Oil Burner Primary Control and CAD Cell Operation and Troubleshooting!

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 มิ.ย. 2024
  • In this HVAC Training Video, I show How the Oil Burner Works, How the Cadmium Sulfide Flame Detector (CAD Cell) Works, and How the Oil Primary Control (R8184 Protectorelay) Works. I go over the Electrical Troubleshooting with a Multimeter Reading Resistance Ohms and AC Voltage to Measure if the Components are Bad, Intermittently Working, or Functioning Properly. Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    Tools Used In The Video
    UEI DL479 Multimeter With Temp Sensor amzn.to/2jtsUbJ
    Magnet Jumpers- amzn.to/2PyKPQZ
    Alligator Jumpers- amzn.to/2PxqJXn
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos/Articles
    • Gas Furnace Burner Tra...
    • Oil Burner Ignition Tr...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicetech.com/store
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
    Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicetech.com/hvac-ca...
    Our Newest Articles: www.acservicetech.com/articles
    Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
    Our Other Resources: www.acservicetech.com/resources
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicetech.com/tools
    Our Tool List on Amazon: www.amazon.com/shop/acservice...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtools.com/?aff=8
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.com/show/74KXLz5...
    Apple Podcasts: podcasts.apple.com/us/podcast...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided. ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #oil #oilburner #burner #troubleshooting
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

ความคิดเห็น • 150

  • @acservicetechchannel
    @acservicetechchannel  4 ปีที่แล้ว +4

    The E-Book, Paperback and Quick Cards: www.acservicetech.com/store
    The Paperback, Quick Cards at Amazon: www.amazon.com/shop/acservicetech
    Support the Channel- www.patreon.com/acservicetech
    Tool List- www.amazon.com/shop/acservicetech
    Related Video:
    Oil Burner Ignition Transformer and Electrode Troubleshooting!
    th-cam.com/video/Ci6bygNHgzQ/w-d-xo.html
    Tools I Use Are Linked Below!
    Leak Detection:
    Accutrak VPE Ultrasonic Leak Detector amzn.to/2nFYKVe
    Accutrak VPE-GN Ultrasonic Leak Detector amzn.to/2Zy4IZP
    RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn
    Vacuum Tools:
    JB 6 CFM Vacuum Pump - amzn.to/2nqbvo8
    CPS 4 CFM Vacuum Pump - amzn.to/2DxgPwY
    Appion Valve Core Removal Tool - amzn.to/2uYr8WL
    Appion Blue 3/8" to 1/4" Vacuum Hose - amzn.to/2uYlVyc
    Appion Red 3/8" to 1/4" Vacuum Hose - amzn.to/2uYg6Ro
    Yellow Jacket 1/4" by 1/4" 3’ hose - amzn.to/2umtcod
    Appion 1/4" by 1/4" and 3/8” hose - amzn.to/2Zyxzx9
    Uniweld 1/4" by 1/4" 2’ hose - amzn.to/2GFov1Y
    CPS Vacuum Micron Gauge - amzn.to/2v1nM3O
    Supco Vacuum Micron Gauge - amzn.to/2v1JRiA
    JB Vacuum Pump Oil - amzn.to/2mGrlXy
    Checking the Charge:
    Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq
    Refrigerant hoses with valves amzn.to/2aBumVI
    Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9
    Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq
    Digital Refrigerant Scale amzn.to/2b9oXYl
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Fieldpiece SMAN380 Digital Manifold Set amzn.to/3297zse
    Fieldpiece SMAN480 Digital Manifold Set amzn.to/337mGnq
    Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8
    QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg
    RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
    Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3
    Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs
    Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw
    Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ
    Flaring Tools:
    Yellow Jacket Flaring Tool - amzn.to/2OBxGlM
    Spin Flaring Bits 1/4", 3/8", 1/2", 5/8", 3/4"- amzn.to/31BCs8Z
    Yellow Jacket Flaring Tool with Set Depth - amzn.to/2QIKsQH
    Yellow Jacket Torque Wrench - amzn.to/2NRR68Q
    Uniweld Swage and Flare Kit- amzn.to/2T55jyn
    Nylog - amzn.to/2MLJcch
    Ridgid Tubing Cutter - amzn.to/2DnjjR1
    Wolverine Tube Reamer - amzn.to/2QGLyMV
    Swaging Tools:
    Manual Copper Tube Swage/Expander- amzn.to/2WRPa1M
    Spin Swaging Bits 1/4" to 7/8" for the Drill- amzn.to/2YQwwqS
    Uniweld Hydraulic Swaging Tool- amzn.to/2MlrI8m
    Uniweld Swage and Flare Kit- amzn.to/2T55jyn
    Uniweld Hammer Swage kit- amzn.to/2CzWMMU
    Uniweld 3/4" Hammer Swage- amzn.to/2CzXsSs
    Uniweld 7/8" Hammer Swage- amzn.to/2Mja5WE
    Uniweld Multi-Size Hammer Swage- amzn.to/2T3Cx1b
    Brazing Tools:
    Air Acetylene Torch setup - amzn.to/2aQalsb
    15% Silver Brazing Rods - amzn.to/2gVLyLc
    Uniweld Cap-N-Hook and #2 Tip Oxy Acetylene Torch Setup - amzn.to/2STp3Fe
    Ameriflame Oxy Acetylene Torch Setup #1  Tip - amzn.to/2SRm3JF
    #2 Tip for Oxy Acetylene Torch - amzn.to/2SPDaeD
    Cap-N-Hook Tip for Oxy Acetylene Setup - amzn.to/2MbhpUk
    40cu B Tank to 10cu MC Tank Acetylene Tank Fitting - amzn.to/2GxZZPi
    Nitrogen Regulator - amzn.to/2bXdR5f
    Uniweld NitroVue Flow Regulator - amzn.to/2GnsaAo
    Uniweld Nitrogen Flow Meter - amzn.to/2brvoBg
    Bernzomatic Trigger Start Lighter Propane/Mapp Gas - amzn.to/2vit0cv
    Uniweld Soft Flame Sweating Torch Setup for Acetylene - amzn.to/2DyzRD8
    Flint Spark Ignitor - amzn.to/2L3P2u9
    Stay Brite #8 Silver Bearing Solder and Flux - amzn.to/2XIDJsY
    Aluminum Braze Rods - amzn.to/2IGNMu
    Electrical Diagnosis Tools:
    UEI DL389 Multimeter amzn.to/2xAdaJf
    UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ
    Magnet Jumpers- amzn.to/2PyKPQZ
    Alligator Jumpers- amzn.to/2PxqJXn
    Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V
    Nitrogen:
    Uniweld NitroVue Flow Regulator- amzn.to/2GnsaAo
    Uniweld Nitrogen Flow Meter amzn.to/2brvoBg
    Nitrogen Regulator amzn.to/2bXdR5f
    Service Valve & Port Access:
    RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn
    25 Valve Cores - amzn.to/2L37UJU
    25 ¼” Brass Port Caps with rubber O-rings - amzn.to/2GIOdD2
    Brass Valve Core Tool which holds 3 valve cores - amzn.to/2GFEbm2
    Valve Core Torque Wrench - amzn.to/2GHiLoD
    Locking Cap Universal Lock/Unlock Tool - amzn.to/2GGAoVp
    Locking caps - amzn.to/2GFXZ8A
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Yellow Jacket Sealright 90 Coupler- amzn.to/2LsU1V7
    Yellow Jacket 1pk Compact Ball Valve- amzn.to/2uXdF18
    Yellow Jacket 3pk Compact Ball Valve- amzn.to/2AiKfQe
    Thumb Screw Valve Core Depressor with Backseat- amzn.to/2mR0sCL
    Other tool links can be found in the video description section.
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech

