Computation Para Malaman Ang Wire Size at Circuit Breaker Para sa Aircon

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 พ.ย. 2024

ความคิดเห็น • 1.2K

  • @junauxtv
    @junauxtv  5 ปีที่แล้ว +10

    175%-225% ang tama

    • @marlon6254
      @marlon6254 5 ปีที่แล้ว +1

      Sir wala po bang formula kung paano makukuha ang FLA ng isang electric motor...?

    • @gapyaci5507
      @gapyaci5507 5 ปีที่แล้ว +1

      @@marlon6254 Meron po naman Sir na formula sa pagkuha ng FLA ng isang electric motor. Pero pag AC hindi mo po pweding gamitin ang mechanical HP para sa pag compute ng FLA kung halimbawa hindi nakaindcate sa rating doon sa unit po.

    • @allanazotesjr5972
      @allanazotesjr5972 5 ปีที่แล้ว +11

      Three phase Ac Motor Computation to Find Ampere in Delta
      I=Hp×746/√3×V×Eff×Pf
      I=Kw×746/√3×V×Eff×Pf
      Single phase Ac motor Computation to find ampere
      I=Hp×746/V×Eff×Pf
      I=Kw×1000/V*Eff×Pf
      To find Ampere in Wye (FLA)
      Pag nakuha mo na yung Ampere ng Delta. FLA of Delta÷√3=FLA of Wye

    • @joseponce9275
      @joseponce9275 5 ปีที่แล้ว +2

      Hi Sir Jun, ask ko lang din po pala,
      Kasi nasa example 1.5 HP.
      Same lang din po ba ang gagamiting 175% - 225% De Rating kahit gaano kataas ang Horse Power ng Aircon? :)
      Salamat po. Wait ko po yung sagot n'yo Sir. :)

    • @jolitoparado5476
      @jolitoparado5476 5 ปีที่แล้ว +1

      Jun Aux TV sir anu po ba ang gagamitin na ocpd at size ng wire para sa 1/2 hp.paanu po ang computation.

  • @gapyaci5507
    @gapyaci5507 5 ปีที่แล้ว +19

    NIce Sir. Konting trivia lang ako Sir, FLC is from code and FLA is from rating of a certain electric motor. As my own term lang po ito para madali ko syang matandaan FLC = Full Load Code, FLA = Full Load Actual.

    • @blackycute123
      @blackycute123 5 ปีที่แล้ว

      Thanks sir :)

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +1

      Salamat sa walang sawang suporta Engr. Icay.God bless po sir

    • @joseponce9275
      @joseponce9275 5 ปีที่แล้ว

      Thank you. Hehehe
      Naaalala ko na. :)

    • @flordtom
      @flordtom 5 ปีที่แล้ว +3

      FLC & FLA is the same , there is no such thing as Full Load Code & Full Load Actual

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +5

      FLA is for overload
      FLC is for Conductor size and cb ampacity
      FLC is from code book and FLA is from actual nameplate of the motor

  • @melsoriano6503
    @melsoriano6503 4 ปีที่แล้ว +2

    sir walang problema ang explaination mo actually galing narin sayo na nagpatulong kpa sa mga ingineers para maiparating ng maayos ang kaalaman so palagay ko ang nagsabi sayo na magulo ay wala lang talaga interest na matuto or gusto ay actual lang ang itututro mo keep it up may kagaya ko parin na nanonood at nagtitiwala sayo

  • @abigaillupai7201
    @abigaillupai7201 4 ปีที่แล้ว +9

    Ano pong size Ng wire para sa .6 hp aircon..at Ilan PO dapat Ang ampere Ng breaker.ty po

  • @junemonteros9590
    @junemonteros9590 4 ปีที่แล้ว +1

    Boss dto lang kmi nka suporta sayo tulad ko kahit paano may natutunan ako sayo tsaka kumpara sa iba malinaw ka mg turo god bless u lage

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat po sir....God bless us all po

  • @torcrame4183
    @torcrame4183 5 ปีที่แล้ว +3

    I encourage sa mga viewer na kahit may tutorial na katulad nitoo hindi ibig sabihin na pwde na tayong mag fix, gumawa at mag-install require ang proper training at schooling para maging safe ang gingawa natin at lehitimong elektrisyan lamang ang may kakayahan na gaing ang mga electrikal related works.
    Dapat parin tayo komunsulta sa mga lisensyadong elektrisyan para maging ligtas at maprotektehan ang ating pamilya at gamit sa maaring panganib sa dulot patungkol sa mga kuryente.

  • @bienvenidosibug5977
    @bienvenidosibug5977 4 ปีที่แล้ว

    JunAux, Thank you, I am your avid follower, IExcellent teaching performance mo, I i really learned a lot sa mga positive video mo, Bsie teacher ako sa nite hs handling TLE, property custodian, nagamit ko iyong mga tutorial video mo. Keep Safe God Bless You.

