  • TRANE No Heat Call, we take a look at a Trane roof top unit with no heating operations. I thoroughly check the necessary components to make the correct diagnosis for the reason of the heat failure.
    Follow me on twitter - / _travismichael
    Hello Everyone,
    I am a NJ Master HVACR contractor license holder, home renovator and handyman. I have extensive experience in the HVAC field along with adequate knowledge in plumbing, electrical and carpentry to perform most tasks around a house. Subscribe to my channel for more around the home how to videos and other informative content. This video is not sponsored by any brands, products or companies seen or referred to in the video. Always check for power to verify electrical source has been isolated before working on any HVAC equipment. Always remember to follow all manufacturer safety guidelines, recommendations and requirements when working with any powered and non powered tools.

ความคิดเห็น • 22

  • @chova210
    @chova210 10 หลายเดือนก่อน +1

    Excellent troubleshooting. Most techs would diagnose the board and call it a day

  • @nathanhurst5155
    @nathanhurst5155 ปีที่แล้ว +3

    Nic job man, we love the no parts required repairs, unfortunately we don’t get too many of those.
    I was screaming at the screen when you were referencing ground while checking power lol. Then I realized you were doing it to show/prove a point. Only time we should reference ground for power is the safety check. 👍👍

    • @travismichael502
      @travismichael502  ปีที่แล้ว

      Thanks, yes I have seen that numerous time before.

  • @walterpena2430
    @walterpena2430 7 หลายเดือนก่อน

    Good job,you can used a coins or any metal object and touch those 2 screws on the low voltage terminal block and will go fast on test mode,you don’t have to wait,is too cold,be safe

  • @chrisbrasfield4548
    @chrisbrasfield4548 ปีที่แล้ว

    Nice troubleshooting. Very gratifying. Keep the videos coming. Thanks

  • @hkhsm359
    @hkhsm359 2 ปีที่แล้ว +1

    Nice job. Great knowledge and experience.
    Thanks for sharing

  • @mwdub02
    @mwdub02 2 ปีที่แล้ว +1

    Looks like Secaucus to me lol, good video bro. Keep those aaon videos up, It’s been helping a lot. Thanks

    • @travismichael502
      @travismichael502  2 ปีที่แล้ว

      Good guess lol Thanks for the compliment. I ll keep making the videos, hope to get some new stuff out soon.

  • @raymondperez8182
    @raymondperez8182 ปีที่แล้ว

    Bro that’s some great trouble shooting . Can tell you are a great tech ! 2nd year in the trade , just trying to get better !

  • @alexibonnet2634
    @alexibonnet2634 7 หลายเดือนก่อน

    Nice TS ,

  • @Alex-jo2oi
    @Alex-jo2oi ปีที่แล้ว +1

    2 blinks... indicating failure to sense flame.. I replaced the hot surface ignitor and its still not that. pressure switch is fine... not getting voltage to the gas valve. i'm assuming the unit locked itself out due to a limit switch?

  • @maheradous9257
    @maheradous9257 10 หลายเดือนก่อน

    Good job

  • @gordonpotts753
    @gordonpotts753 ปีที่แล้ว

    I like the way u work

  • @WswRefrigeration
    @WswRefrigeration 2 ปีที่แล้ว +1

    Those tranes can be tricky for sure if you’ve never seen one/have no experience

    • @travismichael502
      @travismichael502  2 ปีที่แล้ว

      Yeah no flash code diagnosis to make it easy like many other units have. Just tells you its in heat failure.

  • @kevinmenue8883
    @kevinmenue8883 ปีที่แล้ว +1

    I got a trane that will start up the inducer fan but won't fire. No gas smell, Has new ignitor. Inducer fan will run constantly

    • @travismichael502
      @travismichael502  ปีที่แล้ว +2

      Is there an attempt of ignition? Check igniter and voltage at gas valve. No gas probably indicates that the gas valve is not opening, if voltage is not present at the gas valve but you have a call for heat, check the ignition control board and safeties. Same system run the inducer draft constantly when a limit switch or roll out switch is open. If everything functioning, check inlet gas pressure to the unit.

  • @viperking105
    @viperking105 ปีที่แล้ว

    I think they are terrible they over complicate things I got 114v at the connector for hsi so no readings on it either when test straight to it so hopefully that’s it

  • @ebfsystem
    @ebfsystem 8 หลายเดือนก่อน

    Audio volume way to low,all I herd is the background noise

  • @a2zblogvideo598
    @a2zblogvideo598 8 หลายเดือนก่อน

    Hello I'm from India I'm interested this work and my qualifications diploma in Aircondition and Refrigeration. I also work vrv dakin and caset Aircondition package a.c . And I'm Search job aporchunity