A Solar Inverter can also improve the PF by exporting or importing reactive power. Many inverters now have this option and some brands like SMA can even compensative reactive power at night. Since a solar inverter itself can compensate reactive power then there is no need to install capacitor banks.
Inverter k andar bhi set point options hoty hain aap ny jis paper sy examples quote ki hain ye cheez bhi usmain mentioned hy but aap ny ye cheez discuss nhi ki? is it possible to control pf through inverter set points e.g if i want to improve the pf and i have installed huawei inverters?
Most of the SMA inverter more than 10 kW capacity comes with 100% active and reactive power Therefore you can either take 100 % active or reactive power but most of other inverters do not have this capability
Boss kindly guide if there any PFC device for residential use e.g can attached to inverter output (without battery installed) or will it better if install battery only!
Excellent. Yar thoda pf ko domestic level pe batao na. Aur thoda sa asan karke. Aur yar agar hum ko 1kv ya 1.5 kv ka solar system lagana hai to what precautions to be taken. Infact its very good if you suggest or recommend which panel.,inverter (pcu) and other accessories to be purchased for domestic level to reduce the electricity bill. Thanking you God bless you
Great video! What if the factory is completely solar powered? how are the required KVar (by factory equipment) supplied? because you mentioned Solar plant gives active power only.
i understood what he is saying, my Infini 3kw allows power factor setting which was set at default at 1. this means, should i correct it in my inverter. I have currently set it at 0.97, hope, i dont have to install a capacitive load and inverter now will be producing reactive power.
Hello Himanshu You are doing great ! Please make some videos on stabilizer installation in solar system I am working on it for providing Soalr Inverter we install servo stabilizer in main feed point of Grid. But Sometimes we need to install only in Solar side so in that case I am confusing. So please look in this topic.
Nicely explained Himanshu . Keep Going However, At 8.16, you have shown a power triangle after installation of SPV System for which you have kept the reactive power same (32.9). Doesnt the reactive power also decrease as the power taken from the Grid decreases ? Please do clarify the same
But net active power remains the same which is required by the system(100 KW) whether we are taking it from Grid or from Solar plant (40 KW + 60 KW) . Requirement is the same . If the required active power decreases from 100 KW to 40 KW then we can say that Power Factor is distorted .
Sir You say that our solar plant only generate active power not generate reactive power. So can we move active power without the help of reactive power .?
did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power
Hello Himanshu, Hope you are doing well. I am facing issue in one of my solar project..it's a KIA Motors Service Center plus showroom.we have installed 50kw sungrow inverter with 63kw solar panels.they have their own PFI..when we are connecting our solar with their main power our solar main AC breaker trips..I just want to know, is it possible that this is because of PFI? It seems like their load is less and their minimum size capacitor is of 12.5kvar rating and maximum of 50kvar..with the discharge of that smallest one, the excess power reserve to our solar breaker and cause it's trip...is it possible?if I am wrong please correct me. Thank you
As of my knowledge, the reactive power is generated from our load not received from the utility. The utility imposes fines for the lower power factor forcing us to improve. 4:35
Sir, thanks for making video on pf. But video was very basic. I thought u would focus more on harmonics as Solar plant produces 30-35% Thd which disrupts the existing Apfc & hence affects energy consumption + equipments. Lastly a very interesting question: I measure Solar pf from AC o/p of Inverter it was 0.96, So I my clients only consumes solar generated kwh, how will it affect overall pf?
Sir ji mai aapse ek question poochna chatha ho solar power plant ham installation karthe h heme kase pata hona chiye ki ( A C D B box kitne mpyer ki MCCB lagaye lagna chiye ye bato ya video bano sir ji plz plz plz
Sir ji apne ye nhi bataya power factor ko improve kese karte he solar se koi load chal raha ho to....Or sir jab night me solar work na kare to us condition me bhi power factor par effect aata he..🤔
@@akashprajapati4553 then buy the component from delta service , or book a paid service , you can't fix it on your own , spare is only provided by delta
I have installed a solar inverter in off grid system. When there is no load connected inverter shows an apparent power of 250 VA and active power of 0 watt. Please give any solution
Lekin aapne to example me kvar 32.9 hi liya h jab ki power 100kw se 40kw ho gayi h.. Please explain.. Becoz I am on a site where they company face a leading power factor problem at factory no load condition..