  • @abuxxx3607
    @abuxxx3607 5 ปีที่แล้ว +8

    correction sir, kung nag increase ka ng 175-225% ibig sabihin multiplier un at hindi derating factor. kc ang derating ibig sabihin binawasan mo from it’s original value. #my2cents

    • @blackycute123
      @blackycute123 5 ปีที่แล้ว +2

      Oo satingin ko rin multiplier sya :) ..Kasi yung derating factor parang sa conductor ata yun.. For example kapag summer ..mainit ang temperature nag exceed 30°C ibig sabihin magdederate din ampacity ng wire ..

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +1

      Sorry sir siguro mali lang ang term na ginamit..

    • @bongsalva6885
      @bongsalva6885 5 ปีที่แล้ว

      Jun Aux TV tingin ko nga mali ang term na nagamit mo. Tama si Abu Gab sa kanyang nabanggit. Ito ba ay nkita o nabasa mo sa PEC? Kung ganun, mali ang pagkakasulat ng PEC at dpat ipagbigay alam mo sa tech'l committee nila para ma-revise nila ang wordings.

  • @derickkupalson5414
    @derickkupalson5414 4 ปีที่แล้ว

    Very nice saktong sakto tamang tama dapat talaga di tataas sa ampere rating ang possible mangyare sunog na aircon di pa nagtitrip 😀😀

  • @relaymatik5984
    @relaymatik5984 5 ปีที่แล้ว +5

    Yung sa starting current ba ng motor yang sinasabi mo mataas talaga yan ng x6 or 600% bago mag normalize

    • @torcrame4183
      @torcrame4183 5 ปีที่แล้ว

      600% is not apply for that particular load...i.e WAC...

    • @edwardnonescan3479
      @edwardnonescan3479 4 ปีที่แล้ว +1

      para sa mga malalaking motor yan.. tama yan.. example nyan fire pump na 50hp, 3phase. ... ma lalaki talaga ang starting currents nun.. 600% ginagamit sa computation nun at fire rated cables gamitin.

    • @nenitavillamor6374
      @nenitavillamor6374 3 ปีที่แล้ว

      Ask ko lang kung paano kung 3.5 ang size ng ACU namin. Salamat

    • @relaymatik5984
      @relaymatik5984 3 ปีที่แล้ว +1

      @@nenitavillamor6374 ano po ba acu ninyo inverter na po ba or yung mga dating model parin para safe gamit nalang po kayo ng 5.5 stran wire

    • @nenitavillamor6374
      @nenitavillamor6374 3 ปีที่แล้ว

      @@relaymatik5984 mga inverter na po acu ko. Salamat

  • @radical0720
    @radical0720 4 ปีที่แล้ว

    salamat sir. ito magandang video na maayos ang paliwanag at may batayan o reference di ung base lang sa experience o opinyon. more power!

  • @maribelcaderao8417
    @maribelcaderao8417 5 ปีที่แล้ว +3

    Sir my tanung ako pwd. Magdagdag kc kami ng 6 acu. Ang 5.tag 2.3hp. Ang 1 1.5hp. Ok lang ba gagawa ako ng sub panel? Ang main ko ay 100 tapoa sa isang acu tag 20ampers xa. Din 3.5 nga wire ang gagamitin. Ok lang ba yan sir?

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Para sure po kayo mam sundan nyo lang po ung video natin sa computation...madali lang yan mam...tanong po kayo sakin kung may hindi po kayo naiintindihan

    • @mercylynnemalicay4659
      @mercylynnemalicay4659 4 ปีที่แล้ว +2

      Suggestio lang po ah.... Sa 1.5hp acu 10amp Po..... 5.5 thhn or thwn wire size tapos grounding natin 3.5 .....and 30 amp breaker ...
      Ganun din po sa 2.3hp......sa 6branch.... 60amp main breaker nyo #6 as 14mm service intrance wire ....corretion nalang po if my mali .....

  • @milktribe
    @milktribe 4 ปีที่แล้ว

    Maraming salamat dito sa video mo sir,, nagionstall kasi ako ng ercon at wala ako background sa pag pili ng breaker sa ercon ko,, and ammo ko natutunan dito. Thanks a lot

  • @arnelaustria9419
    @arnelaustria9419 5 ปีที่แล้ว +4

    sir ano po size of wire at OCPD ng 1hp aircon?