  • @Parabellum-X
    @Parabellum-X ปีที่แล้ว +11

    Go figure!
    I'm in school for HVACR right now, and I'm in the middle of learning about furnaces, boilers, etc. I go to search TH-cam for an Oil Furnace video, and lo and behold, Craig is at it again! 😆 You never cease to amaze me, bud. You're the best!
    Keep up the good work!

  • @stephenzies8867
    @stephenzies8867 2 ปีที่แล้ว +7

    You Are A Great Teacher Thank You For Your Time

  • @ranckie
    @ranckie 2 ปีที่แล้ว +4

    Excellent video and very well explained. The world needs more You Tube videos like yours.

  • @chrisgormley5751
    @chrisgormley5751 4 ปีที่แล้ว +10

    I work on a lot of oil burners in New Jersey. This was very informative. Thank you for doing this.

  • @bodyshop8008
    @bodyshop8008 3 ปีที่แล้ว +4

    EXCELLENT Tutorial, Great job explaining to the common folk! I never knew these assemblies were so simple.

  • @amazincrackmonkey7176
    @amazincrackmonkey7176 2 ปีที่แล้ว +1

    This helped me so much I've never worked on a heater before, this guide answered my problems.

  • @bkoz319
    @bkoz319 4 ปีที่แล้ว +4

    Cant wait the the OIL BURNER SERVICE book!!!

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว +1

      Ha ha, there will be other books before that one comes out i think. It all takes time, thanks!

  • @simeonhappel5182
    @simeonhappel5182 3 ปีที่แล้ว

    Terrific instructional video! You have a gift for teaching and dictation.

  • @jimbola77
    @jimbola77 4 ปีที่แล้ว +1

    wow, interesting there partner first time I even heard of this oil burner, thank you for sharing! I hope you had a wonderful Christmas.

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว

      Yes Christmas was very nice and I spent a lot of time with the family. I hope you got to spend time with family and had a nice Christmas! Thanks Jimbola77!

  • @marcom.9425
    @marcom.9425 2 ปีที่แล้ว

    Very helpful and informative. Thanks for the great videos!

  • @dagestanifive
    @dagestanifive 7 หลายเดือนก่อน

    Extremely good information here. Thank you.

  • @eman3208
    @eman3208 4 ปีที่แล้ว

    Thanks for always showing such good videos!!