Thank you very much for your valuable information, could you please inform me what capacity of capacitor bank to be used/For How much panel solar wattage with houseload (1/ 2 / 3 / 4/ 5 Kw ) capacitor value with complete diagram,Thank you very much for your effort used,God bless you
did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power
Please tell me inverter ki settings se kaise correct kr skte h? I've installed 56kw SPV with 80kw polycab inverter and it's commissioned 5days ago Lekin tbse hi factory ka PF 0.98 se gir k 0.86 Aa gya h Please help
Wah, very good👍 explanation
Thanks for the support
Beneficial information
Expecting more technical contents like this. 👌
A Solar Inverter can also improve the PF by exporting or importing reactive power.
Many inverters now have this option and some brands like SMA can even compensative reactive power at night.
Since a solar inverter itself can compensate reactive power then there is no need to install capacitor banks.
yes this is an important point not made in the video
Wow, Amazing Information, Thank you Bhaisaheb, Keep-up the Good work.
Thanks for the support
Inverter k andar bhi set point options hoty hain aap ny jis paper sy examples quote ki hain ye cheez bhi usmain mentioned hy but aap ny ye cheez discuss nhi ki? is it possible to control pf through inverter set points e.g if i want to improve the pf and i have installed huawei inverters?
Inverter will only generate reactive Component , which will maintain your PF quality
Your explanation is the reason for the question "WHY SOLAR INVERTERS ARE RATED IN KW NOT KVA"
That's quite a sharp observation ,
Because solar panels generate dc power,which is measured in kw(no power factor)
Inverter comes with both ratings
If refer operating manuals technical details you will get both value kVA and kW
The provided kW values at this PF 1
Also for capability of inverter to feed reactive power check parameter power factor displacement
Most of the SMA inverter more than 10 kW capacity comes with 100% active and reactive power
Therefore you can either take 100 % active or reactive power but most of other inverters do not have this capability
Ekdam barabar bathadiya bro
The way you explain it's really easy to understand. Thanks brother
Thanks for the support
Mast yaar......
Thanks for the support
Very informative sir ji
Thanks for the support
Great👍👍👍👍👍👍himanshu sir.
Thanks for the support
Very good explanation . Thanks you sir
Thanks for the support
Good job .,....... Sir
Thanks for the support
Very informative video, Thanks dear, I just installed 3.3KW solar, how can i check and correct pf, Pls advice
You are shining 🌟 .
Beer cheers 🔥
Ghar me capacitor bank ke jagah voltage stabilizer use kar sakte hai kya 5kw solar system ke liye ya capacitor bank hi lagana parega?
Boss kindly guide if there any PFC device for residential use e.g can attached to inverter output (without battery installed) or will it better if install battery only!
good job, and what about small residential plant it must be get same issue of pf how to control it at home.
By changing the reactive power settings
Very good
Thanks for the support
It helps a lot to me...
Learning..❤❤🙏🙏
Very good information sir,,🙏🙏
Amazing 🌼🌼
Very good explanation, Thank you very very much Sir...
Thanks Anand
Very good explain sir
Thanks for the support
Good
Superb explained sir .....thank you so much...
Excellent. Yar thoda pf ko domestic level pe batao na. Aur thoda sa asan karke. Aur yar agar hum ko 1kv ya 1.5 kv ka solar system lagana hai to what precautions to be taken. Infact its very good if you suggest or recommend which panel.,inverter (pcu) and other accessories to be purchased for domestic level to reduce the electricity bill. Thanking you
God bless you
Very good information bro....
Solar lagne ke bad apfc panel solar se pehle conect kre ya solar grid conection k bad kre
Good explanation sir.. Thank you
Thanks for the support
Nice explation. Please share more vedio on power factor reduction. Thanks
Sure
should we use capacitor bank for 5kW home solar. my net meter is showing power factor of 0.90
Very nice explanation
Good explanation.
💥💥💥💥💥💥💥👍👍🤗🤗 again stunning photo छोटे भाई
Thanks
Great video!
What if the factory is completely solar powered? how are the required KVar (by factory equipment) supplied? because you mentioned Solar plant gives active power only.
By making grid code settings in the inverter
What are the reasons of fire in inverter .this activity held in 1mw plant.
