ECM Multi-Speed Blower Motor Troubleshooting!

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ม.ค. 2025

ความคิดเห็น • 315

  • @acservicetechchannel
    @acservicetechchannel  5 ปีที่แล้ว +8

    The E-Book, Paperback and Quick Cards: www.acservicetech.com/store
    The Paperback, Quick Cards at Amazon: www.amazon.com/shop/acservicetech
    Support the Channel- www.patreon.com/acservicetech
    Tool List- www.amazon.com/shop/acservicetech
    Related Videos:
    ECM Variable Speed Genteq 3.0 Troubleshooting: th-cam.com/video/locNv9WsanA/w-d-xo.html
    Make Your Own ECM Genteq 2.3 Tester: th-cam.com/video/lKsIgjEJDII/w-d-xo.html
    Variable Speed Motor Testing: th-cam.com/video/lO5PArRF9rg/w-d-xo.html
    PSC 120v Motor Testing: th-cam.com/video/flbUtLMeSOQ/w-d-xo.html
    PSC 240v Blower Motor Testing: th-cam.com/video/uHXw8o_YoZk/w-d-xo.html
    PSC 240v Blower Motor Wiring: th-cam.com/video/5GITgsRmSZ4/w-d-xo.html
    Tools I Use Are Linked Below!
    Leak Detection:
    Accutrak VPE Ultrasonic Leak Detector amzn.to/2nFYKVe
    Accutrak VPE-GN Ultrasonic Leak Detector amzn.to/2Zy4IZP
    RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn
    Vacuum Tools:
    JB 6 CFM Vacuum Pump - amzn.to/2nqbvo8
    CPS 4 CFM Vacuum Pump - amzn.to/2DxgPwY
    Appion Valve Core Removal Tool - amzn.to/2uYr8WL
    Appion Blue 3/8" to 1/4" Vacuum Hose - amzn.to/2uYlVyc
    Appion Red 3/8" to 1/4" Vacuum Hose - amzn.to/2uYg6Ro
    Yellow Jacket 1/4" by 1/4" 3’ hose - amzn.to/2umtcod
    Appion 1/4" by 1/4" and 3/8” hose - amzn.to/2Zyxzx9
    Uniweld 1/4" by 1/4" 2’ hose - amzn.to/2GFov1Y
    CPS Vacuum Micron Gauge - amzn.to/2v1nM3O
    Supco Vacuum Micron Gauge - amzn.to/2v1JRiA
    JB Vacuum Pump Oil - amzn.to/2mGrlXy
    Checking the Charge:
    Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq
    Refrigerant hoses with valves amzn.to/2aBumVI
    Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9
    Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq
    Digital Refrigerant Scale amzn.to/2b9oXYl
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Fieldpiece SMAN380 Digital Manifold Set amzn.to/3297zse
    Fieldpiece SMAN480 Digital Manifold Set amzn.to/337mGnq
    Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8
    QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg
    RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
    Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3
    Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs
    Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw
    Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ
    Flaring Tools:
    Yellow Jacket Flaring Tool - amzn.to/2OBxGlM
    Spin Flaring Bits 1/4", 3/8", 1/2", 5/8", 3/4"- amzn.to/31BCs8Z
    Yellow Jacket Flaring Tool with Set Depth - amzn.to/2QIKsQH
    Yellow Jacket Torque Wrench - amzn.to/2NRR68Q
    Uniweld Swage and Flare Kit- amzn.to/2T55jyn
    Nylog - amzn.to/2MLJcch
    Ridgid Tubing Cutter - amzn.to/2DnjjR1
    Wolverine Tube Reamer - amzn.to/2QGLyMV
    Swaging Tools:
    Manual Copper Tube Swage/Expander- amzn.to/2WRPa1M
    Spin Swaging Bits 1/4" to 7/8" for the Drill- amzn.to/2YQwwqS
    Uniweld Hydraulic Swaging Tool- amzn.to/2MlrI8m
    Uniweld Swage and Flare Kit- amzn.to/2T55jyn
    Uniweld Hammer Swage kit- amzn.to/2CzWMMU
    Uniweld 3/4" Hammer Swage- amzn.to/2CzXsSs
    Uniweld 7/8" Hammer Swage- amzn.to/2Mja5WE
    Uniweld Multi-Size Hammer Swage- amzn.to/2T3Cx1b
    Brazing Tools:
    Air Acetylene Torch setup - amzn.to/2aQalsb
    15% Silver Brazing Rods - amzn.to/2gVLyLc
    Uniweld Cap-N-Hook and #2 Tip Oxy Acetylene Torch Setup - amzn.to/2STp3Fe
    Ameriflame Oxy Acetylene Torch Setup #1  Tip - amzn.to/2SRm3JF
    #2 Tip for Oxy Acetylene Torch - amzn.to/2SPDaeD
    Cap-N-Hook Tip for Oxy Acetylene Setup - amzn.to/2MbhpUk
    40cu B Tank to 10cu MC Tank Acetylene Tank Fitting - amzn.to/2GxZZPi
    Nitrogen Regulator - amzn.to/2bXdR5f
    Uniweld NitroVue Flow Regulator - amzn.to/2GnsaAo
    Uniweld Nitrogen Flow Meter - amzn.to/2brvoBg
    Bernzomatic Trigger Start Lighter Propane/Mapp Gas - amzn.to/2vit0cv
    Uniweld Soft Flame Sweating Torch Setup for Acetylene - amzn.to/2DyzRD8
    Flint Spark Ignitor - amzn.to/2L3P2u9
    Stay Brite #8 Silver Bearing Solder and Flux - amzn.to/2XIDJsY
    Aluminum Braze Rods - amzn.to/2IGNMu
    Electrical Diagnosis Tools:
    UEI DL389 Multimeter amzn.to/2xAdaJf
    UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ
    Magnet Jumpers- amzn.to/2PyKPQZ
    Alligator Jumpers- amzn.to/2PxqJXn
    Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V
    Nitrogen:
    Uniweld NitroVue Flow Regulator- amzn.to/2GnsaAo
    Uniweld Nitrogen Flow Meter amzn.to/2brvoBg
    Nitrogen Regulator amzn.to/2bXdR5f
    Service Valve & Port Access:
    RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn
    25 Valve Cores - amzn.to/2L37UJU
    25 ¼” Brass Port Caps with rubber O-rings - amzn.to/2GIOdD2
    Brass Valve Core Tool which holds 3 valve cores - amzn.to/2GFEbm2
    Valve Core Torque Wrench - amzn.to/2GHiLoD
    Locking Cap Universal Lock/Unlock Tool - amzn.to/2GGAoVp
    Locking caps - amzn.to/2GFXZ8A
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Yellow Jacket Sealright 90 Coupler- amzn.to/2LsU1V7
    Yellow Jacket 1pk Compact Ball Valve- amzn.to/2uXdF18
    Yellow Jacket 3pk Compact Ball Valve- amzn.to/2AiKfQe
    Thumb Screw Valve Core Depressor with Backseat- amzn.to/2mR0sCL
    Other tool links can be found in the video description section.
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech