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +2

      20A #12wire size po

    • @filecategory6596
      @filecategory6596 5 ปีที่แล้ว

      YOU ARE MISGUIDING THESE PEOPLE.
      1) ARE YOU LEP (LICENSED ELECTRICAL PRACTITIONER)?. COZ IF NOT, YOU DONT HAVE THE AUTHORITY TO PRACTICE ELECTRICAL UNLESS UNDER THE SUPERVISION OF LEP. RA7920..
      2) HAVE YOU STUDIED ENGINEERING? PEC IS JUST THE BASICS. BUT THE VEINS ARE THE CORE SUBJECTS OF ELECTRICAL ENGINEERING.
      3) DO NOT MISLEAD THE PEOPLE BY GIVING THEM WHAT YOU'VE READ ON PEC WITHOUT ENGINEERING EDUCATION. THERE ARE PARAMETERS TO CONSIDER BEFORE INSTALLING WHATEVER EQUIPMENT THAT IS..
      4) YOU COULD BE JAILED IF YOU'RE DOING ELECTRICAL PRACTICE WITHOUT A LICENSE - RA7920.
      5) ELECTRICAL IS ONE OF THE MOST CRUCIAL WHEN IT COMES TO OPERATION. THIS IS THE REASON WHY ONLY LEP HAS THE AUTHORITY TO PRACTICE/SUPERVISE ELECTRICAL.
      6) YOU MAY THINK OF IT LIKE A SIMPLE CALCULATION BUT THE ENGINEERING METHOD IS NOT. EVER THINK WHERE THOSE MULTIPLIERS COME FROM? 125,225,250,140,130 ETC. IT'S ENGINEERED...
      7) ALWAYS CONSULT A LEP(LICENSED ELECTRICAL PRACTITIONER FOR YOUR SAFETY)
      8) YOU ARE DISREGARDING THE SAFETY FACTOR FOR THE CLIENT.

    • @edguantero9188
      @edguantero9188 3 ปีที่แล้ว

      @@filecategory6596 can you give us some light on this correction ? It looks like you are an engineer ?

  • @jeffreyednalino8295
    @jeffreyednalino8295 4 ปีที่แล้ว

    Sir salamat nagdadagan kaalaman ko sa mga vlog nyo plan ko kc kumuha ng nc2 para dagdag knowledge at magamit ko kht sa bahay lng or pede sideline.

  • @vochemindagnal9829
    @vochemindagnal9829 5 ปีที่แล้ว +3

    sir sana sinama mo kung paanu mgcompute sa 3phase ,may single phase kna para kumpleto tlga..hnd ko sure kung gagamitan ng (√3)square root of three ung 3phase s computation....mapansin sana sir.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +3

      Dagdag natin sa topic yan sir...tnx po

  • @randypaneda5696
    @randypaneda5696 4 ปีที่แล้ว +1

    The best po kayo Sir, marami napo ako natutunan sa inyo po.. Sana marami pa kayo ipapakita sa mga video niyo po.. Siya nga pala po san po ang office niyo po..

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Marami pa tayong pag uusapan sir.... maraming salamat din po sir sa pagtakilik sa mga videos sa channel natin sir...

  • @julitocm964
    @julitocm964 5 ปีที่แล้ว +1

    maraming salamat po sir sa explanation nyo. Nakakatulong talaga para matuto tayong magcompute ng load saka mag wiring, Sana more video pa sir. Thnaks po sir.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Yes sir marami pa po... salamat din po sir

  • @sacphiltv933
    @sacphiltv933 4 ปีที่แล้ว

    Very nice explanation. Pag may nagreklamo pa ei mag aral na sila sa tip. Godbless boss.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat po sir...

  • @helpingsharingofskill8908
    @helpingsharingofskill8908 5 ปีที่แล้ว +1

    galing mo pre, hayaan mo sila ingget lang yon, ang importante, naka2long ka..

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Haha...ayos lng yan sir sila dahilan na pag igihan ko pa ang paggawa ng mga video ko sir

    • @filecategory6596
      @filecategory6596 5 ปีที่แล้ว

      YOU ARE MISGUIDING THESE PEOPLE.
      1) ARE YOU LEP (LICENSED ELECTRICAL PRACTITIONER)?. COZ IF NOT, YOU DONT HAVE THE AUTHORITY TO PRACTICE ELECTRICAL UNLESS UNDER THE SUPERVISION OF LEP. RA7920..
      2) HAVE YOU STUDIED ENGINEERING? PEC IS JUST THE BASICS. BUT THE VEINS ARE THE CORE SUBJECTS OF ELECTRICAL ENGINEERING.
      3) DO NOT MISLEAD THE PEOPLE BY GIVING THEM WHAT YOU'VE READ ON PEC WITHOUT ENGINEERING EDUCATION. THERE ARE PARAMETERS TO CONSIDER BEFORE INSTALLING WHATEVER EQUIPMENT THAT IS..
      4) YOU COULD BE JAILED IF YOU'RE DOING ELECTRICAL PRACTICE WITHOUT A LICENSE - RA7920.
      5) ELECTRICAL IS ONE OF THE MOST CRUCIAL WHEN IT COMES TO OPERATION. THIS IS THE REASON WHY ONLY LEP HAS THE AUTHORITY TO PRACTICE/SUPERVISE ELECTRICAL.
      6) YOU MAY THINK OF IT LIKE A SIMPLE CALCULATION BUT THE ENGINEERING METHOD IS NOT. EVER THINK WHERE THOSE MULTIPLIERS COME FROM? 125,225,250,140,130 ETC. IT'S ENGINEERED...
      7) ALWAYS CONSULT A LEP(LICENSED ELECTRICAL PRACTITIONER FOR YOUR SAFETY)
      8) YOU ARE DISREGARDING THE SAFETY FACTOR FOR THE CLIENT.