Overheating
i understood what he is saying, my Infini 3kw allows power factor setting which was set at default at 1. this means, should i correct it in my inverter. I have currently set it at 0.97, hope, i dont have to install a capacitive load and inverter now will be producing reactive power.
Hello Himanshu You are doing great !
Please make some videos on stabilizer installation in solar system I am working on it for providing Soalr Inverter we install servo stabilizer in main feed point of Grid. But Sometimes we need to install only in Solar side so in that case I am confusing. So please look in this topic.
Sure noted
Sir is it possible to improve the pf of home?
Please guide or make a video on this topic. Thank you 🙏
Good explanation 👍
Thanks for the support
Pl. Make a video on gross metering having load 40 - 90kw with CT connection & wiring diagram
Hi sir
Is there any inverter who can deliver Active and reactive both the power.
ABB & Ingeteam
THANK GSES POWER FACTER INFORMATION
Nice sir . please tell me dc wire calculation solar system to inverter.and also tell me ac dc wire how much use.
Bahati acha lecture ha.sir "dot pan" file and "dot ond" file making Ka upor ak video banaya.
Definitely
Nicely explained Himanshu . Keep Going
However, At 8.16, you have shown a power triangle after installation of SPV System for which you have kept the reactive power same (32.9).
Doesnt the reactive power also decrease as the power taken from the Grid decreases ? Please do clarify the same
Really Awesome & informative Video Sir.
Love From Varanasi (Mahakal Ki Nagari)🇮🇳🇮🇳🇮🇳🇮🇳🕉🕉🕉🙏🙏🙏❤❤❤❤♥️❤♥️❤♥️😊😊😊😚😘😍
Thanks for the support
how you are calculating apparent power?
Sir household meter reading mein pf .56 hai, solar panel laga rakha hai 5kva ka . Is it ok to have APFC panel for home appliances?
God bless u dear
Thanks for the support
Well done bro.
Really very fine and quality knowledge you are sharing through your videos.. We love u bro. 😘😘
Thanks for the support
But net active power remains the same which is required by the system(100 KW) whether we are taking it from Grid or from Solar plant (40 KW + 60 KW) . Requirement is the same .
If the required active power decreases from 100 KW to 40 KW then we can say that Power Factor is distorted .
Nice bro
Sir You say that our solar plant only generate active power not generate reactive power.
So can we move active power without the help of reactive power .?
Please explain the main control room in large projects
Sure soon
Thank you sir
AoA
Bro hum ny industry ma pf manage karny k liye Huawei inverter py pf .88 set kar dia ha
Lakin uss sy kwh production kam ho gai ha
Kya ye sahi ha ?
Explanation bahut hi Badhiya ..
Share views OR make a video on Night time SVG !
Definitely
How to calculate exact value of extra value of capacitor bank need to insert for pf improvment.
did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power
Thanks
Thank you
According to example: after solar installation p.f. is 0.77 (Bad Quality). How to improve this.
By installation of Capacitor bank
Hello sir how to maintain at the home PF when using solor power
Use less inductive load
Thank you sir bhohot kuch information mili sir thank so much
If different Amps on loads p.f also low?
Obviously any deflection will affect PF
@@SustainableEveryDay thanks
Different Amps on 3 phase loads r effecting P.F
Sir can you please explain how to calculate apperant power i did'nt understand the power triangle calculation
THD AND FLICKERING VIDEOS BENAVO BRO......👍
Hello Himanshu,
Hope you are doing well.
I am facing issue in one of my solar project..it's a KIA Motors Service Center plus showroom.we have installed 50kw sungrow inverter with 63kw solar panels.they have their own PFI..when we are connecting our solar with their main power our solar main AC breaker trips..I just want to know, is it possible that this is because of PFI? It seems like their load is less and their minimum size capacitor is of 12.5kvar rating and maximum of 50kvar..with the discharge of that smallest one, the excess power reserve to our solar breaker and cause it's trip...is it possible?if I am wrong please correct me.
Thank you
Hello bro tell me about solar optmizer
Sure very soon
Very good bro ooo😍
How to maintain power factor while using domestic rooftop solar plant?
please explain active power,reactive power and apparent power in detail
Sure very soon
As of my knowledge, the reactive power is generated from our load not received from the utility. The utility imposes fines for the lower power factor forcing us to improve. 4:35
Sir, thanks for making video on pf. But video was very basic. I thought u would focus more on harmonics as Solar plant produces 30-35% Thd which disrupts the existing Apfc & hence affects energy consumption + equipments.