    • @samuelneil7490
      @samuelneil7490 3 ปีที่แล้ว

      I dont mean to be offtopic but does anyone know a tool to log back into an Instagram account??
      I somehow forgot the login password. I love any tricks you can give me!

    • @xavierleandro188
      @xavierleandro188 3 ปีที่แล้ว

      @Samuel Neil instablaster ;)

    • @samuelneil7490
      @samuelneil7490 3 ปีที่แล้ว

      @Xavier Leandro thanks for your reply. I got to the site through google and im waiting for the hacking stuff now.
      Takes a while so I will reply here later with my results.

    • @samuelneil7490
      @samuelneil7490 3 ปีที่แล้ว

      @Xavier Leandro it did the trick and I actually got access to my account again. I am so happy:D
      Thanks so much, you really help me out !

    • @xavierleandro188
      @xavierleandro188 3 ปีที่แล้ว

      @Samuel Neil no problem :)

  • @johndoe-wt4ui
    @johndoe-wt4ui 5 ปีที่แล้ว +114

    Nobody at my job can teach me any of this 🤦‍♂️ I have to go to TH-cam your channel to learn how to be a hvac Service Tech it’s frustrating man thanks ac service tech

    • @eclipse369.
      @eclipse369. 5 ปีที่แล้ว +25

      Most technicians are part changers. Learn all you can :)

    • @TheOneshot78
      @TheOneshot78 5 ปีที่แล้ว +14

      Read books and learn on your own..we are in a field that never stop learning. Also go to Expos and trade shows. Any training you can go too do it.

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว +12

      We all just try to invest in ourselves as best we can. Thanks John Doe for letting me know! I am glad that the videos are helping in your current situation!