  • @leoawag578
    @leoawag578 5 ปีที่แล้ว +1

    Para sa akin sir Jun maliwanag ang tutorial mo.
    Ang nagsabing magulo sir sila yon ginugulo nila ang isip nila.
    Hindi nila iniisip na sila walang naibigay na kaalaman baka kong may kaalaman nila sinasarili nila kasi madamot sila hindi kagaya mo na nagsishare ka ng iyong kaalaman sa iba.
    Dapat sila pasasalamat kahit nagulohan sila.
    Patuloy sir sa mabuti mong gawain.
    Para sa akin ikaw ay isang hero at dapat pasasalamatan.
    thanks sir Jun.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      maraming salamat din po, yaan mo na yan sir..hahaha

    • @allthatmatters2441
      @allthatmatters2441 5 ปีที่แล้ว

      ingat k lng bka mali ang natututunan mo.consult a knowledgeable people about the subject .....ed

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      @@allthatmatters2441 ano po ba mali jan sa tinuro ko sir kasi parang mas alam nyo ata computation nito..pwd po ba namin malaman saan ako mali para maverify ko din.... salamat sir, Gob Bless you po sir Ed Pasto

    • @allthatmatters2441
      @allthatmatters2441 5 ปีที่แล้ว

      @@junauxtv bro.ok ang ginagawa mo.income generating ang mg youtube,pero nman sana mging responsable ka sa mga sinasabi mo dito.yung wala kng maooffend na group ng tao.qoute ko lng ung caption nung isang video mo. parangganito mo sinabi" maraming electrician ang di alam ito"....wag n tying electrician ang patutsadahan mo.focus k n lng sa advice mo ng walang side comments pa.ok?

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      @@allthatmatters2441 income generating oo nandon na tayo pero hindi po ganun kalaki sa inakala mo dapat alam mo yan sir pambili lng din ng materials para sa Tutorial .... TH-camr ka din db?...mali po ata kayo ng interpretation don sa caption ko sir....ginawa ko un para macorrect ang ibang Electrician....hindi para maoffend ang mga Electrician...tingin mo sir bakit ko ginagawa ang channel ko?tingin mo ba para maoffend ang mga Electrician?...ginawa ko tong channel na to para matulongan at magkaroon man lang ng idea ang mga ibang Electrician na hindi alam kung ano ang PEC at ano ang standard....

  • @JesusMallari1959dec28
    @JesusMallari1959dec28 4 ปีที่แล้ว

    Napakalinaw sir ng paliwanag mo at sana lumaki pa lalo ang channel mo para mas marami pang makinabang. Sana dalawin mo rin ang channel ko para makapagsuggest ka sir kasi gusto ko ring makatulong sa marami. Salamat sir.

  • @norielangeloduran322
    @norielangeloduran322 3 ปีที่แล้ว

    salamat po ng marami sa clear answer ng circuit breaker ng aircon .. godbless po

  • @joseponce9275
    @joseponce9275 5 ปีที่แล้ว +1

    Salamat po Sir. :)
    Abangan ko pa lahat ng videos na ilalabas mo. :)
    Magagamit ko po ito para sa Board Exam ng RME.
    Suggest Videos po sir, sana sa susunod mo yung tungkol din po sa RME Exam po..
    Maraming salamat po. :)

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Dagdag natin sa topic yan sir...

    • @joseponce9275
      @joseponce9275 5 ปีที่แล้ว

      Sa nakaraang Topic nyo po about Load Computation, hindi nyo pa po natatapos yun. Nag-end yung videos sa Service Entrance Conductors.
      May natitira pa pong 4. SERVICE EQUIPMENT AND 5. DIAGRAM.

  • @mhadtv9901
    @mhadtv9901 5 ปีที่แล้ว +1

    Boss lahat ng tutorial mo shinishare ko sa classmate ko sa Tesda Pa shout sir salamat😁

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat po sir....

  • @reynaldaclan7952
    @reynaldaclan7952 5 ปีที่แล้ว +1

    Sir pa shout out po .. lage akong nanunuod sayo .. student po ako sa BOHOL ISLAND STATE UNIVERSITY ( BISU ) nice po mga videos mu nkatulong talaga sakin sir thanks po

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Sino prof mo sir....galing ako jan....

