Air Compressor keeps tripping out circuit breaker.. how to fix this problem

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ก.ย. 2023
  • Hi and welcome to Micks Mowers
    In this Video I have a new Air Compressor that keeps tripping out the circuit breaker.. in this how to fix video I will show you what the problem is and how to fix it.
    Micks Mowers Merchandise UK Store below
    micksmowersthemowerman.myspre...
    Micks Mowers Merchandise USA Store below
    micks-mowers-usa.myspreadshop...
    Here is my channel wish list if you would like to show some support in purchasing some tools or spare parts, it is gratefully appreciated www.amazon.co.uk/hz/wishlist/...
    TOOLS I USE -
    Oil Extraction pump amzn.to/2UBApDI
    Fan Blade Bulb amzn.to/39BLI4a
    Blade removel tool amzn.to/3nxBVQj
    Micro Drill Bits amzn.to/36Jpv0R
    Carb Cleaning Files amzn.to/3lH8ESx
    Hex Shank Extension Drill Bits Bar Set 1/4" 3/8" 1/2" amzn.to/3oFKHx9
    Dewalt DCF887M1- Impact Driver, amzn.to/3oEVcjZ
    Lawnmower Rotary Blade Balancer amzn.to/3e6UOWN
    Rode WIGO Wireless GO Wireless Microphone amzn.to/2JlRlIN
    Neewer 176 LED Light amzn.to/2HaubnJ
    Universal Style, Mower Deck clamp for blades amzn.to/31PKygE
    Briggs & Stratton Diaphragm and Gasket set amzn.to/3kF8Y3H
    GT SONIC 3L Ultrasonic Cleaner amzn.to/2TDdVy9
    VEVOR 3L Ultrasonic Cleaner amzn.to/2Gb3PBJ
    Stainless Steel Strainer for carb jets in a cleaner amzn.to/3e6CxJ2
    Please follow me for more channel updates
    Instagram micksmowers...
    Twitter micksmowers?s=07
    Banjo Hop by Audionautix is licensed under a Creative Commons Attribution license (creativecommons.org/licenses/...)
    Artist: audionautix.com/
    Disclaimer: My Videos are for information only- i am not a professional or repair shop im just someone in a shed enjoying a hobby- If you choose to try one of the suggestions made in my videos, you do so at your own risk. No information contained in this video shall create any express or implied warranty or guarantee of any kind. Any injury, damage or loss that may result from the improper use of tools, equipment or information contained in this video is the sole responsibility of the viewer and not Micks Mowers The Mower Man.THE SIGNS IN THE BACKGROUND ARE FOR DISPLAY PURPOSES ONLY.I HAVE NO AFFILIATION WITH THEM AND I CONFIRM I AM NOT A MAIN DEALER OF SAID COMPANIES I HAVE PERMISSION TO USE THEM
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 55

  • @themowerman
    @themowerman  10 หลายเดือนก่อน +1

    Here is my channel wish list if you would like to show some support in purchasing some tools or spare parts, it is gratefully appreciated www.amazon.co.uk/hz/wishlist/ls/13BO7QKGAZZV2/ref=nav_wishlist_lists_2?_encoding=UTF8&type=wishlist

  • @bofor3948
    @bofor3948 10 หลายเดือนก่อน +6

    Hi Mick, unless you were adding to an existing load on the breaker i.e. lights, cooling fans, tools etc. and you exceeded the breaker rating, this should not have happened. If it was only the compressor switched on, then this could be caused by what is known as inrush current. High reactance loads like big transformers, motors and capacative (condensor) loads will pull higher current for milliseconds at startup. You have found a solution but SGS should be notified. If that compressor is rated at 13A and expected to run on domestic mains they should modify the equipment by adding an inrush current limiter device. Your sparks has added a similar device to your supply board, but the equipment should run at the notified rated current without tripping existing circuits. If you had that compressor in your van and you were mobile doing repairs, you wouldn't expect customers to have uprated mains RCD's

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      That's a good point...

  • @themowerman
    @themowerman  10 หลายเดือนก่อน +2

    Micks Mowers Merchandise UK Store below
    micksmowersthemowerman.myspreadshop.co.uk/men?q=D1
    Micks Mowers Merchandise USA Store below
    micks-mowers-usa.myspreadshop.com/all

  • @davidcarlisle3384
    @davidcarlisle3384 10 หลายเดือนก่อน +3

    Good advice about the startup current spike.
    Also, if you need air farther away,it is better to get a longer hose than to use an extension cord. 😊