    • @benjamindyer7348
      @benjamindyer7348 3 ปีที่แล้ว +4

      I agree, must of my co workers are great at what they do but they don't know the real deep details on how this stuff works

    • @kidernie7
      @kidernie7 3 ปีที่แล้ว +1

      Dammm I did a service call and the motor kept spinning even tho the ts was off, now I know why thanks boss couldn’t help that day 🤨

  • @kr4awkr4aw5
    @kr4awkr4aw5 2 ปีที่แล้ว +5

    I LOVE TH-cam!!!!! The motor on my furnace went out. An AC/Heat company said it would cost over two thousand bucks to fix it, due to the type of motor ECM. which cost around 1500.00 dollars. So like always I went to youtube to see how hard would it be to replace the motor. To my surprise, there were many videos showing how to do it. Looked pretty simple to me. I found a place that sells rebuilt motors and found exactly what I needed for $300 dollars no tax or delivery charges. Just got the motors and fixed my unit in less than two hours, most of that time was cleaning the furnace. The wife is happy and I am very happy. Thank you, TH-cam you're the best!!!

    • @Raulito9
      @Raulito9 9 หลายเดือนก่อน +3

      What site was it?

  • @Armand9100
    @Armand9100 2 ปีที่แล้ว +14

    I bought a Genteq 5SBA39FLP8013 ECM blower motor to replace the Broad Ocean motor which stopped working in my air handler. The Genteq is an X13 with 5 speed taps as shown in the video. I decided to test it before going to the trouble of mounting it in the air handler. I laid it on its side next to the air handler and connected the wiring. The thermostat was set to fan only. When I turned on the power the shaft began to spin for about 1 second and shut off and then a few seconds later it came back on and shut off and continued this pattern until the power was shut off. My neighbor's son in law is a HVAC technician, so I called him and explained the problem. He told me that the motor detects the load that is on it and adjusts for that load to maintain a steady speed. It needs to have the blower wheel on it and be mounted in the blower housing in order to detect a load. I installed it in the air handler and it works perfectly. I don't know why this information is not in the video and why the motor in the video is not showing this problem.

    • @jeanettejack2152
      @jeanettejack2152 5 หลายเดือนก่อน

      FYI The Genteq X13 will determine a CW or CCW rotation on it's own when powered on the first time. This can take a minute as it figures load, direction and speed. The sensor in mine went bad (12 years old) and would hunt back and forth only. Fan never did get up to speed.

    • @rThirstwastaken
      @rThirstwastaken 8 วันที่ผ่านมา

      Holy shit! The one time I go to TH-cam first and find the exact fix to my issue. Thank you, I never would have figured that out on my own, I thought It was a faulty mod.

  • @orangetuono38
    @orangetuono38 2 ปีที่แล้ว +9

    HELLYA! Paid $85 for a service call for the guy to lie to me about the issue. Watched AC Service Tech video, got the skinny, back up in the attic troubleshoot to a likely blown Cap on the ECM module, order an exact replacement off Ebay for $82. 3 hours of YT videos, 1 hour to Trane shop to be denied, 1 hour surfing Ebay, then 10 minutes mounting replacement ECM and I'm UP AND RUNNING! It was a total of 6 screws to fix!! You saved me $2400!!!!!!!!!!!!!!!!!!!!!!!! Signed up for Patreon. I'm not an HVAC pro so would have preferred a one-time payment.

    • @hliz8818
      @hliz8818 9 หลายเดือนก่อน +4

      Your machine could have been out off warranty. You were paying parts and labor. Did you know it was the blower motor BEFORE he got there? I'm glad you fixed it. But don't bash the tech. Most of the time the company sets the prices..we just do our part and diagnose issues for customers.. plus it's an attic. Salute

    • @orangetuono38
      @orangetuono38 9 หลายเดือนก่อน

      @@hliz8818Company, Tech or both, they tried to get $2500 for the blower replacement or better yet a $8000 full system replacement. It's a year later and I'm out $75 in parts and my HVAC is running great. I spent more time watching this video than the repair took.
      If that's how you "just do our part" you might want to think about how you sleep at night.

    • @mattschulz558
      @mattschulz558 5 หลายเดือนก่อน +2

      No doubt, glad you can do it yourself but a licensed company has a certain value for their time. Incidentally I've been researching and there are conversion boards from ecm to psc.
      Suppliers won't help you fix old stuff, only push new sales

    • @edbouhl3100
      @edbouhl3100 4 หลายเดือนก่อน

      I had a similar experience with the capacitor being the failed part but a tech was not involved. After looking at TH-cam videos for 2 days (I’m retired) there was a throwaway comment at the end of one that gave me the clue. That was 3-4 years ago and it’s still going (but who knows for how much longer). I think the takeaway from your story is if you have the time just go ahead and get the part when it fails (assuming you can confirm which one that is), change it out yourself (follow the diagram), save on the labor, fix the original if you can and keep it as a spare.