  • @irishmike4914
    @irishmike4914 2 ปีที่แล้ว +2

    First off I really like your videos, very informative.
    Never forget to clean the end cone! So many plumbers put 80 hollows in everything and it gets coked up blocking the flame. Sometimes 2 minutes with a 7/16 can save a lot of trouble shooting. Keep up the great videos!

    • @irishmike4914
      @irishmike4914 2 ปีที่แล้ว

      @nothingtoseehere Sorry but we oil guys are just drunks.......until AC season lol

    • @irishmike4914
      @irishmike4914 2 ปีที่แล้ว

      @nothingtoseehere you don't have to do it all at once. Baby steps. I have faith lol. What area are you from. I'm in nj and my old service manager called me yesterday. He is pretty desperate for bodies. Just a thought

    • @irishmike4914
      @irishmike4914 2 ปีที่แล้ว

      @nothingtoseehere Not a problem. You would be surprised how hard it is to find someone with a head on there shoulders that is willing to get dirty. Remember with oil, especially up there where it's colder, your vacuum gauge is your friend!

  • @Silverado1st
    @Silverado1st 4 ปีที่แล้ว +4

    Great video, tons of important info and hands on. I'm a retired vet now, ex-mechanic, electrician, engineer, construction worker and such, so love to do all my own repairs and maintenance. Got this 20yr old (according to the maintenance sheet on the wall) Wayne oil furnace I've been trying to troubleshoot and this is the most in depth video I could find. Needed info about the cad cell readings on the multi-meter for a go and no go answer. Thank you for the valuable information, from a grateful veteran.

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว +4

      Glad to help and thank you very much for serving our country!

    • @Silverado1st
      @Silverado1st 4 ปีที่แล้ว

      @@acservicetechchannel Appreciate that very much :-)

  • @williamswan7779
    @williamswan7779 4 ปีที่แล้ว +1

    Awesome description and video ,thanks.

  • @RineboBohead
    @RineboBohead 4 ปีที่แล้ว

    Thank you again for helping me advance in my knowledge!

  •  4 ปีที่แล้ว

    Excelente explicación, muchas gracias.

  • @kenshinpa
    @kenshinpa 3 ปีที่แล้ว

    Thank you. I was able to diagnose why my new honeywell wouldn't start and it was because I didn't connect the two screws with a wire lol. Thank you for the explanation!

  • @brianmcdermott1718
    @brianmcdermott1718 4 ปีที่แล้ว +2

    Great info. Thanks. Great teacher too.

  • @kevinkevin9448
    @kevinkevin9448 4 ปีที่แล้ว

    Nice video please continue the bench testing of equipment

  • @watermanone7567
    @watermanone7567 4 ปีที่แล้ว +1

    Nice job. Please keep up the great video's.

  • @concretecurt
    @concretecurt 2 ปีที่แล้ว

    Awesome information, Thanks

  • @Pretzel114
    @Pretzel114 4 ปีที่แล้ว +1

    Nice vid Craig. Thanks.

  • @Attest411
    @Attest411 3 ปีที่แล้ว

    More oil!! I’m new and I know very little about oil. Steve L and Gray do a great job. But more material is always better.

  • @rodgraff1782
    @rodgraff1782 ปีที่แล้ว +1

    Great video. Worked on hundreds of these. I didn’t like those solid state transformers. Always used the old style.

  • @jashua2089
    @jashua2089 2 ปีที่แล้ว

    Please make more videos like this.

  • @Xbreaselx
    @Xbreaselx 4 ปีที่แล้ว

    Great video

  • @beephoon7489
    @beephoon7489 3 ปีที่แล้ว

    I love watching your video. Very well explained and very informative. Can you please show more video on troubleshooting oil furnace..Also can you show how to install honeywell primary control modelR72841004

  • @markk4409
    @markk4409 2 ปีที่แล้ว

    Thank you for an excellent explanation. 1.1 kOhms or 1100 Ohms, but not 1100 kOhms as you state.

  • @BrewCityRider
    @BrewCityRider 2 ปีที่แล้ว

    Very helpful information. When did the Beckett oil burners begin using the oil pump solenoids?

  • @vernwhite568
    @vernwhite568 ปีที่แล้ว

    We still the old system and still works great lost the mother board inside the flame control box but its
    Common the box was almost 9 years old I work on my own furnace and have been since I was 14 never have ever had a problem

  • @danielmanziuc8244
    @danielmanziuc8244 3 ปีที่แล้ว

    👍 thumb up for the video and effort to explain!
    shoot! If I'd have watched this I wouldn't have to go to skool to learn all this!
    Are you sure step-up tranny is20KV output not just 10K? If I remember correctly, gas appliances uses higher than oil kv output to ignite fuel; Inwork mostly on commercial oil burners where transformers are just 6Kv output .
    They were 10kv but came out few yrs back with just 6kv output .
    Becket have 10 or 15kv if I am not mistaken!
    But hey, you r the hero here, spending time showing something I had to pay for!
    Much appreciated!

