Diagnosing Daikin U0 Error

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 พ.ย. 2024

ความคิดเห็น • 47

  • @CodyHVAC
    @CodyHVAC 2 ปีที่แล้ว +5

    Hey Mitch what Aircons would you recommend a AC installer to install for their customers I’m guessing daikin would be your favourite? Any other ones? I was looking at GREE, Samsung and Haier just because of the cheaper cost to purchase.

    • @maracservices
      @maracservices  2 ปีที่แล้ว +2

      I like Daikin and Panasonic mate. I’m more familiar with Daikin but I like Panasonic after sales support way better. If it’s a ducted, I like Daikin because you can dismantle the indoor units whereas a lot of other brands you can’t.

    • @CodyHVAC
      @CodyHVAC 2 ปีที่แล้ว

      @@maracservices ok cheers Mitch I’ll look into Panasonic and daikin

    • @alexalicia5686
      @alexalicia5686 12 วันที่ผ่านมา

      Best is a Mitsubishi heavy industrial

  • @16valve64
    @16valve64 3 ปีที่แล้ว +2

    Thanks a lot sir..tace care always

  • @Smohamed5779
    @Smohamed5779 2 ปีที่แล้ว +3

    brother..we have diking unit...duct type..it showing..UO ...there is no leak found..gass is ok....but the issue when we put temperature 24 its working continues ..but when we put temperature 16..out door will off and showing ...uo...we have change...3 outdoors....same issue.and indoor..boards..pls can u ..give me a i dea abou this

    • @maracservices
      @maracservices  2 ปีที่แล้ว +1

      If you’re 100% sure the refrigerant charge is correct (you reclaimed all the existing gas in recovery mode and weighed the exact amount specified back in) then I would definitely be testing the Electronic Expansion Valve to make sure it works. I’d also be testing the low pressure transducer and thermistors. One of those things is causing the issue. If all those things are working fine, then the only other thing I can think of is there is a blockage in the lineset. Good luck!

    • @Smohamed5779
      @Smohamed5779 2 ปีที่แล้ว +1

      thank u brother

  • @b.r5198
    @b.r5198 ปีที่แล้ว +1

    Hey bro,What's tools did u use for running comp?

  • @MMWA-DAVE
    @MMWA-DAVE 2 ปีที่แล้ว +1

    Is the leak detector always pulled out for the Daikins? I have a 2018 built wall hung split thats had poor cooling performance all summer long this year and finally quit with the dreaded U0 code. i’m going to replace the piece of rubbish with Mitsubishi heavy industries version. Tell me i’m not buying another piece of crap please, or recommend a decent brand that doesn’t engineer their products to last the warranty period only.

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      It’s a tough one because the leak could legitimately be in the lineset and nothing to do with the Daikin unit. In that case, the U0 code is justifiable because the unit is just protecting itself. If it is Daikin, they should repair under warranty. Maybe try Toshiba, I heard they give 7 year warrant now. I’d definitely pressure test the lineset before installing the new unit though.

    • @MMWA-DAVE
      @MMWA-DAVE 2 ปีที่แล้ว +1

      @@maracservices Cheers. Plan is to throw out the lines snd have a completely new install performed. Luckily its just about back to back so no big deal. Where ever the leak is its very small, ive gone over everything with soap spray and seen no bubbles including inside the roof on a 40c day and sprayed the flare nut connections on the inside unit too 😎

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      @@MMWA-DAVE just out of curiosity, did you increase the pressure within the system before looking for the leak with bubbles? In regards to Mitsubishi Heavy Industries, iv only ever installed a few of them before and they all worked well.

    • @MMWA-DAVE
      @MMWA-DAVE 2 ปีที่แล้ว +2

      @@maracservices Nah, it was just running in normal operation mode. I dont have any dry nitrogen. BTW, my ac on the job experience totals about 3 months when 17 then quit and moved into IT. I couldn’t handle the roof spaces in summer. I never got an arc license, but still tinker with old car aircon systems, rebuilding, vacuuming and charging with hychill. For us non licensed plebs this stuff works great, havent had a single rebuilt system leak yet.