    • @reynaldaclan7952
      @reynaldaclan7952 5 ปีที่แล้ว +1

      Jun Aux TV c Prof. CEFERINO LAMANILAO PO SIR .. DITO PO KAYO NAG SCHOOL ??

    • @reynaldaclan7952
      @reynaldaclan7952 5 ปีที่แล้ว +1

      Jun Aux TV pa shout out nmn po 👍

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      @@reynaldaclan7952 tanong mo nga sa kanya sir kung naalala nya Jundemel Auxtero? sabihin mo sir i-recommend kamo nya yong youtube channel ko hahaha...shout out ko kayong dalawa sir...add kita sa facebook sir, sana makausap ko si sir lamanilao.jan ako ng aral sir sya din prof ko

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      @@reynaldaclan7952 cg po..pwd ba sir makavideo call si sir lamanilao?

  • @mbp9012
    @mbp9012 5 ปีที่แล้ว +1

    New subscriber here. Wala akong alam sa electrical pero sayo natototo ako. Good job at ituloy mo lang ang informative video, marami kang natutulungan👍👍

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Tnx sir...and welcome to our channel

  • @michaelmalinao8699
    @michaelmalinao8699 4 ปีที่แล้ว

    Salamat sir sa video marami aqng natutunan mabuhay kayo sir

  • @shaabalos2617
    @shaabalos2617 4 ปีที่แล้ว

    thanks po.sakto mgkkabit ako bukas ng 1.5hp window type ac.

  • @albertovillaruel6100
    @albertovillaruel6100 4 ปีที่แล้ว

    Ayos yan sir kasi nasa standard ng PEC ang basehan mo God bless

  • @ericbenemerito8115
    @ericbenemerito8115 3 ปีที่แล้ว

    Maraming salamat sir natoto ako kc bago lng po ako sa house wiring po

  • @sherrylperlas8729
    @sherrylperlas8729 5 ปีที่แล้ว +1

    sir..my mga negative viewers ka pala...para sakn naiingit lng sa u sir jun... kasi ang totoo hnd nla kaya ung talino mo at abidad about eletricity...sir marame ka nga natutulongan e...isa na ako dun.. sir hayaan mo lng cla ...godbless more power to u...

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Aware ako jan mam sa lawak ng Electrical hinding hindi mo talaga makabisado ang lahat kaya marami talagang maraming alam kisa satin....pero naniniwala akong aangat tayo...

  • @joselitoloreto5719
    @joselitoloreto5719 5 ปีที่แล้ว +1

    Gusto ko tong video mo ngayon sir kasi supported na ng code ang mga nilelecture mo.
    Kung hindi naman makakaabuso sa inyo, pwede po ba next time gumamit ka ng index card. Para maganda yung sequence at maging direct to the point ang lecture mo.
    Yung sinasabi ng iba magulo ka magpaliwanag, hindi totoo yun.
    Nakakahilo ka lang magpaliwanag kasi may mga pinapasok ka sa lecture na hindi kailangan sa topic. Hehe
    Thanks for taking time to read.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Thank you sir...medyo need lng talaga ng matinding aral alam mo nmn ang PEC sir hirap intindihin...tnx po sa suggestions sir

  • @robertpalomata4653
    @robertpalomata4653 2 ปีที่แล้ว

    Thanks sa info sir. Pwede ba mag request? Computation ng breaker at wire pra sa 5-units na ACU na 1.5 HP plus 3-units na ACU na 2HP. Thanks.

  • @JLFerriol567
    @JLFerriol567 4 ปีที่แล้ว

    Sir. . .salamat sa mga informative knowledge mo about sa mga electrical. . .Pwede ka rin ba gumawa ng tutorial kung paano mag compute ng mga malalaking load katulad sa mga Factory na malalaki ang load kung paano computetin ang gagamiting mga wire at mga circuit breakers Thanks. . .sa mga sharing mo . . .God bless

  • @geronimoisla1606
    @geronimoisla1606 3 ปีที่แล้ว

    Galing mo tlga idol dami Kong natutunan pa shout out idol

  • @mjs_drawing16
    @mjs_drawing16 3 ปีที่แล้ว

    Sir.. Anong pangalan ng libro na ginamit para sa table... Please notice me

  • @rjbagyan161
    @rjbagyan161 5 ปีที่แล้ว +1

    Para na ako kumuha ng 2years course sa electrical,Godbless kapatid.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Hahaha... maraming salamat din po sir

  • @arnelnaing1001
    @arnelnaing1001 4 ปีที่แล้ว

    carry lng sir.. salamat sa lesson.. more power.

  • @rameltanedo7856
    @rameltanedo7856 3 ปีที่แล้ว

    Slamt sir nagkaroon ako ng idea tungkol sa wire ng aircon

  • @MultiBatman3000
    @MultiBatman3000 3 ปีที่แล้ว

    Sir salamat sa yo may natutunan ako. Sa 2 hp po. Pwede ba ang no. 12 thhn bago ang breaker nya 30 amp. Or pwede ba na no.10 thhn ang gagamitin ko tapos 30 amperes din ang breaker. Salamat sa magiging tugon nyo.

