Solar Plant | Power Factor Correction | PF | Calculation

แชร์
ฝัง
  • เผยแพร่เมื่อ 25 พ.ย. 2024

ความคิดเห็น • 176

  • @Solarismypassion
    @Solarismypassion 4 ปีที่แล้ว +9

    Wah, very good👍 explanation

  • @kunal-chandra
    @kunal-chandra 4 ปีที่แล้ว +2

    Expecting more technical contents like this. 👌

  • @avinasht14
    @avinasht14 4 ปีที่แล้ว +2

    A Solar Inverter can also improve the PF by exporting or importing reactive power.
    Many inverters now have this option and some brands like SMA can even compensative reactive power at night.
    Since a solar inverter itself can compensate reactive power then there is no need to install capacitor banks.

    • @sokbok
      @sokbok 2 ปีที่แล้ว

      yes this is an important point not made in the video

  • @RiseUp_Again
    @RiseUp_Again 3 ปีที่แล้ว +1

    Wow, Amazing Information, Thank you Bhaisaheb, Keep-up the Good work.

  • @niaziexplores
    @niaziexplores 3 ปีที่แล้ว +1

    Inverter k andar bhi set point options hoty hain aap ny jis paper sy examples quote ki hain ye cheez bhi usmain mentioned hy but aap ny ye cheez discuss nhi ki? is it possible to control pf through inverter set points e.g if i want to improve the pf and i have installed huawei inverters?

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Inverter will only generate reactive Component , which will maintain your PF quality

  • @greenengineer2130
    @greenengineer2130 4 ปีที่แล้ว +5

    Your explanation is the reason for the question "WHY SOLAR INVERTERS ARE RATED IN KW NOT KVA"

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +2

      That's quite a sharp observation ,

    • @netrocker9990
      @netrocker9990 3 ปีที่แล้ว

      Because solar panels generate dc power,which is measured in kw(no power factor)

    • @036_niket_deshmukh5
      @036_niket_deshmukh5 3 ปีที่แล้ว

      Inverter comes with both ratings
      If refer operating manuals technical details you will get both value kVA and kW
      The provided kW values at this PF 1

    • @036_niket_deshmukh5
      @036_niket_deshmukh5 3 ปีที่แล้ว

      Also for capability of inverter to feed reactive power check parameter power factor displacement

    • @036_niket_deshmukh5
      @036_niket_deshmukh5 3 ปีที่แล้ว

      Most of the SMA inverter more than 10 kW capacity comes with 100% active and reactive power
      Therefore you can either take 100 % active or reactive power but most of other inverters do not have this capability

  • @CATips
    @CATips 4 ปีที่แล้ว

    Ekdam barabar bathadiya bro

  • @arifulislam-tb9qk
    @arifulislam-tb9qk 4 ปีที่แล้ว +1

    The way you explain it's really easy to understand. Thanks brother

  • @rajeshpratapsingh5361
    @rajeshpratapsingh5361 4 ปีที่แล้ว +1

    Mast yaar......

  • @rameshmodi4051
    @rameshmodi4051 3 ปีที่แล้ว +1

    Very informative sir ji

  • @vijayyadav1249
    @vijayyadav1249 3 ปีที่แล้ว +1

    Great👍👍👍👍👍👍himanshu sir.

  • @AvinashSawarbandhe
    @AvinashSawarbandhe 4 ปีที่แล้ว +1

    Very good explanation . Thanks you sir

  • @mukeshnishad1272
    @mukeshnishad1272 4 ปีที่แล้ว +1

    Good job .,....... Sir

  • @shrikantbhaibhosale
    @shrikantbhaibhosale 6 หลายเดือนก่อน

    Very informative video, Thanks dear, I just installed 3.3KW solar, how can i check and correct pf, Pls advice

  • @aizazrahim8313
    @aizazrahim8313 3 ปีที่แล้ว

    You are shining 🌟 .

  • @CATips
    @CATips 4 ปีที่แล้ว +1

    Beer cheers 🔥

  • @abhisheksingh-fu5gz
    @abhisheksingh-fu5gz 4 ปีที่แล้ว

    Ghar me capacitor bank ke jagah voltage stabilizer use kar sakte hai kya 5kw solar system ke liye ya capacitor bank hi lagana parega?

  • @Dummy-qu4fx
    @Dummy-qu4fx 2 หลายเดือนก่อน

    Boss kindly guide if there any PFC device for residential use e.g can attached to inverter output (without battery installed) or will it better if install battery only!