    • @MMWA-DAVE
      @MMWA-DAVE 2 ปีที่แล้ว

      @@maracservices just to clarify, the daikin was professionally installed, not by me.

  • @mohammedislam998
    @mohammedislam998 2 ปีที่แล้ว +1

    When I fill up the frozen Do I have to have the AC on

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      No, you can gas it up when the system is off.

  • @frankajlouni2306
    @frankajlouni2306 2 ปีที่แล้ว +2

    So it’s giving me the same error code but Refrigerant level is good , I heard you saying it could be the sensors which ones exactly?

    • @maracservices
      @maracservices  2 ปีที่แล้ว +2

      U0 fault means the Suction Pipe Temperature is too high. So if the Suction Pipe Thermistor is faulty it can trigger a U0 fault even if there is enough refrigerant. These things don’t have LP switches anymore. They just go off that one thermistor.

  • @kellyrichardson217
    @kellyrichardson217 ปีที่แล้ว

    Hey Mitch, I have the same unit!with the same issue. Just curious did you ever find the leak and if so what was it?

  • @DugiDevetCarabolium
    @DugiDevetCarabolium 3 หลายเดือนก่อน +2

    Daikin the worst, i have this problem every year, calling service to fix it every time, they fix and next year again.
    Definitive solution is to throw whole device in the garbage and buy new one but not Daikin....

  • @superunknown8775
    @superunknown8775 3 ปีที่แล้ว +2

    Did you find the leak..?

    • @maracservices
      @maracservices  3 ปีที่แล้ว +1

      To be honest mate, I’m yet to go back to that job. I’ll definitely be going back, I’m just waiting on them to get back from holidays.
      Interestingly the system hasn’t missed a beat since (so it’s obviously a slow leak). I’m due to go back there this week or next to sort it out. I’ll be taking my leak detector this time.

    • @yuhaogu4744
      @yuhaogu4744 2 ปีที่แล้ว +1

      @@maracservices we've got a daikin multi split system in an apartment that from time to time shows U0. Evidently there is a leak but have not been able to locate it. Can you do some magic?

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      @@yuhaogu4744 Does the unit blow nice cold air when it works? The reason I ask is, if the fault only happens every so often, then it sounds to me like it’s more likely to be a faulty thermistor or faulty pressure sensor as opposed to a refrigerant leak.

    • @yuhaogu4744
      @yuhaogu4744 2 ปีที่แล้ว +1

      @@maracservices it's been an issue for a number of years. U0, light flashing, tested as low refrigerant, add some more, back to working until it doesn't in a few months. Also heating seems to always work but not cooling. Tested as having an unlocated leak somewhere...one more reason for people to steer clear of apartments.

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      @@yuhaogu4744 if the outdoor unit is located a long way away from the indoor unit (for example, outdoor unit being located on the roof of apartment building), then the only way to approach this in my opinion is to pressure test the system in three different sections. Not as one. So for example, pressure test the outdoor unit only. Pressure test the indoor only. Pressure test the lineset only. That way you will identify if the leak is in the indoor unit, outdoor unit or lineset. This way you can at least have a chance of finding it.

  • @anupbiswas4745
    @anupbiswas4745 3 ปีที่แล้ว +1

    Sir daikin inverter ac orginal pcb hain ap ke pass,, milaga kya india main?

  • @guillermomera4153
    @guillermomera4153 2 ปีที่แล้ว +1

    what tool are you using to read the EEV?

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      I used my Fluke multimeter to check the ohms of the EEV coil.

    • @guillermomera4153
      @guillermomera4153 2 ปีที่แล้ว +1

      @@maracservices how do read through pins of the cable to the coil? Does the D checker also tell you if the eev is working?

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      @@guillermomera4153 the service tool tells you the pulse of the EV. So you know if it should be opening or closing. When I want to check the valve. I use a magnet. When I want to check the coil, I test the ohms of the pins on the plug that goes into the PCB. You can get the correct ohm readings from Daikin app.

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      So to clarify, I test the plug on the coil (not the PCB). Just to be clear.
      Thanks

    • @LC-qi5ff
      @LC-qi5ff ปีที่แล้ว

      @@maracservices what does testing the valve with a magnet involve?