  • @louiecarbonilla4229
    @louiecarbonilla4229 5 ปีที่แล้ว +2

    sir next video pa request nmn...
    proper installation ng service intrance..salamat..✌️

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว +1

      Noted po sir...

  • @rogermoda2011
    @rogermoda2011 5 ปีที่แล้ว +1

    Hi sir Jun very interesting yung naging topic nyo. Hindi po ako electrical pero itatanong ko lang po sa conductor sizing kung ikinonsidera ba sa 125% de-rating factor yung tinatawag nila voltage drop halimbawa ang tapping from the source nasa 10 meters ang layo. My mga data po ba kayo ng mga std.breaker selection. Thanks.

    • @junauxtv
      @junauxtv  5 ปีที่แล้ว

      Malaking building po ba to sir or residential lng po?

    • @rogermoda2011
      @rogermoda2011 5 ปีที่แล้ว

      @@junauxtv Residential lang po ito sir.

  • @radiantfairy4079
    @radiantfairy4079 2 ปีที่แล้ว

    Salamat sa video sir. Pwede po ba sa isang 20A cb and 2 x 0.75hp inverter aircon? Bale total nila is 1.5hp din naman. Wala na po kasing extra na paglalagyan sa panel. Salamat po.

  • @ezraalvaro2994
    @ezraalvaro2994 4 ปีที่แล้ว

    salamat po sir jun may natutunan po ako new lang po ako sa chanel mo

  • @livinsolow9198
    @livinsolow9198 4 ปีที่แล้ว

    Maraming thank you sir.. Naliwanagan aq..
    Sana magtuloy tuloy pa kau sa mga pag gawa ng mga video related sa electrical

  • @mary-joycetorrepapalma3015
    @mary-joycetorrepapalma3015 4 ปีที่แล้ว +1

    Salamat boss na dagdagan ang kaalaman ko.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir

  • @tanyaortega5291
    @tanyaortega5291 3 ปีที่แล้ว

    sir base sa compute nyo 12.5 ampacity wire ang need. so basta may ampacity na 12.5 ang wire pwede na? nakita ko sa columbia brand wire table 1.6mm wire nila ay 25 amps na, so pwede na ito? ang 2mm wire nila may ampacity na 30. halos triple ng 12.5 na kailangan based sa compute nyo

  • @one_man_army...
    @one_man_army... 4 หลายเดือนก่อน

    Sir, Yung in-rush current ba ilang percent sa FLC during starting if 1 HP ang iyong A/C

  • @roypeterosjr.9850
    @roypeterosjr.9850 4 ปีที่แล้ว

    IDOL ! MARAMING SALAMAT SA KNOWLEDGE PA SHOOUT OUT NAMAN PO SA NXT VLOG MO . PASHOUT OUT PO NGPROF. NAMIN SA TESDA SI SIR MANNY CORPUZ SIYA PO NAGRERECOMMEND NA PANUORIN TO
    ! MORE POWER SIR AT GOD BLESS

  • @aleharamjetriptidedivas9805
    @aleharamjetriptidedivas9805 2 ปีที่แล้ว

    Salamat po malinaw po ang paliwanag po, pwede po mag request po ung diagram po ung drawing po para isang tingin ko lng po makakabisa ko na po agad 😆😆haha salamat po sa Dios...

  • @francistapiaoblena1161
    @francistapiaoblena1161 5 ปีที่แล้ว +2

    ayus yan kabayan nadagdagan naman kaalaman ko

  • @nathanaelkerbycana5369
    @nathanaelkerbycana5369 ปีที่แล้ว

    gudmorning sir.. same lng po. ba yung size wire at circuit breaker for 2hp inverter splitype?

  • @BonjoVee6161
    @BonjoVee6161 3 ปีที่แล้ว

    Hindi ako licensed electrician pero graduate ako 2yrs Electrical tech sa Samson tech nung 1982, pero DIY lang ako sinusunod ko Yung requirements ng PEC dahil puro license Electrical engineers sila.

  • @geraldinevillarba3984
    @geraldinevillarba3984 2 ปีที่แล้ว

    tuloy mo lng sr ayus yan tnx in advance

  • @jleosio3517
    @jleosio3517 2 ปีที่แล้ว

    Sir tanong lng po , ganyan din po ba ang pagcompute sa mga induction motor at pump motor tnx

  • @ewinoseo7676
    @ewinoseo7676 3 ปีที่แล้ว

    Nice sir jun salamat sa explain mo

  • @ronniecopon4714
    @ronniecopon4714 3 ปีที่แล้ว +1

    Sir halimbawa po ang nakaabang na wire ay 5.5mm at 30amp CB po.. Kasi yun dati pong AC na gamit...
    Papalitan po ngayon ng. .5hp po ok lang po ba kahit ganon pa rin ang wire?