  • @zaidi62
    @zaidi62 3 ปีที่แล้ว +1

    good job, and what about small residential plant it must be get same issue of pf how to control it at home.

  • @mukeshbhardwaj1756
    @mukeshbhardwaj1756 3 ปีที่แล้ว +1

    Very good

  • @kamranshaikh7744
    @kamranshaikh7744 4 ปีที่แล้ว

    It helps a lot to me...

  • @ab-ed1gl
    @ab-ed1gl 3 ปีที่แล้ว

    Learning..❤❤🙏🙏

  • @lokanathbehera8455
    @lokanathbehera8455 4 ปีที่แล้ว

    Very good information sir,,🙏🙏

  • @Prince_Mehedi
    @Prince_Mehedi 2 ปีที่แล้ว

    Amazing 🌼🌼

  • @anand30571
    @anand30571 4 ปีที่แล้ว +1

    Very good explanation, Thank you very very much Sir...

  • @SIGMATICLIGHTS
    @SIGMATICLIGHTS 4 ปีที่แล้ว +1

    Very good explain sir

  • @digitalelectrofast9863
    @digitalelectrofast9863 หลายเดือนก่อน

    Good

  • @sanketbhoi5720
    @sanketbhoi5720 4 ปีที่แล้ว

    Superb explained sir .....thank you so much...

  • @daniyalchiwne4153
    @daniyalchiwne4153 4 ปีที่แล้ว +1

    Excellent. Yar thoda pf ko domestic level pe batao na. Aur thoda sa asan karke. Aur yar agar hum ko 1kv ya 1.5 kv ka solar system lagana hai to what precautions to be taken. Infact its very good if you suggest or recommend which panel.,inverter (pcu) and other accessories to be purchased for domestic level to reduce the electricity bill. Thanking you
    God bless you

  • @dharaskhatana4893
    @dharaskhatana4893 4 ปีที่แล้ว

    Very good information bro....

  • @alimehboob9387
    @alimehboob9387 7 หลายเดือนก่อน

    Solar lagne ke bad apfc panel solar se pehle conect kre ya solar grid conection k bad kre

  • @mayankparmar8518
    @mayankparmar8518 4 ปีที่แล้ว +1

    Good explanation sir.. Thank you

  • @najmuddin123456
    @najmuddin123456 4 ปีที่แล้ว +1

    Nice explation. Please share more vedio on power factor reduction. Thanks

  • @saifsyedmohammad3769
    @saifsyedmohammad3769 ปีที่แล้ว

    should we use capacitor bank for 5kW home solar. my net meter is showing power factor of 0.90

  • @sarikajeswal6016
    @sarikajeswal6016 ปีที่แล้ว

    Very nice explanation

  • @vsksolutions340
    @vsksolutions340 4 ปีที่แล้ว

    Good explanation.

  • @TheSachin6678
    @TheSachin6678 4 ปีที่แล้ว +1

    💥💥💥💥💥💥💥👍👍🤗🤗 again stunning photo छोटे भाई

  • @aizazafzal1996
    @aizazafzal1996 4 ปีที่แล้ว +2

    Great video!
    What if the factory is completely solar powered? how are the required KVar (by factory equipment) supplied? because you mentioned Solar plant gives active power only.

  • @Nareshkumar-px8yc
    @Nareshkumar-px8yc 2 ปีที่แล้ว +1

    What are the reasons of fire in inverter .this activity held in 1mw plant.

  • @talhamalik3353
    @talhamalik3353 ปีที่แล้ว

    i understood what he is saying, my Infini 3kw allows power factor setting which was set at default at 1. this means, should i correct it in my inverter. I have currently set it at 0.97, hope, i dont have to install a capacitive load and inverter now will be producing reactive power.

  • @MananMPatel-xw2gm
    @MananMPatel-xw2gm 4 ปีที่แล้ว +2

    Hello Himanshu You are doing great !
    Please make some videos on stabilizer installation in solar system I am working on it for providing Soalr Inverter we install servo stabilizer in main feed point of Grid. But Sometimes we need to install only in Solar side so in that case I am confusing. So please look in this topic.