Lastly a very interesting question:
I measure Solar pf from AC o/p of Inverter it was 0.96, So I my clients only consumes solar generated kwh, how will it affect overall pf?
Yes part 2 I m covering the Harmonic testing process
Sir ji mai aapse ek question poochna chatha ho solar power plant ham installation karthe h heme kase pata hona chiye ki ( A C D B box kitne mpyer ki MCCB lagaye lagna chiye ye bato ya video bano sir ji plz plz plz
Sir ji apne ye nhi bataya power factor ko improve kese karte he solar se koi load chal raha ho to....Or sir jab night me solar work na kare to us condition me bhi power factor par effect aata he..🤔
Sir Himanshu 🇮🇳👍
Thanks Arvind
Sir ..........Please provide the angle meter app link
Bhai inverter ka AC plug damage ho gaya hai...how can repair it ?...
Warranty service kitni hai?
Delta company bt warranty expires...2014 installed
@@akashprajapati4553 then buy the component from delta service , or book a paid service , you can't fix it on your own , spare is only provided by delta
I have installed a solar inverter in off grid system. When there is no load connected inverter shows an apparent power of 250 VA and active power of 0 watt. Please give any solution
Bhai, agar KW grid se kam ho gia to KVARbb kam hona chahye tha.
Agar grid se power consumption kam ho gaya to reactive power kam nhi hogi kya??
Yes
Lekin aapne to example me kvar 32.9 hi liya h jab ki power 100kw se 40kw ho gayi h.. Please explain.. Becoz I am on a site where they company face a leading power factor problem at factory no load condition..
Sir how to decide how much kvar capacitor bank to be installed? to compensate between two supply 1. Discom 2. Solar.
Sir, how pf is maintained at MW scale Solar plant? Is it done by the inverters?
See there is very small inductive load or self consumption to disturb the PF of system
You have explained why solar power reduces PF. How would one improve the power factor subsequently ?
By increasing the reactive Component in Inverter this feature is now available in Inverter , and by using good quality Capacitor bank
How to calculate reactive power?
Hi... How to improve power factor in my site I have E B power 112 KW solar plant 72 KW and I have capacitor bank in my power room
PF for EB import Power factor 0.636
Solar Export Power factor 0.950 So how to improve my import Power factor
Thank you very much for your valuable information, could you please inform me what capacity of capacitor bank to be used/For How much panel solar wattage with houseload (1/ 2 / 3 / 4/ 5 Kw ) capacitor value with complete diagram,Thank you very much for your effort used,God bless you
did u get some solution, I am facing the same problem.........where to place the CT with integrated systems of PV solar and utility. our system consumes 300KVA and solar panels provide only 200KW , the pf goes down specially when our utility is not consuming power
Sir capacitor bank can't maintain grid PF when we install solar power plant, we can maintain it from Inverter site to add reactive power settings.
Capacitor bank maintain load PF. Yes branded Inverters do have KVAR settings.
@@greenengineer2130 how can Capacitor bank maintain a variable load?
@@dkmanna its a variable capacitor bank which works as per load pf condition.
@@greenengineer2130 your linkedin id please?
Check discription
Hum inverter ki settings se bhi correct kr skte hai 😉 👍
Corret
Please tell me inverter ki settings se kaise correct kr skte h?
I've installed 56kw SPV with 80kw polycab inverter and it's commissioned 5days ago
Lekin tbse hi factory ka PF 0.98 se gir k 0.86 Aa gya h
Please help
very nice video but what is solution
Can you do an English version ?
Sir hamre yaha 200kva ka on grid solar plant laga hi we hamra ac side me 400 amp ki mccb ko trip karra hi
Inverter to MCCB , Cable distance kitna hai?
@@SustainableEveryDay 100 meter
Reactive power kese nikale
Hamara gharme power factor .75 arah Hain sir plz solve calculation
Ghar ka PF itna he hota hai , and there is no penalty for it
Sir i have completed BE Electronics m I eligible for This field or only electrical engg are eligible ????