

    • @jonathannarvato9604
      @jonathannarvato9604 ปีที่แล้ว

      Based sa PEC every C.O. is 180va kahit pa 1-gang, 2-gang or 3-gang pa yan 180va parin dapat gamitin jan. Dapat hindi na nag multiply ng 2.

  • @talldarkencurly
    @talldarkencurly 2 ปีที่แล้ว +1

    Sir tanong lang po. san po kaya papasok na CB yung mga wallfan/ceiling fan?
    LO po ba or CO? thanks po.
    same sa mga router etc.

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Sa C.O po. Salamat po sa feedback godbless po

    • @talldarkencurly
      @talldarkencurly 2 ปีที่แล้ว

      @@ElectricalPinoyTutorialTV maraming salamat po sir. Lagi ko po kayo pinapanood. Bukas po free shipping sa shopee. Bibili na kami ni mama bukas ng gagamitin. Try ko po apply mga tutorial nyo na actual sa jumper ng line to neutral. Wala pa kasi pambili ng bagong CB. More power po

  • @clydekevintumlos5602
    @clydekevintumlos5602 ปีที่แล้ว +1

    Asan na po ung video na ganito tapos may kasamang aircon?

  • @juancarlosmilantoribio5682
    @juancarlosmilantoribio5682 2 ปีที่แล้ว +1

    Master bakit 5.5mm2 gamit mo sa 40amp diba pag 40amp na 8.0mm2 na? pang 30amp lang yang 5.5 base sa PEC

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  ปีที่แล้ว +2

      Binago ko na po in actual. #8 n po ginamit natin during installation. Dis regard nyo nlang po ung size dyan sa tinuro ko

  • @stephenalbiso6483
    @stephenalbiso6483 2 ปีที่แล้ว +1

    Master matanong Lang po kapag may limang aircon ang bahay. Ilan ang amperahe ng main breaker?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Depende po sa total load computation ng bahay nyo po para malaman natin kung anong main cb po ang gagamitin natin.
      Salamat po sa feedback master godbless po.

    • @stephenalbiso6483
      @stephenalbiso6483 2 ปีที่แล้ว

      @@ElectricalPinoyTutorialTV salamat po master

  • @angelineromanbautista6295
    @angelineromanbautista6295 ปีที่แล้ว +1

    sir ano ung meaning nung may arrow na symbol diyan, para san po yun?

  • @RommelNazar-ie2ch
    @RommelNazar-ie2ch ปีที่แล้ว

    Mga sir dapat po b 150 amps ang main n gagamitin hindi po 100amps

  • @lut0sfire748
    @lut0sfire748 5 หลายเดือนก่อน +1

    YUNG MGA ILAW SA CR AT MGA HAGDANAN AT PATHWAY EH HINIWALAY MO NA LANG SANA NG ISANG PB, UNFAIR NAMAN YUN PARA SA ROOM 1 AT ROOM 5

  • @markjoshuaeduardo8192
    @markjoshuaeduardo8192 2 ปีที่แล้ว +1

    sir tanong koln po ano poba ang AF ? cinocompute poba yun?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      AF is ampere frame. D n po ung kinocompute un po is desegnated na cb para sa isang circuit.
      Salamat po sa feedback master godbless po.

  • @ronnienavarro6688
    @ronnienavarro6688 2 ปีที่แล้ว

    Kaya mo ba gumawa ng AUTOMATIC TRANSFER SWITCH WITH AUTO START GENSET..?

  • @baboovideo2212
    @baboovideo2212 2 ปีที่แล้ว

    Master ask ko lng panu amg connection or diagram papunta sa main distribution panel..

  • @maravs5117
    @maravs5117 ปีที่แล้ว +1

    Sub panel A and B parang hindi dumaan sa main dist'n panel...

  • @hawker501
    @hawker501 2 ปีที่แล้ว

    lodz,,yung 40amps ba per room,,my branches pa ba yan na breaker,,ex,,brans ng ,ilaw,saksakan,,at yung isa pang saksakan..?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว

      Yes po master hiwa hiwalay na po sa 40amps ung ilaw? Outlet at spo sa isang room.Salamat po sa feedback master godbless po.

  • @aaronsantos9551
    @aaronsantos9551 2 ปีที่แล้ว +1

    idol ung 40 amperes main , each rooms ba un?or sa lahat na ng rooms un?un na ang pinaka main ng lahat ng rooms? salamat sa sagot idol

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +2

      Yes po master salamt po sa feedback goodnless po

    • @louieelmersimon5889
      @louieelmersimon5889 2 ปีที่แล้ว

      Dapat master (40amp.x5) =200amp.x 80% DF so bale 160amp. ang total full load current para sa mdp..Tama ba ako master? Tulad din sa pagcompute sa per room. Sum up lahat ng branch circuit kada panel

  • @johnfernandez2722
    @johnfernandez2722 2 ปีที่แล้ว +1

    Ib po ba yung S.P.O ng aircon at ref

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Same SPO. sila. SPO lang ang term ko kc mga heavy appliances po dapat po bukod ng cb palage.
      Salamat po sa feedback master godbless po.

  • @samanthajerag.netario6869
    @samanthajerag.netario6869 2 ปีที่แล้ว +1

    sir bat po nag assume na lang po kayo na isang SPO na lang? kasi kalimitan naman po sa ngayon di nawawala sa isang bahay ang ref at washing machine?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Higher load n po ang ang dineclare ko plano para maging accurate ang computation po

    • @winstondelacruz5225
      @winstondelacruz5225 2 ปีที่แล้ว +1

      Ref seperate tlaga yn out let ng linya at breaker kasi continuos lng yn pag gamit lalo n kung maraming lamn ref mo,pero ung washingmachine poydi isabay mo lng sa pG saksak yn sa iba hindi nmn 24hrs pgmit washing machine at hindi nmn continous sa pgmit sa pgllaba

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว +1

      Salamat po sa feedback master godbless po.

  • @totoy9695
    @totoy9695 2 ปีที่แล้ว

    Bos idol pwede ba dalawa .5 na aircon isang linyada 5.5 wire 30 amps breaker?

    • @ElectricalPinoyTutorialTV
      @ElectricalPinoyTutorialTV  2 ปีที่แล้ว

      hindi bukod po sila ng cb kahit tig 15amps lang.
      Salamat po sa feedback master GODBLESS PO💜💜💜
      KINDLY SUPPORT AND LIKE,SHARE AND FOLLOW OUR FACEBOOK PAGE AND SUBSCRIBE MY TH-cam CHANNEL:
      FB PAGE LINK:
      facebook.com/Electrical-Pinoy-Tutorial-TV-104634308893921/
      TH-cam CHANNEL LINK:
      th-cam.com/users/ElectricalPinoyTutorialTV
      THANK YOU! GOD TO BE THE GLORY! GOD BLESS 💜💜💜