  • @samuelvalenzuela4541
    @samuelvalenzuela4541 4 ปีที่แล้ว +5

    These are the best HVACR videos around the world from AC Service Tech, congratulatuons from México

  • @ToughCowboy
    @ToughCowboy 2 ปีที่แล้ว +10

    Unbelievably helpful, THANK YOU!!! I literally got 2 quotes - one was for $3,850 to replace motor and ECM and the other company said there was not available replacement available and said I absolutely MUST buy new unit which was $10-12k. I just replaced the motor and ECM with parts from Supply House for $750. However, from your video I figured out that it was the inrush current limiter that had blown and bought new component for $5.07, so will either save as backup or sell used but working on eBay and probably get $200-300 of my money back, I would have sure paid it.

    • @tooftaker
      @tooftaker 2 ปีที่แล้ว

      Where did you find the inrush current limiter?

  • @brunoshvac2578
    @brunoshvac2578 3 ปีที่แล้ว +14

    Thanks for sharing Craig. I tell all my trainees to watch your videos. It’s amazing what this industry has become with everyone sharing information thanks to people like you putting in the time. Great video sir!! 😎

  • @EyeForKnowledge.
    @EyeForKnowledge. 2 ปีที่แล้ว +10

    I got myself into the trade watching TH-cam. AC service tech knows their stuff. I started at an apartment complex as a groundskeeper and within two years I was lead tech. Now, I’m in residential working for a really good company that really doesn’t have time to train. Most companies don’t have the resources (especially in todays economy with everything getting so expensive), to send two techs to a house so one can learn. So you either start as a helper making $10/hour where you’ll be on install or you learn the stuff and go in making $30/hour on service. Learn this stuff. You won’t be rich but you’ll make a comfortable living. I’ll be moving into industrial and commercial soon. We do commercial now but I’m looking forward to working on more complicated things like chillers and oil heaters.

  • @rb5875
    @rb5875 5 ปีที่แล้ว +12

    Your electrical troubleshooting videos have been helping me on a daily basis, and your book has been a huge help in the field for me to look back on instead of calling my techs. It would be amazing if you made a book on electrical troubleshooting, having a good guid handy really helps out in a jam for a newbie on call lol

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว +4

      Thank you very much for letting me know and I would very much like to in the future, thanks!

  • @coydog6665
    @coydog6665 ปีที่แล้ว

    Congratulations Shawn on the marriage, I wish you and your wife a lifetime of happiness.
    Brother I’ve been following from the beginning and will continue to follow your videos. I enjoy the way you approach content and then share it.
    Semper Fi brother!

  • @jesseduenes7380
    @jesseduenes7380 3 ปีที่แล้ว +3

    Thank you so much for the information on this ECM.
    I'm a maintenance technician at a retired community and I have ran into some problems with some of my air handler blower with this ecm. So watching this video gives me a little more information on what to look for.
    Again thank you for your fine work & information!

  • @martinsharp2400
    @martinsharp2400 6 หลายเดือนก่อน +1

    Thanks!

  • @ericbrobst5591
    @ericbrobst5591 5 ปีที่แล้ว +3

    Great imformational video. Had an X-13 motor running constantly, without 24v, about a month ago. I replaced the entire motor. I was unaware untill watching this video that you could replace the module only. Your videos are always helpful.

  • @Cl4rkTheShark
    @Cl4rkTheShark 2 ปีที่แล้ว +1

    If you replace an ECM motor and it is ramping up & down... make sure the blower is turning the right way. Thanks for the video!

  • @hvacdoc2338
    @hvacdoc2338 5 ปีที่แล้ว +16

    Great explanation !! I’ve been in the field for many years and still learn a lot from your videos.

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว +1

      Absolutely, I wish I had all the online training, articles, and videos when I started. I could have learned a lot faster when I started in the trade, thanks!

  • @jashua2089
    @jashua2089 3 ปีที่แล้ว +1

    Thank you all HVAC school members for these great lessons.

  • @pointblank6467
    @pointblank6467 3 ปีที่แล้ว +3

    This was the most detailed explanation of these motors I have ever seen. Thank you so much!

  • @davisgarrett7689
    @davisgarrett7689 5 หลายเดือนก่อน +1

    This video was fantastic and helped me diagnose some issues I was having with my blower fan. Thanks for putting this together! Very informative and very helpful. Keep up the great work!

  • @acheatdoctor
    @acheatdoctor 5 ปีที่แล้ว +5

    I was just diagnosing one of the ocean broad motors yesterday, this video was right on time. Kudos

  • @stuzman52
    @stuzman52 5 ปีที่แล้ว +4

    Great information Greg! Just to add another tidbit of information, I had purchased a generic X13 preprogrammed ECM motor, but the motor ran backwards. There are three stator windings which are very similar to a 3-phase motor. One can cut any two of the three wires on the connector going to the stator windings, reverse the leads and the motor will run in the reverse condition. I don't recommend this, but it will work as I've done it to get a unit to work. Fortunately, the motor speed was very close to the original.

