Si, está disponible. Sin embargo, en el caso del control PID, la salida se activa/desactiva con frecuencia, lo que puede afectar la vida útil del relé.
i got problem, indicator value is more higher than actually. how to solve this problem? thermometer 10-15oC lower than indicator on oven. but normal and show samevalue at room temperature@@AutonicsCorp
I use tcn4s for an oven with 2 heaters using ssr. I have tried to replace the thermocouple but the measurement results when the temperature is hot are way off. I have reset and tuned pid. Is there anything wrong or missing in what I did to get it back to normal?
The difference between the PV displayed value and the actual temperature is a problem on the temperature sensor side. Do the temperature sensor type used and the temperature controller settings[In-t] match? The PID value is not relevant to this issue.
TK4L-24SN is an SSR drive voltage output product. So, there is no need for separate settings related to output. For the PID value, set the set value(SV) and execute Auto-tuning.
@@muhamadsolehabdillah3124 Unfortunately, there is no video based on the TK series. However, it is similar to the TCN series auto-tuning method in this video. 01:52 Just set [At] of parameter 2 group from [OFF] to [ON].
Hola, se puede usar el modo PID con la salida Rele?
Si, está disponible.
Sin embargo, en el caso del control PID, la salida se activa/desactiva con frecuencia, lo que puede afectar la vida útil del relé.
How long auto tune do?
Auto-tuning controls the temperature twice based on the SV and calculates the value.
So, it may take more than twice as long to reach the set value.
i got problem, indicator value is more higher than actually. how to solve this problem? thermometer 10-15oC lower than indicator on oven. but normal and show samevalue at room temperature@@AutonicsCorp
I use tcn4s for an oven with 2 heaters using ssr. I have tried to replace the thermocouple but the measurement results when the temperature is hot are way off. I have reset and tuned pid. Is there anything wrong or missing in what I did to get it back to normal?
The difference between the PV displayed value and the actual temperature is a problem on the temperature sensor side.
Do the temperature sensor type used and the temperature controller settings[In-t] match?
The PID value is not relevant to this issue.
@@AutonicsCorp I have tried replacing the type K thermocouple, and the result remains the same.
how to setting type TK4L-24SN output SSR.
We Setting PID for Temperature Heater Stabil
TK4L-24SN is an SSR drive voltage output product.
So, there is no need for separate settings related to output.
For the PID value, set the set value(SV) and execute Auto-tuning.
@@AutonicsCorp do you have video tutorial execute auto tuning?,
@@muhamadsolehabdillah3124 Unfortunately, there is no video based on the TK series.
However, it is similar to the TCN series auto-tuning method in this video. 01:52
Just set [At] of parameter 2 group from [OFF] to [ON].
@@AutonicsCorp thanks you very much for information.
I Will try
Please i need help it is same way for tcn4w
The TCN4S and TCN4W parameter setting methods are the same.
What problem might you have?
Great
Do you kniw where I can buy this product? Are the ones on aliexpress original or fake?
Visit our website www.autonics.com/company/global. Please check the nearest corporation and contact us. Thank you.
Bagaimana kalau muncul error tpi AL 1 dan AL2 nyala semua. Bagaimana cara mengatasinya
If the alarm operation mode of parameter 2 group is set to [AM0], the alarm output can not be used.
Hello. For recovery password, could you provide me the steps to reset it? I have error 6329.thank you
Could you please check your model name?
T4KM-T4CN
Please try [0516]. If this does not work, please contact us again.
Thank you very much for your support. It is ok now
I write you again because after i did factory reset now is asking again ne to put pass, and i have error 9300