  • @gilbertfaulk4748
    @gilbertfaulk4748 6 หลายเดือนก่อน

    Wow good info

  • @aliso-pv7ll
    @aliso-pv7ll 4 ปีที่แล้ว

    Craig, Would you do a short video on a 30lbs. cylinder as to how many cubic inches(volume) are the industry standard for the cylinder, and what does the empty cylinder weight? As always thanks for your fine teaches on your videos.

  • @xtremecomfort7799
    @xtremecomfort7799 4 ปีที่แล้ว +1

    Thanks!!!!!

  • @kemonbannister3405
    @kemonbannister3405 2 ปีที่แล้ว

    Thank you for the valuable information, I didn’t know anything about oil furnaces. Where can I fine the order of operation for oil furnace? Like how I would fine with gas furnace?

  • @fishsquishguy1833
    @fishsquishguy1833 3 ปีที่แล้ว +1

    Great video! Ever think of doing a Beckett with the Genisys primary controller?

  • @stanleym2679
    @stanleym2679 3 ปีที่แล้ว +1

    Great video,have a mobile home had problems with furnace from repairman worked on it, have some experience with furnaces,( I am a home owner) rebuilt furnace,reset electrodes ,put in new nozzle and adjusted it,and new pump, everything runs good,with cold weather upon us turned thermostat 2 wire to 68-69 furnace runs and after cycle shuts off and about 1/2 when room cools down comes on again and heat good,Now when turning up thermostat to 70-71 the furnace runs heats up rooms ,shuts down but then comes right back on in about 15-20 minutes ,all the time ,turn it back down and it run like before ,Question is this normal or is it in thermostat or primary unit, appreciate the help

  • @99shadows66
    @99shadows66 ปีที่แล้ว

    Hi, I am curious, if the aquastat has a bad relay will it trip the red reset button on the oil burner? Thank you for posting these educational videos.

  • @oilburner9989
    @oilburner9989 3 ปีที่แล้ว +1

    Oil spays into the chamber, not the heat exchanger.

  • @CL-ty6wp
    @CL-ty6wp 2 ปีที่แล้ว

    spewinng oil would be into the combustion chamber. But that sort of is part of the exchanger in a sense.

  • @mattfoley6082
    @mattfoley6082 ปีที่แล้ว

    How to decide which new primary to buy? The ones with displays and diagnostic codes are actually less expensive!
    How to decide which lockout time to use: 15 seconds or 30 seconds or 45 seconds?

  • @coreym3762
    @coreym3762 4 ปีที่แล้ว

    Just ordered your book and cards. I've been doing HVAC for a year now. But this my first winter and I still have a lot to learn on electric heat strips, sequencers, etc. I understand most of it but I still find myself running into older units that look different and sometimes it just looks like a big pile of wires going everywhere lol is there any way yall can do a video on older or more complex electric heat strips?

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว

      Thanks for your purchase and please let me know what you think of the book after reading it! Thanks for letting me know what you would like to see. So far, i did do one video on how older heat strips work. th-cam.com/video/7_-x6u9uzhU/w-d-xo.html

  • @marks291
    @marks291 ปีที่แล้ว

    Hello, I've recently picked up a Nest thermostat and need to use one of their Nest Power Connectors to my furnace, i have the Becket burner and Honeywell as in your video, but I don't know where to insert the Nest Power Connector.

  • @dootz79
    @dootz79 2 ปีที่แล้ว +1

    How would one wire this unit with a fancier thermostat to allow just the blower to run when heat was wanted ?

  • @stanleym2679
    @stanleym2679 3 ปีที่แล้ว

    Question,just redone my furnace in our mobile home,new nozzle ,electrodes and fuel pump and set correctly,everything runs great, Q,how long should it be between time furnace stops and blower comes on

  • @enzoamore9173
    @enzoamore9173 4 ปีที่แล้ว

    Can you do a video presentation on Carlin retro fit gas burners

  • @BoriPR82
    @BoriPR82 4 หลายเดือนก่อน

    My furnace is only 2 years old, the cad is clean. My burner turns on for 30 seconds and then it turns off. Then white smoke comes out of the burner.

  • @mattfoley6082
    @mattfoley6082 2 ปีที่แล้ว

    My burner would run for a minute then shut off. Good oil flow, good flame. Weird. Cad cell was clean. I was about to bypass the cad cell and noticed its screw terminals on the controller were loose. Tightened them and burner is running.
    Whew, very relieved. I guess they got loose from the motor vibration.

  • @09fatbobmike
    @09fatbobmike 2 ปีที่แล้ว

    I'm only seeing ohms when I shine light on cad cell. Other than that is nothing. Which is just a 1 on my screen
    And when it saw light the reading went from 1900 on down. Direct light took it down low enough to beep

  • @stanleym2679
    @stanleym2679 3 ปีที่แล้ว

    Question,just got done installing new nozzle, electrodes and pump, furnace runs great, and blow nice hot air( not like before) but now it seem it dose not kick in as often as before when temp drops in room but it dose come on ,is this a calibration issue or is because it’s blowing hot air and takes more time to cool down for thermastat

  • @kimberHD45
    @kimberHD45 4 ปีที่แล้ว +1

    Thanks for all your awesome training videos! I would like to know if you have a preferred wire termination method for high amperage incoming field wiring to the electric furnace. Say for like stranded #4/2 w G AWG or #6/2 w G AWG, do you use heavy duty barrel crimpers or split bolts?