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว

      Nice, thanks Stuzman!

    • @Zeknix
      @Zeknix 3 ปีที่แล้ว

      Some of those motors have a way to program it to reverse the direction of the motor. Also, the motor is a three phase motor, but that doesn't mean you can hook it up to three phase straight from the breaker panel as a temporary work around. I tried this as a last ditch effort to get the AC blowing again, and the windings started to cook. We were over 80 miles offshore so getting a replacement wasn't going to be quick. Thankfully, the field had a crew boat that was making a run to the beach for resupply the next day.

  • @earlguillory5168
    @earlguillory5168 3 ปีที่แล้ว

    I see a lot of ECM motors on Fan powered boxes (VAV's) and this is the best video with explanations I have seen to date. Usually, the factory recommendation is to use the "Tech-Mate" adapter and call it good.
    Thanks for the great video.

  • @markit8dude321
    @markit8dude321 ปีที่แล้ว

    I just started out in this field and luckily I have been lucky enough to work with someone who has 30 + years experience.. But he will make the time to teach you if you’re interested and trying. Not trying to wast time

  • @Eddy63
    @Eddy63 5 ปีที่แล้ว +18

    Excellent explanation Craig ... I wish you were around 40 yrs ago ... Lol ... Happy 2020 ...

  • @stevehiggins9338
    @stevehiggins9338 ปีที่แล้ว

    Perfect explanation and understanding of how to service these motors. I have been trying to find something like this for a while now and you nailed it. Thanks man.

  • @DIYDaveT
    @DIYDaveT ปีที่แล้ว +2

    Excellent vid. IT would be nice to know what application of the 24 VAC motor speed control signal actually do, and how one goes about "programming" which speeds are active. It is clear from your vid that only 1 control signal is to be applied at a time. What if the air handler controller feeds 2 at a time?

    • @benbernank1341
      @benbernank1341 ปีที่แล้ว +1

      I found the same thing… a Goodman system feeds 24v to 1&2 when heating or cooling and 24v to just 1 with call for “G” alone…

  • @Deus_Ex_Machina.
    @Deus_Ex_Machina. 2 ปีที่แล้ว +1

    Thank you! You're a saint for bringing this secret information to the people! And to clearly explained. The manufacturers and installer/dealers are in cahoots to make it hard for the owners of the appliances to handle their own hardware failures. I don't much like situations where early failures bring profit to someone else, after I shelled out for the equipment. I'm not saying everyone should try this at home, but if you are technically educated, it's nice to have the simple facts so you can take care of issues.

  • @patbrock7460
    @patbrock7460 3 ปีที่แล้ว +2

    I live in the Chicago area, lots of supply houses, but on a Saturday night at 100 bucks + an hour the bill can be ridiculous. I've also had supply houses be out of stuck. I always carry a standard PCM motor for older style motors. At -10 outside the people don't want to hear you'll be back tomorrow if you can find the part. So, I will install the PCM motor and hot wire it low for heat and high for AC.to give them service. I know some guys that carry an old working motor just to give service and you can take your time getting the right part. I carry a 1/2 hp. does 1/6 thro 1/2 and 90% of my calls.

  • @michaelcolgan3182
    @michaelcolgan3182 2 ปีที่แล้ว

    This was an excellent description on how these work. Thank You

  • @joshainsw
    @joshainsw 2 ปีที่แล้ว +1

    I have a carrier unit with the broad ocean ecm you have in the video. I have had an issue 3 times now where all of a sudden when the ac turns on the inducer/blower motor doesnt turn on. The first time I got it working, but to be honest not sure what I did is all I did was test just like you said and when I hooked back up it worked like nothing had ever happened. It then did it again several months later. I was out of town but the wife and kids were at home and I just called an hvac tech to come and look at it since I couldn't trouble shoot. I had the wife simply kill power to the whole unit and when the tech got their the next day he flipped the power back on and it worked with no issues. Basically paid him for a trip to come to my house and turn it on. Well now it has been about 6 months since hat time and it has done it again. Of course I am out of town, but I will trouble shoot when I get back.
    Sorry for being such long winded but wanted to give you as much info as possible. So you have any idea why it would be intermittently not working. Why would it not work then when turned off for a period of time or when testing it it just all of a sudden works like normal again. I had thought the first times were due to power surges and actually installed a whole house Honeywell surge protector about 3 weeks ago so it wouldn't happen again. This last time, today my wife said there were not any power surges. Any help would be appreciated.

