Fixing an Illegal S Trap with In Line Vent AAV and P Trap

แชร์
ฝัง
  • เผยแพร่เมื่อ 12 ก.ย. 2024
  • I walk through how I fixed an illegal S trap setup with an inline vent, also called an AAV (air admittance valve), for drainage in a laundry room with a sink.

ความคิดเห็น • 17

  • @noelburke6224
    @noelburke6224 ปีที่แล้ว +8

    This is the wrong way to install a vent the vent should terminate 13 inches above the flood level of the sink.This information is from a master plumber

    • @jacksplumbingvideos7147
      @jacksplumbingvideos7147 6 หลายเดือนก่อน +7

      Those vent valves dont need to be above the flood level at least in my area, most manufacturers just say a minimum of 5 inches above the tee.

    • @legolwa
      @legolwa 5 หลายเดือนก่อน

      @@jacksplumbingvideos7147 my code says 4" above the tee.

  • @modarm
    @modarm ปีที่แล้ว +5

    Not a lot of space above the vent to unscrew if you ever needed to replace the unit from what I could see in the video.

  • @MrTinks01
    @MrTinks01 11 หลายเดือนก่อน +5

    When was the original installed??.. if before no S traps allowed -it is legal. No code ever says to go back and update any system installed under a prior code or no code. You only have to meet the current code on anything installed at that time.

    • @2011Maynard
      @2011Maynard 5 หลายเดือนก่อน +1

      Not always true… if just replacing the trap, maybe. If remodeling - must meet code!!!

    • @kw6713a
      @kw6713a หลายเดือนก่อน

      My house has several grandfathered s traps and no issues

  • @2011Maynard
    @2011Maynard 5 หลายเดือนก่อน +1

    Don’t take the distance-above the Tee as being gospel. Check your local codes to ensure that distance above is above-flood or above-tee. You will fail inspection and could have problems filing insurance damage claims for overflow flooding if not done properly.

  • @nedflanders1559
    @nedflanders1559 14 วันที่ผ่านมา

    Good info. Thanks! One question... you, and others, say these AAVs wear out and may need to be replaced from time to time. How would one know if their AAV is not functioning properly, or is worn out?

    • @VincentStevenson
      @VincentStevenson  14 วันที่ผ่านมา

      If you start smelling sewer gases, then it means it aav isn’t blocking them anymore and you should replace it

  • @paulmiller6277
    @paulmiller6277 ปีที่แล้ว +2

    It can every where else in the world America must have different water to rest of us

  • @jeromewelch7409
    @jeromewelch7409 11 หลายเดือนก่อน +1

    Wait a minute? You're advocating this is a fix? Looks like you're doing a pretty extensive rehab. You have the walls open seems you're in the basement as the pipe terminates to concrete so you have access to this vent, but failed to connect to it through any and all means. You're leaving the ferco tee which appears to be inside of wall. where is this 4 inches that you mentioned coming from at least 4 inches? you need to be 12 inches above the rim of the flood zone? Which in your case is top of your washing machine trap arm which absolutely needs to be 2 inch in size you will not like the results of leaving that vent in that location where you're clearly draining the washing machine above the point of vent… your washing machine is going to discharging! Out of your vent!!!!….. DoDYI

  • @ragtop63
    @ragtop63 11 หลายเดือนก่อน +1

    When you say "illegal", do you mean illegal in CA?

    • @legolwa
      @legolwa 5 หลายเดือนก่อน +1

      An s-trap is no longer legal in the USA

  • @bradjenkins932
    @bradjenkins932 4 หลายเดือนก่อน

    It's not illegal.... The vent must be 6" above sink!!

  • @SloverOfTeuth
    @SloverOfTeuth ปีที่แล้ว

    Very helpful thanks. If one instead used an open external vent pipe, what's the minimum height it needs to run to please?

    • @VincentStevenson
      @VincentStevenson  ปีที่แล้ว +4

      If the vent pipe doesn’t have an AAV on the end of it then you’re supposed to have it vent above the roof so any sewer gases are not going into your home.