Troubleshooting APC UPS PFC Fault | Repair Guide
ฝัง
- เผยแพร่เมื่อ 16 ต.ค. 2024
- #apc #ups
Troubleshooting APC UPS PFC Fault | Step-by-Step Repair Guide
apc ups red light and beeping
ups apc
apc ups not powering on
apc ups pfc fault
online ups repair
apc ups repairing
pfc circuit
apc surt ups
apc ups
apc ups repair
apc ups problem
ups repair
ups repair karne ka tarika
apc online ups repair
apc ups circuit board repair
apc 5kva ups pfc repair
pfc fault
uninterruptible power supply
how to fix ups pfc fault
electronics repair
apc
ups
pfc
#apc #ups #upsrepairing #apcups #akelectrotech
بہت اعلی سر آپ کے اس ویڈیو کی وجہ سے آج ایک اور فالٹ ریپیئر کرنا سیکھ لیا۔ آپ نے علم کو فروغ دیا اللہ اپ سے راضی ہو۔
In my case showing pfc fault on both battery mode and ac main mode what's the proble
@@maheshworld4933
Check PFC portion for that issue
This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me. I want everyone who has had problems with UPS devices, to know about him. He has an expert knowledge. That's why I write this comment on all his videos. I spent 4 nights without sleep looking for the problem. 👍
👍👍
Master at work. I didnt know about this fix. Its nice to watch someone else diassembling these and seeing how they do it differently. I liked the way you took the fan and personality board out at the same time. I dont think anyone has come up with the way to get the board back in without a bit of a jam!
well done
Thank you
Sir app ki video bhot interesting and informative hoti Hain .
Thanks
Good
Nice video with step by step guide.Thank you sir.
Wellcome
Thank you sir for the in depth APC repair course, IS it ALSO POSSIBLE TO HANDLE TRIPPLITE UPS FAULTS and trouble shooting?
For APC SURT codes you can see video with full detail and wait for tripplite ups
Greeting Sir, I have Apc surtd3000xli its showing 70 - 80% load, and sometimes 100% load without attach any load. Help me sir thanks in advance
@@PakGuides
R758 and R759 are used for load sensing. pl check them. 237k ohm resistors are used here
@@AKElectroTech Sir, both registers are ok showing R758=229k R759= 233k.
@@PakGuides replace with 237K
@@AKElectroTech ok
@@AKElectroTech Sir, I replace both registers with 237k ohm but issue still exist. Help me sir
❤
Mery Pass surt 10 kva ups aya hy battery py ups theek Kam krta hy jab main lgaty hen yo pfs supply +500 or _ 180 volt ban rhy hen is ko kysy thek krna +500 col or _180 bol bna rhy hen
Pl check rectifier stage
Error code 01100 APC 3kva online ups. How to slove
@@noenoe-km9re
There may be PFC shortage, Q28 short or Q707 mis behaving
Nice
Thanks
سر کیا میں آپ سے ذاتی طور پر رابطہ کر سکتا ہوں
Wattsapp +923215717132
Waalaikummussalam