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว +1

      I prefer split bolts but often you can get them directly into the lugs depending on the size, thanks

    • @kimberHD45
      @kimberHD45 4 ปีที่แล้ว

      AC Service Tech LLC thank you

  • @carmelpule6954
    @carmelpule6954 2 ปีที่แล้ว

    At 5:48 he says that " ........It is reading, one point one, kilo-ohms, so eleven hundred kilo ohms while it is running,.........."
    The first part should be," .......it is reading one point one, mega-ohms so eleven hundred kilo ohms..................."
    Also at 9:39, he says that the orange wire is sending 120 volts to the three wires, the motor, the transformer, and the
    solenoid...."
    Logically speaking the solenoid controlling the fuel valve should have a slight delay with respect to the motor start, so that the fuel pump would have reached the highest pressure and it will spray well rather than dribble during the transient of the start of the motor. when the pump is not producing its highest set pressure.
    Switching off the motor and the fuel valve at the same time is fine, as the fuel will be cut off and no dribbling takes place during the slowing down transient when the pump is not producing its highest set pressure.

  • @stumpynubs5387
    @stumpynubs5387 หลายเดือนก่อน

    When replacing the 7505 is it plug and play or do you have to program it?

  • @jacobsouthers9162
    @jacobsouthers9162 4 ปีที่แล้ว

    Hello I have a Beckett oil furnace that fires and shuts off after time out ! I’ve changed the filter and checked the cad cell with no luck , any thoughts ?

  • @SaltMinerOU812
    @SaltMinerOU812 7 วันที่ผ่านมา

    I have a question One of my igniters porcelain has a crack the length of it could that be a problem? And maybe why it's cycling over and over?

  • @stanleym2679
    @stanleym2679 3 ปีที่แล้ว

    Great video helps a lot,I just replaced pump and coupling ,new electrodes, and nozzle,heats and run nice ,question, when thermostat,( 2 wire manual) is set at say 65 and furnace runs ,after shut down it seems to get cooler in mobile home before furnace kicks on again ,is that in some kind of calibration

  • @alexmetz3493
    @alexmetz3493 2 ปีที่แล้ว

    I have a Beckett af11 in my shop on a radiant tube. Been using it for 8 years but have a issue with the post time cutout. It’s set for 4 min but only runs 15 secs after thermostat stops calling for heat. Any ideas?

  • @wiremonkeyshop
    @wiremonkeyshop ปีที่แล้ว

    I have the same Beckett/Honeywell setup. Solid red light. CAD cell is within limits, when red reset button is pressed, the fan/pump/transformer does not come on. Reset button will not stay down. 120V coming off orange wire. Should I be suspecting that the Honeywell unit is bad? Or start thinking that one of the 3 things that are being fed power (fan/pump motor, transformer or solenoid) bad?

  • @zekenzy6486
    @zekenzy6486 4 ปีที่แล้ว +1

    Great video and detail Oil Burner . Thank you for sharing ^_^. I want to ask you something, what's different between expensive and cheaper price Multi meter ? I'm on a market for buy first Multimeter. Thank you.

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว

      The UEI meters I use are True RMS so they are usefull for measuring things like dc micro amps. You don't need an expensive meter but one that includes capacitance. The DL 479 and higher would work. I used to use the DL389 and that worked very well too. I use the ST4 for single and dual temp readings. I have the tools i use linked at www.amazon.com/shop/acservicetech thanks!

  • @captainobvious5993
    @captainobvious5993 3 ปีที่แล้ว

    What if you turn your thermostat on but your furnace does not respond. I have to reset the furnace to get it to turn on. It won't kick on automatically when the temperature drops below what I set it on.

  • @jimmyjean6663
    @jimmyjean6663 3 ปีที่แล้ว

    Help me please. I have a hallmark oil furnace, soon I'm going to install Evap coil on top of it the AC. I want to know how the low volt wire has to be wired. Oil has a transformer on it with R, C, W, G, Y. And the T-stat has only 2 wire into it. Can you help me with the wire when it's calling Ac for the fan and the condenser to kick on please?

  • @apisglider9
    @apisglider9 ปีที่แล้ว

    I can't find any information on this but it seems like from your video I need to jump tt on an 8184g even with a triple aquastat so the safety switch functions. Is that correct? Thanks

  • @tedrose8894
    @tedrose8894 4 ปีที่แล้ว

    Do you still use the 8184G? I prefer the 7284U for several reasons. Do you have any thoughts regarding the 7284U?

  • @robertdecker146
    @robertdecker146 2 ปีที่แล้ว

    On my newly installed "Oil primary control", the red-button won't stay clicked down. It keeps popping back up. And obviously, the heater shuts right off. It does this within seconds lately. Wondering what it could be. Can't seem to get ahold of the person who recently installed the "Oil Primary Control".