    • @themowerman
      @themowerman  10 หลายเดือนก่อน +1

      Good advice mate

  • @alandykes2519
    @alandykes2519 10 หลายเดือนก่อน +1

    Great to see you have got it all up and running now Mick 👍👍👍👍

  • @themowerman
    @themowerman  10 หลายเดือนก่อน +1

    TOOLS I USE -
    Oil Extraction pump amzn.to/2UBApDI
    Fan Blade Bulb amzn.to/39BLI4a
    Blade removel tool amzn.to/3nxBVQj
    Micro Drill Bits amzn.to/36Jpv0R
    Carb Cleaning Files amzn.to/3lH8ESx
    Hex Shank Extension Drill Bits Bar Set 1/4" 3/8" 1/2" amzn.to/3oFKHx9
    Dewalt DCF887M1- Impact Driver, amzn.to/3oEVcjZ
    Lawnmower Rotary Blade Balancer amzn.to/3e6UOWN
    Rode WIGO Wireless GO Wireless Microphone amzn.to/2JlRlIN
    Neewer 176 LED Light amzn.to/2HaubnJ
    Universal Style, Mower Deck clamp for blades amzn.to/31PKygE
    Briggs & Stratton Diaphragm and Gasket set amzn.to/3kF8Y3H
    GT SONIC 3L Ultrasonic Cleaner amzn.to/2TDdVy9
    VEVOR 3L Ultrasonic Cleaner amzn.to/2Gb3PBJ
    Stainless Steel Strainer for carb jets in a cleaner amzn.to/3e6CxJ2

  • @markcreeney-if7rr
    @markcreeney-if7rr 10 หลายเดือนก่อน +1

    I used to be an electrician in a previous life. I put my garage on a ring main as providing your incoming cable is big enough you can get away with 32 amp breaker. If your incoming cable is say 2.5 mm and a distance from the house I would be a little wary of using 32 amp. I would do what you have done and put the compressor on a separate 20amp breaker but make it a close as possible to the consumer unit so only a short cable run. Never keen on a 20 breaker on the end of a run of sockets even if in theory it is ok. For me as long as you have the correct breaker protecting your underground cable to your outbuilding you won’t go far wrong as it will protect everything. But good video as many people will think they have a faulty compressor. Also got my grey cells working and brought back memories when I was on the tools.

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Thanks for watching.. yes I'm got to add a stocket just for the compressor.. the others are on a ring main...

  • @Turningwrenches85
    @Turningwrenches85 9 หลายเดือนก่อน +1

    Glad it was able to be fix there mick with the bigger Amp to allow the initial startup

    • @themowerman
      @themowerman  9 หลายเดือนก่อน

      It's running great...

  • @fixitorstripitGardenmachines
    @fixitorstripitGardenmachines 10 หลายเดือนก่อน +1

    I don't have that problem with my baby air compresor. Interesting video and very helpfull for people who upgrade.

    • @themowerman
      @themowerman  10 หลายเดือนก่อน +1

      Thanks mate

  • @GuysPlayingWithTools
    @GuysPlayingWithTools 10 หลายเดือนก่อน +1

    I have slow blow circuit breakers on mine, works like a charm. 🙂

  • @liljoeii6091
    @liljoeii6091 10 หลายเดือนก่อน +1

    Yeah, do the same thing you did. I got a better breaker in there. An it don't pop the breakers anymore. Thank you for the video

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Fantastic...

  • @wrxs1781
    @wrxs1781 10 หลายเดือนก่อน +1

    Good video Mick, and glad to see the compressor issue resolved. Not familiar with the UK electrical code but, we size the breaker to the wire gage and also the wire run distance, longer the run the larger the wire gage, they have line loss charts on line.

    • @ianharvey868
      @ianharvey868 10 หลายเดือนก่อน

      It's the same here in the UK, we use a physical size not like a gauge rating, so we would use 1.5mm(sq) cable for lights and 10mm(sq) cable for showers etc. We also take in consideration if the wire is also embedded in insulation or in conduit vs open air over the length for thickness and protection rating

  • @HobbyMotorDK
    @HobbyMotorDK 10 หลายเดือนก่อน +1

    Funny - I had the same issue with my hydraulic, remote comtrolled, totally awesome, in floor lift table 🙂

  • @derrasenmaher9730
    @derrasenmaher9730 10 หลายเดือนก่อน +1

    Nice and it just purrs away 👍🏻 Great Setup Mick

    • @themowerman
      @themowerman  10 หลายเดือนก่อน +1

      Thanks mate

  • @dnrsmallenginerepair
    @dnrsmallenginerepair 10 หลายเดือนก่อน +1

    Good fix my friend

  • @ianharvey868
    @ianharvey868 10 หลายเดือนก่อน +2

    Could be a few things, what I don't get is the fuse in the 13a plug didn't blow first as that is less than the 16a mcb/rcd, this to me means its probably a faulty mcb/rcd in reaction time, most are a "c16 b" so it's a bit slower and should trip around 50a at a few microseconds and as the video says the varient " C" is even slower.
    What concern me in this video he says his cables are rated for 20a, so the mcb in the house should be a 16a to protect the cable going to the shed, this is because the mcb/rcd/fuse won't blow at 16a but around 1.3times that (20.8amp) is where it will trip, if he has a 20amp fuse or mcb in the house that will trip/open circuit at 26amps, so his 32amp mcb/rcd in the shed is technically "no protection" at that actual point, however if the mcb/rcd in the house is a 32amp then that's a problem, as this won't trip until like 40amps which as he said his cable is only rated for 20amps, this can make that long cable a large resistive wire heating up and may cause a fire before a direct short-circuit happens then tripping the mcb/rcd.
    I'm no qualified electrician but fuses, mcb, rcd, rcbo's etc are designed to protect the wires not the equipment, I have something called common sense when doing research.
    So that being said what in my opinion should have been done is exchanged the "c16b" for a "c16c or d" this protection for short circuit of upto 20amps at his shed keeping his wires going to the house safe too