    • @batso-felik3436
      @batso-felik3436 11 หลายเดือนก่อน +2

      You may have an intermittent problem with that blower motor. That means it’ll work when it wants to and it won’t work when it wants to. That’s a sign of a bad module or blower motor or both.

  • @jiangbian76
    @jiangbian76 5 ปีที่แล้ว +2

    The best video for troubleshooting the ECM, thank you!

  • @oscarestrada5509
    @oscarestrada5509 4 ปีที่แล้ว +2

    He's very nice and very good explain ed I have 6 yes in the field and I've still learned with this man other thing.you are doing well thanks

  • @Craig1967
    @Craig1967 3 ปีที่แล้ว +2

    Great video! Too bad most control modules are potted. I do component level repairs on just about everything, so it bothers me when manufactures make things disposable. I liked that you said that the MOV is replaceable. Hopefully some technicians will have good soldering skills and will replace them rather than swapping out the module and/or motor. I have worked on some large 3 phase VFD drives for big commercial air handlers, and most of the time its poor soldering and capacitors. The VFDs that I work on are external, and are not potted. Of course there are no schematics, so it is sometimes a challenge. Keep up the great work. Your book is great - I purchased it about a year or so ago. Thank You.

    • @chuckcraigs9310
      @chuckcraigs9310 2 ปีที่แล้ว

      could a bad mov cause the motor to continuously run or is that likely something else in the module?

  • @superiorcomfortheatingairl3373
    @superiorcomfortheatingairl3373 5 ปีที่แล้ว +7

    You always do great training videos, but this one is one of my favorites. Unfortunately I have already ran across a OEM replacement motor that was programmed wrong, not for sure if it was the manufacturer or the distributor (lot of distributors are able to program motor with OEM specs). Since the motor was under warranty, the service call was negative profit for labor.

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว +1

      Sorry to hear that and yeah we need to be very well versed with the things we tend to run into. Thanks for letting me know Superior!

  • @brianrott921
    @brianrott921 2 ปีที่แล้ว +1

    Catus Maximus! ...I've got a variable speed blower motor went bad so thanks for the info

  • @jackpast
    @jackpast 5 ปีที่แล้ว +2

    Great hands-on, Craig!

  • @bluebeastgamer3005
    @bluebeastgamer3005 4 ปีที่แล้ว +1

    You are the best 👍👍👍

  • @derf_the_mule1405
    @derf_the_mule1405 2 ปีที่แล้ว +3

    Some of the X13 controllers have an OFF Delay (30sec-3min) built in. My ComfortMaker (Carrier) does this. The only way to stop it is replace the control board without the OFF delay.

  • @zookeroni1834
    @zookeroni1834 3 ปีที่แล้ว +1

    beautiful explanation

  • @bobrebera494
    @bobrebera494 3 ปีที่แล้ว +1

    always a great reference tool-thanks my friend

  • @borshardsd
    @borshardsd ปีที่แล้ว

    Another great share! Good content from your team always 👏

  • @boogerhead0
    @boogerhead0 2 ปีที่แล้ว

    My ECM had magnets detached from the rotor. Cleaned off the junk glue film remaining on the rotor and magnets, and re-affixed them with epoxy, original orientation, spacing. Motor working fine again. Thank GE, Beloit and Junktek or whoever owns this now Genteq for stupid glue application. Even multirotors have the magnets arranges so they cannot be thrown off.

  • @samersam1933
    @samersam1933 3 ปีที่แล้ว +1

    Thank you sir nice explanation👏🏻

  • @fahadsheikh5374
    @fahadsheikh5374 ปีที่แล้ว

    Thank you for your guidance and explanation , keep it up 👍

  • @marcusdarnell3348
    @marcusdarnell3348 5 ปีที่แล้ว +1

    Thanks Craig! Happy 2020!

  • @johncasale2195
    @johncasale2195 2 ปีที่แล้ว

    Excellent in detail

  • @donnierobertson3088
    @donnierobertson3088 3 ปีที่แล้ว +1

    Great job and video like always

  • @RockoRocko-rz7kx
    @RockoRocko-rz7kx 5 ปีที่แล้ว +2

    Great video. Thank you for sharing your knowledge

  • @ricardofuentes2153
    @ricardofuentes2153 8 หลายเดือนก่อน

    Great video! Plenty knowledge

  • @syn-techcooling7282
    @syn-techcooling7282 3 ปีที่แล้ว +1

    Well done. You are a master!

  • @JuanTodoli
    @JuanTodoli 5 ปีที่แล้ว

    Good one. Happy new year Craig.

  • @tymr.t3645
    @tymr.t3645 4 ปีที่แล้ว +1

    Thank you 🙏😊👍

  • @enduringpromise
    @enduringpromise 3 ปีที่แล้ว +1

    Great information. Thank you!