  • @ahamilton1544
    @ahamilton1544 7 หลายเดือนก่อน

    Hi. Do can cad cells still function but be less efficient when they get old? My furnace runs if I shine a flashlight on the cell, but the furnace locks out when installed.

  • @lump42104
    @lump42104 2 ปีที่แล้ว

    Help my oil furnace is not staying lite the flame turns on and off like its cycling if I turn thermostat up way high it stays lite for a bit longer bit only for a short time then back to on and off

  • @lordtickles1478
    @lordtickles1478 5 หลายเดือนก่อน

    I know this video is older but hope you see this.i have the same set up. But my furnace fires on and off rapidly. I replaced the cad sensor. Wanted to test it so I hooked up an external one and while the furnace is running I shine a flashlight on the sensor and it turns off thr furnace? Also if if I disconnect the sensor the furnace runs fine till it trips. Any ideas?

  • @albertpavone4840
    @albertpavone4840 4 หลายเดือนก่อน

    Beckett oil primary control

  • @kyledennis1802
    @kyledennis1802 5 หลายเดือนก่อน

    So i have an older version of the burner abkne. The reset butten is pressed in, but the burner will not light. The cad sensor is testing OL. Im not getting any voltage through the switch either. Any ideas?
    It was working just fine 3 days. So i thought it ran out of fuel, but we put some more in and it is not even attempting to light to let me bleed the system

  • @MrSte553
    @MrSte553 4 ปีที่แล้ว +2

    I have heard that the transformer sends 10k volts to the spark igniter. Is it 20k? Are not all oil furnace transformers the same? Also what happens if you put in the wrong size nozzle in an oil furnace?

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว +1

      The older wound transformers are usually 10,000 to 12,000 volts and these electronic transformers have a peak voltage rating of 20,000 to try to help with full ignition of the oil. The nozzle size has to do with gpm flow which has to due with how many BTU/hr is needed for the furnace. You want to make sure to not overfire a furnace especially a forced air furnace since it needs to maintain a supply temp while the blower rejects the heat into the building, thanks!

  • @greg6264
    @greg6264 3 ปีที่แล้ว

    I've got 118v in, but no power coming out. What are possible causes? CAD cell is good.

  • @dezdon01
    @dezdon01 3 ปีที่แล้ว

    This morning there was a chill in my house. I woke up to an “erratic buzzing” sound coming from the oil furnace. It was not running, but I believe calling for heat. I could feel a vibration that was in sync with the noise coming from the plastic box of the control unit when I placed my fingers on it.
    I shut the power off to the unit and checked all the wiring, oil supply tank and opened up my Honeywell control box, same as featured in the video, nothing was discovered out of sorts. The coil inside the control box with the contact set looked fine and floated as freely in place.
    I cleaned the contacts and reassembled everything and the same erratic buzzing continued.
    The electric motor spins freely, the igniter and CAD cell are less then a year old.
    Has the control unit gone bad? This would be a $110 “guess” to just try a new control unit. How could I verify its failed or what else could the problem be? Thank you and EXCELLENT video!!

    • @CL-ty6wp
      @CL-ty6wp 2 ปีที่แล้ว

      Cap or contacts in motor are bad. Cad relay can stick, and tapping or flipping over might get it to work.

    • @dezdon01
      @dezdon01 2 ปีที่แล้ว

      @@CL-ty6wp The CAD went bad. I happened to have an old one laying around and tried it just for shits and giggles. I’ve never had one act like that before.

  • @jennyjunebugg
    @jennyjunebugg 4 ปีที่แล้ว

    have oil furnace t
    That keeps blowing cad cells

  • @hollywinsman9464
    @hollywinsman9464 2 ปีที่แล้ว

    Craig, do you prefer Beckett or Riello?

  • @hook9line5sinker94
    @hook9line5sinker94 2 ปีที่แล้ว

    Hey thank you for the video! But I need some help! I have a beckett oil burner and I ran out of oil but I just filled it back up with diesel and I usually hit the reset button and bleed the air out.
    But my problem is, the reset button pops up when I turn the heat on, but it won’t send oil through the lines and won’t try to start up, it just makes a buzzing sound when I hit it, and then once it goes through the cycle it pops back up.
    What is going on?

  • @x.y.8581
    @x.y.8581 3 ปีที่แล้ว

    Can't use the reset button - it is non functional - whats wrong; how can I reset it so it will work again?

  • @TheMagpyeTrader
    @TheMagpyeTrader 2 ปีที่แล้ว

    Just to confirm, I should be getting some resistance even if the CAD cell is in total darkness correct? If not it's busted right?

    • @carmelpule6954
      @carmelpule6954 2 ปีที่แล้ว

      MontyKensicle, You should be getting between 1 and 2 mega-ohms in total darkness, so it is not " getting some resistance", but a lot of resistance.