  • @tanyaortega5291
    @tanyaortega5291 3 ปีที่แล้ว +1

    sir anong table ginamit mo pag check ng wire ampacity ng thhn

  • @richardbongay7996
    @richardbongay7996 2 ปีที่แล้ว

    Sir ano po ba ang pwedeng gamitin na wire at circiut braker para sa ac na my 0.5 Hp na aircone window type.

  • @marjonbaron4748
    @marjonbaron4748 4 ปีที่แล้ว

    Sir ganda explaination mo.. natuto ako agad thank you sir.
    Saan po ba makakabili nang libro sa PEC sir?

  • @makingdifference4498
    @makingdifference4498 3 ปีที่แล้ว

    Sir. Ok lng ba na gamitin ang 3.5mm wire sa 1hp na water pump.. na almost 30meters ang layo sa main supply

  • @danielherrerajr3444
    @danielherrerajr3444 ปีที่แล้ว

    Kung 2 horse power aircond pwede ba gamitin yung number 12 awg wire

  • @richardatenas6438
    @richardatenas6438 4 ปีที่แล้ว +1

    pwede po bang mg top sa breaker ng window tipe na aircon pra panibagong supply ng isa pang window tipe na aircon.papalitan lang ng 60amps.

  • @MultiBatman3000
    @MultiBatman3000 2 ปีที่แล้ว

    Salamat po sa paliwanag nyo. Paano po ang 2.5hp wala po ata FLC ng 2.5hp

  • @erniemulay3831
    @erniemulay3831 2 ปีที่แล้ว

    Puide po b pagsabayin ang dalawa aircon 1 hose power s 30ampers n 3.5 mm n wire.kaya po b sya

  • @ronaldsamson9321
    @ronaldsamson9321 2 ปีที่แล้ว

    Sir bgo lng me sa channel nyo.. tnong ko lng. d2 sa amin line to neutral ang current.. ok lng po b na ang stranded wire n gagamitin ko ay ms payt ung wire pra sa sa neutral. Kunwari sa 0.5hp n aircon ay 3.5 sa live tpos sa neutral ms payt na.
    Tnx.

  • @jurysworld2830
    @jurysworld2830 4 ปีที่แล้ว +1

    sir salamat kahit papaano nadaragdagan idea ko,,,

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat din po sir

  • @galaxyunicorn6170
    @galaxyunicorn6170 22 ชั่วโมงที่ผ่านมา

    Boss papaano pag dalawa o tatlo ang aircon pwede ba iyon sa isang linya lang. salamat

  • @muckoyr
    @muckoyr 4 หลายเดือนก่อน

    Sir pwede po ba mas malaking capacity ng indor breaker sa 2.HP mero po kasi ako 40 amp

  • @emherzoncruz8716
    @emherzoncruz8716 หลายเดือนก่อน

    Sir pwede ask ano Ang need gawin sa Aircon na automatic Ang line supply if may energy na Ang line then auto off kung generator Ang gamit

  • @regietangente5073
    @regietangente5073 3 ปีที่แล้ว

    Thanks po sa video sir. Matanong ko lang po kung anong tamang breaker at number ng wire para sa 1hp na aircon interver type? Salamat po

  • @arjaydentenatividad5813
    @arjaydentenatividad5813 3 ปีที่แล้ว

    Gud pm sir tanong ko lng po kong ok lng po ba na my sarili din na 20amp na braker ang refrigerator.salamat

  • @jimboynuer5898
    @jimboynuer5898 4 หลายเดือนก่อน

    Idol may tanong po ako, yung dalawang 1 hp na a.c.u pwede po ba ito iconnect sa 40 amp na CB?

  • @alexanderagena2689
    @alexanderagena2689 3 ปีที่แล้ว

    Un bang AC at heater panel ay pwedi pgsamahin s isng 20A breacker

  • @sakalemstv897
    @sakalemstv897 2 ปีที่แล้ว

    master slamat sa idea mlaking tulong po
    sa kgaya ko

  • @toraldearnie
    @toraldearnie ปีที่แล้ว

    newbie po aq balak q magpakabit ng 1hp at 2.5hp s bahay q pwd bang combine q nlng ung Amps nung dawala para isang wire nlng ung papagapangin q papuntang outdoor unit ? or need q talaga pag hiwalayin supply nung dalwang AC?

  • @johnjuridico1564
    @johnjuridico1564 4 ปีที่แล้ว

    Meron akong 5 washing machines sa laundry shop. Need ba isa isa ang circuit breaker bwat machines?. rated 15a ang isang washing machine.. ano po recomendation nyo sir?

  • @ramgenreyes9571
    @ramgenreyes9571 3 ปีที่แล้ว

    Thanks for sharing this video master Jun.