  • @alsera9063
    @alsera9063 3 ปีที่แล้ว

    Excellent video tutorial! Thanks!

  • @broncheemims8493
    @broncheemims8493 5 ปีที่แล้ว +1

    Thanks Craig for the info

  • @richardleveson6467
    @richardleveson6467 7 หลายเดือนก่อน

    Thanks for this. The industry charges huge margins for relatively inexpensive parts from Mexico or even China and then we get charged double that by the less scrupulous service technicians. Here in Canada things are worse as the parts suppliers won't sell to the public. I fixed my furnace blower for $25 (cost of five thermistors plus overnight Fedex from DigiKey) after being quoted $1,500 for a new unit. I wish I could find a tech like the creator of this video but, sad to say, they are few.

  • @bryantylerservices
    @bryantylerservices 5 ปีที่แล้ว

    Excellent explanation on ECM motors diagonis / test for continuity and ground..
    And on module itself!
    Great video ,Craig !
    Bryan Tyler Refrigeration

  • @zadvindersingh4234
    @zadvindersingh4234 4 ปีที่แล้ว

    Honestly a great video great teaching abilities
    👍👍

  • @williampaul8979
    @williampaul8979 5 ปีที่แล้ว +1

    A great video as always. Keep doing what you do best !

  • @manolinrosales9640
    @manolinrosales9640 2 ปีที่แล้ว

    Excelent explanation!

  • @tube8533
    @tube8533 6 หลายเดือนก่อน

    Great video!

  • @mannyfilmsinc
    @mannyfilmsinc 3 ปีที่แล้ว +1

    awesome video, thank you so much for sharing... would you be more incline to replace just the module or the whole motor on an ECM Genteq , if the motor is constantly running....

  • @harryappliancesrepair8587
    @harryappliancesrepair8587 2 ปีที่แล้ว

    thanks bro i,m always leaning alot new things

  • @Dogecoinfuture
    @Dogecoinfuture 2 ปีที่แล้ว

    I love you man . You are the best .

  • @patmason7276
    @patmason7276 3 ปีที่แล้ว +1

    Ac company came to fix our unit thought it was the blower assembly, then the board find out the yellow wire to the thermastat had voltage on it all the time. Swapped with another extra wire in the harness everything is good.

  • @xelaju8
    @xelaju8 5 ปีที่แล้ว +1

    Thanks for the video. Very useful.

  • @gregoriomatos3935
    @gregoriomatos3935 4 ปีที่แล้ว

    can`t explained any better.great content

  • @anvibrimel41
    @anvibrimel41 4 ปีที่แล้ว +1

    Thanks a lot for this lesson you are awesome and I already have your book but I going to get your quick cards reference,thanks

  • @MrCRYLATINO911
    @MrCRYLATINO911 4 ปีที่แล้ว +1

    This was a very helpful video my gosh. Do you happen to have a video showing the step by step to swapping an ECM motor to a PSC motor that you would typically carry on the truck?

  • @JerichoStephen
    @JerichoStephen 7 หลายเดือนก่อน

    Which book you recomend to get more knowledge about furnace & ac unit sir 👌🙏🫵🫶 your videos.
    Indeed your are a great master

  • @leonelgamez3302
    @leonelgamez3302 4 ปีที่แล้ว +1

    Thanks.. good explanation.!!

  • @bobrebera494
    @bobrebera494 5 ปีที่แล้ว +1

    great video and easy to understand-thanks

  • @joem3384
    @joem3384 5 ปีที่แล้ว +1

    I appreciate your help Very helpful knowledge

  • @jayecheverria2454
    @jayecheverria2454 2 ปีที่แล้ว

    Awesome video👍

  • @Fredflinstone23
    @Fredflinstone23 2 ปีที่แล้ว

    Thank you

  • @royabreu3627
    @royabreu3627 ปีที่แล้ว

    Good explanation,thx,what would be the case if the motor cycle off and on,this will be the module or the motor,thx

  • @sknight0391
    @sknight0391 5 ปีที่แล้ว +1

    Great Job 👍

  • @mr.airservicesllc1373
    @mr.airservicesllc1373 2 ปีที่แล้ว

    Great video on ECM's, I hope you put out more video's on Broad Ocean and Rescue motors (maybe you did already??). I would change your explanation on the motor potentially overheating if there's an airflow restriction because motors draw less current with an obstruction (less work as your not pushing as much air - less work = less amperes). I subscribed, looking forward to watching more technical videos!

  • @enrolledregistrar103
    @enrolledregistrar103 ปีที่แล้ว

    Awesome thank you very much

  • @ttk1opc
    @ttk1opc ปีที่แล้ว +1

    Are you better off changing the whole motor if you find that it is just the control module?