  • @kyleh1974
    @kyleh1974 4 ปีที่แล้ว +1

    I've never seen a solenoid with that primary control. Do you just wire the solenoid in series with the transformer?

  • @bigpardner
    @bigpardner 3 ปีที่แล้ว

    At 3:17 you illustrate that you removed one of the yellow CAD cell wires from the control. Which wire? Does it make any difference? Also, I am trying to figure if a CAD cell malfuction can be dangerous. Right now I'm thinking if the cell always reads high and does not respond to light the worst thing that can happen is the burner will turn off after so many seconds thinking that there has been no ignition. If the cell reads too low the burner won't start. Both non-working conditions but not dangerous.

    • @CL-ty6wp
      @CL-ty6wp 2 ปีที่แล้ว

      no difference and correct on sensor function.

    • @irishmike4914
      @irishmike4914 2 ปีที่แล้ว

      All the yellows due is read resistance (ohms) not powered

  • @pauliekruger7639
    @pauliekruger7639 3 ปีที่แล้ว

    Great presentation, the thing i was searching for is why is my furnace was cutting out the safety button. It fires, but Knowing the ohms is relevant but in my case when you said or something causing it to trip or cut is the real problem. So my question is the cause rather than light, or flame out, or light seeping in thru a loose box hole, or crack, " poor flame", or lots of smoke. A dirty chamber or obstructed vent. Is this true? will a high ohms condition due to smoke cut the unit out? Thank You.

    • @pauliekruger7639
      @pauliekruger7639 2 ปีที่แล้ว

      A year later and i am not sure why I would patronize your channel...?

    • @SaltMinerOU812
      @SaltMinerOU812 7 วันที่ผ่านมา

      The guy has a life, he can't answer every damn comment.. not to mention your comment was all gibberish

    • @pauliekruger7639
      @pauliekruger7639 7 วันที่ผ่านมา

      @@SaltMinerOU812 get real. It's what should be done on here fool.

    • @pauliekruger7639
      @pauliekruger7639 4 วันที่ผ่านมา

      @@SaltMinerOU812 Did you get a basic education? It seems you are tender.

    • @SaltMinerOU812
      @SaltMinerOU812 4 วันที่ผ่านมา

      @@pauliekruger7639 after reading your comment, that's some good projection there buckwheat

  • @subigirlawd_7307
    @subigirlawd_7307 2 ปีที่แล้ว

    I have a question 🤔 I obviously know nothing about hvac or boilers ect, but I do love electronics and electrical engineering,
    anyway according to your wiring, it seems to have the the electronic transformer that sparks the fuel is always running when the boiler is running, is there a reason?

    • @subigirlawd_7307
      @subigirlawd_7307 2 ปีที่แล้ว

      P.S. my comment was supposed to in a different video you made on how to wire a primary controller, my phone went to the next video,

    • @TheodoreHuckstable-lb1uy
      @TheodoreHuckstable-lb1uy ปีที่แล้ว +1

      When boiler is running it is constantly feeding oil that needs ignition or it'll fill with unburnt oil, make stinky mess😘

    • @subigirlawd_7307
      @subigirlawd_7307 ปีที่แล้ว

      ​@@TheodoreHuckstable-lb1uy aww ok, I was thinking once it sparked it kept lit, I forgot all about this so I never asked about it again.. Interesting Thanks for the reply and a kiss lol 😘

  • @l.a.m7645
    @l.a.m7645 3 ปีที่แล้ว +1

    Can you do a video on White Rogers Zone Valves

  • @Ratman_Bejo
    @Ratman_Bejo 3 ปีที่แล้ว

    how are you sir, greetings my name is Mr Ratman from PT Indira Dwi Mitra wrong
    I am interested in the burner product, do you have a distributor in Indonesia?

  • @robertdecker146
    @robertdecker146 2 ปีที่แล้ว

    If my "Oil primary control" device's red-button keeps popping up, would it be safe for me to sit a long heavy pair of pliers on top of the red-button..?, so it doesn't immediately pop back up after the furnace goes on..?
    When I press it in,it clicks down fine,but then,after I close the furnace door,and turn the locking knob of the furnace door,which keeps the furnace door closed, the red-button pops back up after the furnace runs for a mere 5-10 seconds. It just shuts right down, obviously at that Moment. That's why I'm wondering, if I could just sit those long heavy pliers on top of the red-button..? Would that be an easy hack Fix Solution..? Or would that be too Dangerous and Risky..? 🤔

    • @ranckie
      @ranckie 2 ปีที่แล้ว +1

      Surely, you're joking, but if you aren't, PLEASE READ THIS: DO NOT EVER consider doing that unless you want to risk burning your house down, potentially killing your family in the process. That RED button is telling you that something is WRONG with your boiler, (or oil furnace). If you watched his video, you'd know that he specifically said, DO NOT KEEP PRESSING THAT RED BUTTON DOWN, if it keeps popping back up, it means something is wrong! Go back and watch the video again.

  • @RayRay-nb7tn
    @RayRay-nb7tn 4 ปีที่แล้ว +1

    I didn't see the oil burner electrodes settings in your videos. Would like to see how you set electrodes, burner head, by using the electrodes gauge or gauges.