  • @SUVROCHAKRABORTY-ig8wt
    @SUVROCHAKRABORTY-ig8wt ปีที่แล้ว

    Sir is it possible to improve the pf of home?
    Please guide or make a video on this topic. Thank you 🙏

  • @kamranatif4692
    @kamranatif4692 2 ปีที่แล้ว

    Good explanation 👍

  • @Rajkumar-ox9tn
    @Rajkumar-ox9tn 4 ปีที่แล้ว +1

    Pl. Make a video on gross metering having load 40 - 90kw with CT connection & wiring diagram

  • @solarfacts4242
    @solarfacts4242 3 ปีที่แล้ว

    Hi sir
    Is there any inverter who can deliver Active and reactive both the power.

  • @shahzadmasood3176
    @shahzadmasood3176 2 ปีที่แล้ว

    THANK GSES POWER FACTER INFORMATION

  • @vrunda_food_diary
    @vrunda_food_diary 4 ปีที่แล้ว

    Nice sir . please tell me dc wire calculation solar system to inverter.and also tell me ac dc wire how much use.

  • @dibyenduchakroborty
    @dibyenduchakroborty 4 ปีที่แล้ว +1

    Bahati acha lecture ha.sir "dot pan" file and "dot ond" file making Ka upor ak video banaya.

  • @abigithbaby
    @abigithbaby 4 ปีที่แล้ว +1

    Nicely explained Himanshu . Keep Going
    However, At 8.16, you have shown a power triangle after installation of SPV System for which you have kept the reactive power same (32.9).
    Doesnt the reactive power also decrease as the power taken from the Grid decreases ? Please do clarify the same

  • @satishsaxena2650
    @satishsaxena2650 4 ปีที่แล้ว +1

    Really Awesome & informative Video Sir.
    Love From Varanasi (Mahakal Ki Nagari)🇮🇳🇮🇳🇮🇳🇮🇳🕉🕉🕉🙏🙏🙏❤❤❤❤♥️❤♥️❤♥️😊😊😊😚😘😍

  • @rukesh8227
    @rukesh8227 2 ปีที่แล้ว

    how you are calculating apparent power?

  • @dharma.vibrates
    @dharma.vibrates ปีที่แล้ว

    Sir household meter reading mein pf .56 hai, solar panel laga rakha hai 5kva ka . Is it ok to have APFC panel for home appliances?

  • @MandeepSingh-ch1qo
    @MandeepSingh-ch1qo 4 ปีที่แล้ว +1

    God bless u dear

  • @salmanjaved4393
    @salmanjaved4393 2 ปีที่แล้ว

    Well done bro.
    Really very fine and quality knowledge you are sharing through your videos.. We love u bro. 😘😘

  • @sajidengr1673
    @sajidengr1673 2 ปีที่แล้ว +1

    But net active power remains the same which is required by the system(100 KW) whether we are taking it from Grid or from Solar plant (40 KW + 60 KW) . Requirement is the same .
    If the required active power decreases from 100 KW to 40 KW then we can say that Power Factor is distorted .

  • @mangeshiyer4711
    @mangeshiyer4711 ปีที่แล้ว

    Nice bro

  • @najmussaquib4536
    @najmussaquib4536 2 ปีที่แล้ว

    Sir You say that our solar plant only generate active power not generate reactive power.
    So can we move active power without the help of reactive power .?

  • @rohitnarola
    @rohitnarola 3 ปีที่แล้ว +1

    Please explain the main control room in large projects

  • @birajtech811
    @birajtech811 3 ปีที่แล้ว

    Thank you sir

  • @samiulhassan6706
    @samiulhassan6706 6 หลายเดือนก่อน

    AoA
    Bro hum ny industry ma pf manage karny k liye Huawei inverter py pf .88 set kar dia ha
    Lakin uss sy kwh production kam ho gai ha
    Kya ye sahi ha ?

  • @MrMechdevil007
    @MrMechdevil007 4 ปีที่แล้ว +1

    Explanation bahut hi Badhiya ..
    Share views OR make a video on Night time SVG !

  • @AnandSingh-ty4tl
    @AnandSingh-ty4tl 3 ปีที่แล้ว

    How to calculate exact value of extra value of capacitor bank need to insert for pf improvment.

  • @deepalps
    @deepalps 3 ปีที่แล้ว

    did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power

  • @ramasuperstar
    @ramasuperstar 4 ปีที่แล้ว

    Thanks

  • @saadshamsi1148
    @saadshamsi1148 3 หลายเดือนก่อน

    Thank you

  • @vjkmbj
    @vjkmbj 3 ปีที่แล้ว +1

    According to example: after solar installation p.f. is 0.77 (Bad Quality). How to improve this.