  • @meyerjeff
    @meyerjeff 4 ปีที่แล้ว

    Only to add that the “in-rush current limiter” you point to in the electronics module is called a Metal Oxide Varistor - and as you said, can be field replaced with relative ease.

  • @noealeman8527
    @noealeman8527 4 ปีที่แล้ว

    Thank you!! Awesome video like you always do .

  • @andresmurillo5117
    @andresmurillo5117 4 ปีที่แล้ว

    Excellent video, thank you for share you knowledge.

  • @javiercalvillo4865
    @javiercalvillo4865 3 ปีที่แล้ว

    Thanks 🙏🏽it was really helpful 👍🏽

  • @jonminnella4157
    @jonminnella4157 ปีที่แล้ว +1

    Where I live these motors are 1000 bucks I have been kicked out of customer house because of price of the part I don't even mark these motors up it's grate to have high efficiency but there is no savings if the savings have been spent on repairs

  • @zekenzy6486
    @zekenzy6486 5 ปีที่แล้ว +1

    Great video. Thank you for sharing. Happy New Year . What is different and the same between ECM motor and Variable speed motor ?

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว

      A variable speed can modulate the speed up and down depending on the gas output stage of a furnace where as an ecm multispeed as very specific speeds. However, both are quieter than PSC motors at startup, thanks!

  • @nicosanti100
    @nicosanti100 4 หลายเดือนก่อน

    Awesome

  • @joe65477
    @joe65477 3 หลายเดือนก่อน

    Can you show how to replace the capacitors and the inrush current limitator?

  • @E85_STI
    @E85_STI 2 ปีที่แล้ว

    I’m about to graduate from HVAC course but my IBM went out and the tech that came out did a resistance test on the module and he said it was at 18 ohms but normal limits should be between 10 and 20 so he said it was starting to fail. He replaced the whole blower with a new one that didn’t come with a module on it. So I’m the future I can check the resistance of the motor itself without dealing with the module although the module is cheaper to replace than a motor.

  • @matthewedwardsnyder
    @matthewedwardsnyder 3 ปีที่แล้ว

    You are a saint. Thank you so much man.

  • @baggins1
    @baggins1 3 ปีที่แล้ว

    Excellent

  • @boblab
    @boblab 2 ปีที่แล้ว

    Did you say that the x13 has to be programed and if it does , who does it? Thanks for the great video.

  • @ApartmentMaintenance
    @ApartmentMaintenance 5 ปีที่แล้ว

    Great detailed video 👍 Where would you purchase a new inrush current limiter if that was bad ?

    • @pizzle1011
      @pizzle1011 4 ปีที่แล้ว

      Amazon has them

  • @mewonderwhy
    @mewonderwhy 2 ปีที่แล้ว

    First of all your videos are great. I don’t usually subscribe but I felt compelled to do so after watching two of your videos. What is the expected resistance 1/2 Hp 208/230V X13 motor. I’m getting 12.9 ohms on all. Sorry I’m sure you already answered in comments here or elsewhere but I don’t see how to search comments.

  • @manuel12888
    @manuel12888 4 ปีที่แล้ว

    Thank you so much
    Very

  • @Trigger_32
    @Trigger_32 7 หลายเดือนก่อน

    Just had a first... Payne furnace, newer unit with a broad ocean ECM that wouldnt run so coil froze up. Found circuit board is only supplying 20V to speed tap. Apply 24 direct from transformer, motor fires right up. Apparently the modules are very sensitive and require the full 24V signal.... gotta come up with a circuit board under warranty now🤦🏼‍♂️

  • @INTERNA9
    @INTERNA9 2 ปีที่แล้ว

    Thanx

  • @lancerudy9934
    @lancerudy9934 5 ปีที่แล้ว +1

    Nice video

  • @karimmecherfi5346
    @karimmecherfi5346 5 ปีที่แล้ว +1

    Great video as always would you please do a video on ecm 16 hernes plug thanks

    • @acservicetechchannel
      @acservicetechchannel  5 ปีที่แล้ว

      Karim, yes I believe I have done two videos on that. One was how to wire and make your own variable speed testing setup, thanks!

    • @karimmecherfi5346
      @karimmecherfi5346 5 ปีที่แล้ว

      I look for it thanks

  • @valdemarbenavides3274
    @valdemarbenavides3274 ปีที่แล้ว

    Great informative video. Just had a question. When my ecm is plugged in, it’s hard to turn by hand but when I disconnect the ecm. It moved freely. Does this mean I have a bad ecm or bad blower? Should I just replace both?