When One PA fan trips in this situation top most mill will get trip immediately after that after every 5 second from top mill will get trip command till 4 Mills left in service, but meanwhile this action if PA HDR pressure drops below 500 mmwc in that case all pulverisers will trip and loss of all fuiel initiate evantualy Boiler MFT occurred.
🎉🎉🎉
Sir please provide videos from basic overview of thermal power plant.
Sure
Sir please provide China plant vedio & different between Super critical Boiler & Sub critical Boiler
Today I am going to upload
Aesi I'D, FD KA BNAYE
Sir, lube oil skid me filter kis type ka hota hai.
25 microns size
sir, there will be another reading called "RED PR" what is meant by this ???
two PA fans are working, suddenly one PA fan has tripped
Then what will happen?
Just tell me about mills and load (8 mills are in working)
When One PA fan trips in this situation top most mill will get trip immediately after that after every 5 second from top mill will get trip command till 4 Mills left in service, but meanwhile this action if PA HDR pressure drops below 500 mmwc in that case all pulverisers will trip and loss of all fuiel initiate evantualy Boiler MFT occurred.