  • @sarbjit668
    @sarbjit668 4 ปีที่แล้ว +1

    Hello sir how to maintain at the home PF when using solor power

  • @Ramgadade2002
    @Ramgadade2002 ปีที่แล้ว

    Thank you sir bhohot kuch information mili sir thank so much

  • @hkeengineeringservices2032
    @hkeengineeringservices2032 3 ปีที่แล้ว +1

    If different Amps on loads p.f also low?

  • @faisalchhavani5701
    @faisalchhavani5701 4 ปีที่แล้ว

    Sir can you please explain how to calculate apperant power i did'nt understand the power triangle calculation

  • @CATips
    @CATips 4 ปีที่แล้ว

    THD AND FLICKERING VIDEOS BENAVO BRO......👍

  • @nabeelanwar4840
    @nabeelanwar4840 ปีที่แล้ว

    Hello Himanshu,
    Hope you are doing well.
    I am facing issue in one of my solar project..it's a KIA Motors Service Center plus showroom.we have installed 50kw sungrow inverter with 63kw solar panels.they have their own PFI..when we are connecting our solar with their main power our solar main AC breaker trips..I just want to know, is it possible that this is because of PFI? It seems like their load is less and their minimum size capacitor is of 12.5kvar rating and maximum of 50kvar..with the discharge of that smallest one, the excess power reserve to our solar breaker and cause it's trip...is it possible?if I am wrong please correct me.
    Thank you

  • @vickybhui1878
    @vickybhui1878 4 ปีที่แล้ว +1

    Hello bro tell me about solar optmizer

  • @nageshk9100
    @nageshk9100 4 ปีที่แล้ว

    Very good bro ooo😍

  • @bhupeshshakya4686
    @bhupeshshakya4686 4 ปีที่แล้ว

    How to maintain power factor while using domestic rooftop solar plant?

  • @RohitSingh-yl7jz
    @RohitSingh-yl7jz 4 ปีที่แล้ว +1

    please explain active power,reactive power and apparent power in detail

  • @furqanhamid9578
    @furqanhamid9578 9 หลายเดือนก่อน

    As of my knowledge, the reactive power is generated from our load not received from the utility. The utility imposes fines for the lower power factor forcing us to improve. 4:35

  • @electricalexplained
    @electricalexplained 4 ปีที่แล้ว

    Sir, thanks for making video on pf. But video was very basic. I thought u would focus more on harmonics as Solar plant produces 30-35% Thd which disrupts the existing Apfc & hence affects energy consumption + equipments.
    Lastly a very interesting question:
    I measure Solar pf from AC o/p of Inverter it was 0.96, So I my clients only consumes solar generated kwh, how will it affect overall pf?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Yes part 2 I m covering the Harmonic testing process

  • @mohitaloriya9645
    @mohitaloriya9645 4 ปีที่แล้ว

    Sir ji mai aapse ek question poochna chatha ho solar power plant ham installation karthe h heme kase pata hona chiye ki ( A C D B box kitne mpyer ki MCCB lagaye lagna chiye ye bato ya video bano sir ji plz plz plz

  • @mahendraraikwar5188
    @mahendraraikwar5188 2 ปีที่แล้ว

    Sir ji apne ye nhi bataya power factor ko improve kese karte he solar se koi load chal raha ho to....Or sir jab night me solar work na kare to us condition me bhi power factor par effect aata he..🤔

  • @arvindchauhanlife5516
    @arvindchauhanlife5516 4 ปีที่แล้ว +1

    Sir Himanshu 🇮🇳👍

  • @mukeshnishad1272
    @mukeshnishad1272 4 ปีที่แล้ว

    Sir ..........Please provide the angle meter app link

  • @akashprajapati4553
    @akashprajapati4553 4 ปีที่แล้ว +1

    Bhai inverter ka AC plug damage ho gaya hai...how can repair it ?...

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Warranty service kitni hai?

    • @akashprajapati4553
      @akashprajapati4553 4 ปีที่แล้ว

      Delta company bt warranty expires...2014 installed

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      @@akashprajapati4553 then buy the component from delta service , or book a paid service , you can't fix it on your own , spare is only provided by delta

  • @frassmazhar8757
    @frassmazhar8757 3 ปีที่แล้ว

    I have installed a solar inverter in off grid system. When there is no load connected inverter shows an apparent power of 250 VA and active power of 0 watt. Please give any solution

  • @aizazrahim8313
    @aizazrahim8313 2 ปีที่แล้ว

    Bhai, agar KW grid se kam ho gia to KVARbb kam hona chahye tha.

