TK4L-24SN is an SSR drive voltage output product. So, there is no need for separate settings related to output. For the PID value, set the set value(SV) and execute Auto-tuning.
@@muhamadsolehabdillah3124 Unfortunately, there is no video based on the TK series. However, it is similar to the TCN series auto-tuning method in this video. 01:52 Just set [At] of parameter 2 group from [OFF] to [ON].
i got problem, indicator value is more higher than actually. how to solve this problem? thermometer 10-15oC lower than indicator on oven. but normal and show samevalue at room temperature@@AutonicsCorp
I use tcn4s for an oven with 2 heaters using ssr. I have tried to replace the thermocouple but the measurement results when the temperature is hot are way off. I have reset and tuned pid. Is there anything wrong or missing in what I did to get it back to normal?
The difference between the PV displayed value and the actual temperature is a problem on the temperature sensor side. Do the temperature sensor type used and the temperature controller settings[In-t] match? The PID value is not relevant to this issue.
Hola, se puede usar el modo PID con la salida Rele?
Si, está disponible.
Sin embargo, en el caso del control PID, la salida se activa/desactiva con frecuencia, lo que puede afectar la vida útil del relé.
how to setting type TK4L-24SN output SSR.
We Setting PID for Temperature Heater Stabil
TK4L-24SN is an SSR drive voltage output product.
So, there is no need for separate settings related to output.
For the PID value, set the set value(SV) and execute Auto-tuning.
@@AutonicsCorp do you have video tutorial execute auto tuning?,
@@muhamadsolehabdillah3124 Unfortunately, there is no video based on the TK series.
However, it is similar to the TCN series auto-tuning method in this video. 01:52
Just set [At] of parameter 2 group from [OFF] to [ON].
@@AutonicsCorp thanks you very much for information.
I Will try
Please i need help it is same way for tcn4w
The TCN4S and TCN4W parameter setting methods are the same.
What problem might you have?
How long auto tune do?
Auto-tuning controls the temperature twice based on the SV and calculates the value.
So, it may take more than twice as long to reach the set value.
i got problem, indicator value is more higher than actually. how to solve this problem? thermometer 10-15oC lower than indicator on oven. but normal and show samevalue at room temperature@@AutonicsCorp
I use tcn4s for an oven with 2 heaters using ssr. I have tried to replace the thermocouple but the measurement results when the temperature is hot are way off. I have reset and tuned pid. Is there anything wrong or missing in what I did to get it back to normal?
The difference between the PV displayed value and the actual temperature is a problem on the temperature sensor side.
Do the temperature sensor type used and the temperature controller settings[In-t] match?
The PID value is not relevant to this issue.
@@AutonicsCorp I have tried replacing the type K thermocouple, and the result remains the same.
Do you kniw where I can buy this product? Are the ones on aliexpress original or fake?
Visit our website www.autonics.com/company/global. Please check the nearest corporation and contact us. Thank you.
Hello. For recovery password, could you provide me the steps to reset it? I have error 6329.thank you
Could you please check your model name?
T4KM-T4CN
Please try [0516]. If this does not work, please contact us again.
Thank you very much for your support. It is ok now
I write you again because after i did factory reset now is asking again ne to put pass, and i have error 9300
Bagaimana kalau muncul error tpi AL 1 dan AL2 nyala semua. Bagaimana cara mengatasinya
If the alarm operation mode of parameter 2 group is set to [AM0], the alarm output can not be used.