  • @chestercastillo488
    @chestercastillo488 4 ปีที่แล้ว +1

    S .5HP pwede nb #12 wire at 20amp n breaker sir?

  • @awengz1119
    @awengz1119 3 ปีที่แล้ว

    Sir, tanong lan po, pwede po ba 2 ac, 1hp and 2hp split type inverter sa wire #10? Parehas po na may cb na. Thanks in advance po.

  • @mecoulyssescumpio9145
    @mecoulyssescumpio9145 ปีที่แล้ว

    Good day sir!! Yung 175 na de rating is para sa kahit na Anong klassing motor or pra lang sa ACU? At Yung 125% is Ganon din Po ba??
    Yung dalawa na Yan Po ay same need computation for three phase also??or for single phase lang?? Ty

  • @jennifermarfori6491
    @jennifermarfori6491 2 ปีที่แล้ว

    Sir pag 1.5hp ano pede size ng wire pede gamitin at sa breaker pede 30ampirs

  • @RandyCarandang-p9q
    @RandyCarandang-p9q 11 หลายเดือนก่อน

    Sir pag 7units ng 5toner aircon ilang ampers ang kanyang main circuit breaker

  • @girlierasay2380
    @girlierasay2380 3 ปีที่แล้ว

    Pwede rin ba master ung 5.5 stranded sa 20 amperes para sa aircon

  • @boywakalipz7924
    @boywakalipz7924 4 ปีที่แล้ว

    hi po ask lng po ilang amps.. po ba na breaker ang dapat na gamitin sa 0.6hp na AC.

  • @takemitchihanagaki5094
    @takemitchihanagaki5094 2 ปีที่แล้ว

    Sir question, ito din po ba ang ginagamit na formula sa ibang ACU na may mas mataas at mababang HP?

  • @jesterabenales9499
    @jesterabenales9499 4 ปีที่แล้ว

    Tenk you beri match po nice explanation. God bless. Po

  • @alexsup5237
    @alexsup5237 3 ปีที่แล้ว

    Sir dun sa 3/4hp window aircon puedeng 15a ang breaker at pdx solid wire 3.5mm

  • @nordz109
    @nordz109 4 ปีที่แล้ว

    Sir pwd po ba pagsamahin ang outlet sa isang breaker ang ref. Aircon, washing machine at ano po ba ang need na wire at Ampheres ng circuit breaker?

  • @opecons
    @opecons 3 ปีที่แล้ว

    Sir. Hindi maaari kalimutan yung 746 watts kasi yun ang equivalent ng 1hp, yun ang basic calculation ng motor. Kun palalimin mo ang calculation dyan nanggaling ang flc or fla na 10A ng 1.5 hp.

  • @crissclaud570
    @crissclaud570 3 ปีที่แล้ว

    Sir pwede na.po ba 30ampers ang circuit breaker tapos dalawang 1.5 hp na aircon at isang 1.5 hp na water pump .tapos ang wire na gagamitin ko duplex number10 ang main at..at galing sa mga motor na wire ang gagamitin ko duplex number12 na wire un ang idugtong ko sa main na duplex number10

  • @ridzkanrazid2996
    @ridzkanrazid2996 4 ปีที่แล้ว +1

    sir ask ko lng ilan ampers ng at size ng wire para sa .5 hp na aircon?
    salamat sa sasagot

  • @mannyartates9952
    @mannyartates9952 4 ปีที่แล้ว

    So suitable po ba 1hp aircon sa wire na thhn number 12 or 3.5mm po?

  • @iyabelsie806
    @iyabelsie806 3 ปีที่แล้ว

    Sir sa 0.5hp na window type aircon anng wire ang tamang gamitin? Salamat

  • @MarvinsansanCalope
    @MarvinsansanCalope 8 หลายเดือนก่อน

    Good pm Po sir.swak na Po Ang ac ko 1.5hp gmit ko na breaker is 30 at Ang wire ko Po sir #10 or 5.5 pra sa outlet na ac.

  • @eljiegasis7774
    @eljiegasis7774 4 ปีที่แล้ว

    Pede rin naman po sir ang 1.5hp sa 5.5mm 30amps??
    Galing niyo sir salamat sa mga turo

  • @inuyasha3382
    @inuyasha3382 3 ปีที่แล้ว

    Ano naman ang ang flc sir sa 2hp,or 5hp 10 ampere parin ba.

  • @analynibrahim8667
    @analynibrahim8667 5 หลายเดือนก่อน

    hi po help po pag 0.6hp anong wire at breaker amp need ko ty? nabili ko kc na breaker 20a w/ outlet sa dulo ng breaker

  • @agustinolmos7862
    @agustinolmos7862 3 ปีที่แล้ว

    Boss tanong ko lang kung yang cb ay for each aircon,,isang cb bawat aircon na 1.5 hp?