  • @Vijayukale
    @Vijayukale 4 ปีที่แล้ว

    Agar grid se power consumption kam ho gaya to reactive power kam nhi hogi kya??

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Yes

    • @Vijayukale
      @Vijayukale 4 ปีที่แล้ว

      Lekin aapne to example me kvar 32.9 hi liya h jab ki power 100kw se 40kw ho gayi h.. Please explain.. Becoz I am on a site where they company face a leading power factor problem at factory no load condition..

  • @rishabjaiswal235
    @rishabjaiswal235 4 ปีที่แล้ว

    Sir how to decide how much kvar capacitor bank to be installed? to compensate between two supply 1. Discom 2. Solar.

  • @DebjitDas93
    @DebjitDas93 4 ปีที่แล้ว

    Sir, how pf is maintained at MW scale Solar plant? Is it done by the inverters?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      See there is very small inductive load or self consumption to disturb the PF of system

  • @neerajserohi2394
    @neerajserohi2394 3 ปีที่แล้ว

    You have explained why solar power reduces PF. How would one improve the power factor subsequently ?

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      By increasing the reactive Component in Inverter this feature is now available in Inverter , and by using good quality Capacitor bank

  • @dranilbehal9424
    @dranilbehal9424 3 ปีที่แล้ว

    How to calculate reactive power?

  • @shateesh2841
    @shateesh2841 4 ปีที่แล้ว

    Hi... How to improve power factor in my site I have E B power 112 KW solar plant 72 KW and I have capacitor bank in my power room

    • @shateesh2841
      @shateesh2841 4 ปีที่แล้ว

      PF for EB import Power factor 0.636
      Solar Export Power factor 0.950 So how to improve my import Power factor

  • @aeframferrao1285
    @aeframferrao1285 4 ปีที่แล้ว

    Thank you very much for your valuable information, could you please inform me what capacity of capacitor bank to be used/For How much panel solar wattage with houseload (1/ 2 / 3 / 4/ 5 Kw ) capacitor value with complete diagram,Thank you very much for your effort used,God bless you

    • @deepalps
      @deepalps 3 ปีที่แล้ว

      did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power

  • @dkmanna
    @dkmanna 4 ปีที่แล้ว

    Sir capacitor bank can't maintain grid PF when we install solar power plant, we can maintain it from Inverter site to add reactive power settings.

    • @greenengineer2130
      @greenengineer2130 4 ปีที่แล้ว

      Capacitor bank maintain load PF. Yes branded Inverters do have KVAR settings.

    • @dkmanna
      @dkmanna 4 ปีที่แล้ว

      @@greenengineer2130 how can Capacitor bank maintain a variable load?

    • @greenengineer2130
      @greenengineer2130 4 ปีที่แล้ว

      @@dkmanna its a variable capacitor bank which works as per load pf condition.

    • @dkmanna
      @dkmanna 4 ปีที่แล้ว

      @@greenengineer2130 your linkedin id please?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Check discription

  • @amanlodha332
    @amanlodha332 4 ปีที่แล้ว +2

    Hum inverter ki settings se bhi correct kr skte hai 😉 👍

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Corret

    • @MOHIT852
      @MOHIT852 3 ปีที่แล้ว

      Please tell me inverter ki settings se kaise correct kr skte h?
      I've installed 56kw SPV with 80kw polycab inverter and it's commissioned 5days ago
      Lekin tbse hi factory ka PF 0.98 se gir k 0.86 Aa gya h
      Please help

  • @danispervez4793
    @danispervez4793 4 หลายเดือนก่อน

    very nice video but what is solution

  • @jessew6757
    @jessew6757 2 ปีที่แล้ว

    Can you do an English version ?

  • @jeelectrical5123
    @jeelectrical5123 3 ปีที่แล้ว

    Sir hamre yaha 200kva ka on grid solar plant laga hi we hamra ac side me 400 amp ki mccb ko trip karra hi

  • @navyasolpowersolution6810
    @navyasolpowersolution6810 3 ปีที่แล้ว

    Reactive power kese nikale

  • @mdrezaulkarim6018
    @mdrezaulkarim6018 3 ปีที่แล้ว +1

    Hamara gharme power factor .75 arah Hain sir plz solve calculation

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Ghar ka PF itna he hota hai , and there is no penalty for it

  • @sajidbhagat1927
    @sajidbhagat1927 4 ปีที่แล้ว

    Sir i have completed BE Electronics m I eligible for This field or only electrical engg are eligible ????