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว +1

      th-cam.com/video/Ci6bygNHgzQ/w-d-xo.html

    • @RayRay-nb7tn
      @RayRay-nb7tn 4 ปีที่แล้ว

      Thank you sir.

    • @kyleh1974
      @kyleh1974 4 ปีที่แล้ว

      Get a Beckett Z Gauge. Makes this very easy.

  • @johonneng4105
    @johonneng4105 2 ปีที่แล้ว

    My oil furnace one day stopped working, doesn't start. Oil pressure ok. But I changed the oil filter and nozzle. Again oil pressure ok. Again oil furnace doesn't start. Check the spark it's ok. Again oil furnace won't start. Check the peephole to see if I’m getting spark, no spark. Replace the cad cell and transformer. But I get a spark when I took the nozzle/electrode out of the burner head. So I left the peephole open, guess what? The furnace started. This is completely the opposite of what the cad cell does. I double-check the cad cell, high resistance with no light, low resistance with light. Again cad cell is brand new. The oil furnace only starts with the peephole open, then I close the peephole and it runs great, very smooth. But won’t start up the next time the thermostats want heat on. What’s going on???

  • @cesarvargas1758
    @cesarvargas1758 2 ปีที่แล้ว

    I thought you couldn't test ohms with power on?

  • @randymarcell
    @randymarcell 2 ปีที่แล้ว

    I'm a Journeyman HVAC tech working with more gas/electric furnaces over 20 years. The unit does not sense the flame and locks out. I ohmed and cleaned cell. No change. Replaced cell and wire. Same thing. It keeps running only when I wait then jump F-F. It does not attempt to run as expected if I jump first. It seems it is the flame itself. I have a new primary R7284U to replace R8184G. What are your thoughts?

    • @randymarcell
      @randymarcell 2 ปีที่แล้ว

      Looking atthe flame
      th-cam.com/video/KgO96Heecak/w-d-xo.html

    • @CL-ty6wp
      @CL-ty6wp 2 ปีที่แล้ว

      retention head sooted up blocking light? Light on ohms i think should be around 200. I think over 1200 it gets sketchy.

    • @randymarcell
      @randymarcell 2 ปีที่แล้ว

      @@CL-ty6wp Thanks.

  • @franciscocamacho1017
    @franciscocamacho1017 ปีที่แล้ว

    All the parts for my burner are new the cad cell the electros the nozzle holder the controler the transformer and my burner still shuts off after 50 sec what could be the problem?

    • @SaltMinerOU812
      @SaltMinerOU812 7 วันที่ผ่านมา

      Did you ever find out what the problem was? Filter maybe

  • @Two_Buck
    @Two_Buck 3 ปีที่แล้ว

    I have a problem that I think is a bad controller. Sometimes, most times right now, the burner doesnt turn on and then the fan comes on and blows cold air. I can hear that when the thermostat calls for heat I am not hearing the relay in the control click. The reset button is not tripped. If I tap the side of the control, instantly I hear the relay click and the burner fires right up. So, sounds like the relay inside the control is sticking. I am thinking of just replacing the control. Any thoughts from any of you guys out there?

    • @patrickford5409
      @patrickford5409 3 ปีที่แล้ว

      Yea sounds like your control is going bad. The points are probably dirty or worn out. You can open it up and check.

    • @Two_Buck
      @Two_Buck 3 ปีที่แล้ว

      @@patrickford5409 Thanks for the reply. I ending replacing the control and it solved the problem.

    • @CL-ty6wp
      @CL-ty6wp 2 ปีที่แล้ว

      bad relay in the box. Very common symptom and quick fix to get running.

  • @adamk6103
    @adamk6103 ปีที่แล้ว

    Just throw a 7284u primary on and call it a day

  • @paulinomatos259
    @paulinomatos259 4 ปีที่แล้ว +1

    hi i am Paulino matos and i live in new jersey. I've been working around this industry for about 10 years but i want to know how to get a STC Certificate and a 608 EPA Universal license. And also how to get a certificate for plumper. do you guys have like a course i can take so you guys can help me get a certificate and tell me how much it cost. please contact me

    • @acservicetechchannel
      @acservicetechchannel  4 ปีที่แล้ว

      EPA 608 cert is done through epatest.com and escoinst.com through certified testing locations. You can look up the testing locations through their site. You can also buy a epa 608 test prep and test through a local supply house, thanks!

  • @bekaddisontechnologies4292
    @bekaddisontechnologies4292 2 ปีที่แล้ว

    Thank you. But now my head hurts. I'm a CIO in Information technology services. I can't stand working on my boiler nor my cars nor my lawnmowers. You need to charge more money for your Services, but not to the poor, as we do.

    • @intangible0062
      @intangible0062 7 หลายเดือนก่อน

      I am a system engineer for IT and want you to know you are not alone. I have never met a CIO that actually understood technology.

  • @spymaine89
    @spymaine89 4 หลายเดือนก่อน

    lost cant follow............