  • @stevoj8959
    @stevoj8959 9 หลายเดือนก่อน

    That is a nice compressor. At 14 CFM you could run a spry gun with that. I can see why you will need at least 20 amps to run it. On a cold day it may need more. Nice set up Mick. Stevo

  • @Dstromb232
    @Dstromb232 10 หลายเดือนก่อน +1

    I use a surge protection Eliminate Surges, Spikes. Some compressors depending the size when at first start it uses its full amps to power up then drops off .

  • @Johnny16781
    @Johnny16781 10 หลายเดือนก่อน +1

    Good one again Mick

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Thanks mate

  • @johne8379
    @johne8379 7 หลายเดือนก่อน +1

    Now you’ve had the air compressor for awhile. How are you getting on with it?

    • @themowerman
      @themowerman  7 หลายเดือนก่อน

      It's perfect...

  • @petefroud5308
    @petefroud5308 10 หลายเดือนก่อน +1

    Good job better safe than sorry.

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Yes mate

  • @knighthawk86855
    @knighthawk86855 10 หลายเดือนก่อน +1

    I wired all my compressors with a dedicated circuit, hard wired in thier own box. they all have a their own wire, and in house circut breaker 30amp....and I never run more then one at a time.

  • @MrGWN7
    @MrGWN7 10 หลายเดือนก่อน +1

    Capacitor can be weak, even new. The breaker in the panel can be weak. Have someone test the draw on both. Replace what is needed.

  • @dallasgarner1990
    @dallasgarner1990 10 หลายเดือนก่อน +1

    It would be best to put a socket right next to your compressor mick.

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Yeah I think I will do that ...

  • @ashleystringer7531
    @ashleystringer7531 10 หลายเดือนก่อน +1

    First of all it doesn't matter whether your sockets are connected A16 amp breaker that will not work all sockets are 13 amp but if that compressor says runs off 13 amp it should run off 13 amp if not it's fake advertisement I've had this problem before with my compressors you will need a 16 amp surpply and a breaker are they 16 amp Plug any compressor what's over 50 l will need a 16 amp supply my name is Ashley I like your channel as .

  • @motorcoachtech7615
    @motorcoachtech7615 10 หลายเดือนก่อน +1

    Mick, Is the voltage in the shed 240v?

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Yes mate

  • @KensSmallEngineRepair
    @KensSmallEngineRepair 10 หลายเดือนก่อน +1

    Sparky? I thought that meant something else!!

    • @themowerman
      @themowerman  10 หลายเดือนก่อน +1

      Like what ken.. please explain 🤔

  • @matthewharmer1656
    @matthewharmer1656 10 หลายเดือนก่อน +1

    Just change the b type to c type rcds??

    • @matthewharmer1656
      @matthewharmer1656 10 หลายเดือนก่อน

      C type have a better trip curve designed for motors with a high in rush of current.

  • @robertmailhos8159
    @robertmailhos8159 10 หลายเดือนก่อน +1

    How 2 amps are causing the breaker to trip 😮

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      It's the first start up.. pushing it over 16amps...

    • @robertmailhos8159
      @robertmailhos8159 10 หลายเดือนก่อน +1

      @@themowerman that is the truth about that matter thing is different types of electric motors require different amps at start up depending on the horsepower of the motor

  • @jimlepeu577
    @jimlepeu577 10 หลายเดือนก่อน +1

    Personally I wudda put in a 30a breaker to ensure I was giving it a margin. Better too much than too little or bare enuf - not much difference in the price.

    • @themowerman
      @themowerman  10 หลายเดือนก่อน +2

      Like I said.. I'm not a professional.. however my electrician is...

    • @michaelbarkham6064
      @michaelbarkham6064 10 หลายเดือนก่อน +1

      Please nobody take this guys advice. How do you know the current carrying capacity of the cable is rated for 30a?? Leave it to the experts 😉

  • @paulacabbo466
    @paulacabbo466 2 หลายเดือนก่อน +1

    Sorry I couldn't watch this inordinately long video for a simple fix

    • @themowerman
      @themowerman  2 หลายเดือนก่อน

      Ok but thanks for the comment

  • @outkast187
    @outkast187 4 หลายเดือนก่อน +1

    Holy hell, get to the point. No need for a 13 minute video for a 13 second explanation.

    • @themowerman
      @themowerman  4 หลายเดือนก่อน

      Did you watch it all.. ?

  • @johnobiro5202
    @johnobiro5202 10 หลายเดือนก่อน +1

    Shocking that Mick. You can plug your Jack Hammer in now. 👍🔧

    • @themowerman
      @themowerman  10 หลายเดือนก่อน

      Lol will do mate