Good video ! a Good Habit to get into whenever you see a Condenser fan motor Is - allways give them All a little spin and see if they spin freely. super easy - First thing to do on any condensing unit. allways spin those motors. First thing. Most common failure point in refrigeration for me. 2) That flare nut was probably not leaking last time u were there. what happens is - Cfm - Quits. Head pressure climbs - and pushes past the flare nut - weakest spot. used to see it alot - have not seen it in a while. flare nuts get a bit loose over time - compression of soft copper over time. re-tighten nut & away u go again. old school leak & repair. Good vid !
Everybody in the world envy's you You're always playing with Mr bubbles and with the garden hose every kids dream. So you have the world's perfect job except when you're up there and negative 20° below zero
🏆- you passed the test. After I shot the video I indeed had to reverse the fam direction cuz it was pushing out. I could tell more by the speed of the blade and the overamping 😂
@@restaurantrepairs cool brother, I’m never knocking you. You do great work and admire your attention to detail. You’ve a great tech, keep up the good work ✊
I can’t remember fully but I think you’re located in the south, I’m in the north and if a unit has a HPR on there and no fan cycle control whenever we have to charge it up we weigh in the winter charge for condenser flooding so the receiver doesn’t go low in the winter. Where you’re at does it get cold enough that the receiver gets drained from it trying to maintain head pressure with those HPR heads?
I am in north Ga. It does get cold enough at time to be a head pressure issue. This it has a headmaster control so instead of dropping out the fans it straight bypasses the coil. Trapping that refrigerant in there does create shortage situations of the receiver isn’t topped off proper tho.
Great Repair and Condenser Rinse Off.👍🙏
2:44 bubbles. Great video of a repair.
👍👍👍
Nice job. Enjoy your videos.👍
Good video ! a Good Habit to get into whenever you see a Condenser fan motor Is - allways give them All a little spin and see if they spin freely.
super easy - First thing to do on any condensing unit.
allways spin those motors. First thing.
Most common failure point in refrigeration for me.
2) That flare nut was probably not leaking last time u were there.
what happens is -
Cfm - Quits.
Head pressure climbs - and pushes past the flare nut - weakest spot.
used to see it alot - have not seen it in a while.
flare nuts get a bit loose over time - compression of soft copper over time.
re-tighten nut & away u go again.
old school leak & repair.
Good vid !
Dropping some sweet wisdom on us OC 👍🏼
Nice find Brother!! Enjoy the weekend!
What’s a weekend 😂
Dont forget to put the winter charge
Everybody in the world envy's you You're always playing with Mr bubbles and with the garden hose every kids dream.
So you have the world's perfect job except when you're up there and negative 20° below zero
beep, beep, beep, blizzard machine explodes
Good video bro but that blade is CW shaft end
🏆- you passed the test. After I shot the video I indeed had to reverse the fam direction cuz it was pushing out. I could tell more by the speed of the blade and the overamping 😂
@@restaurantrepairs cool brother, I’m never knocking you. You do great work and admire your attention to detail. You’ve a great tech, keep up the good work ✊
I can’t remember fully but I think you’re located in the south, I’m in the north and if a unit has a HPR on there and no fan cycle control whenever we have to charge it up we weigh in the winter charge for condenser flooding so the receiver doesn’t go low in the winter. Where you’re at does it get cold enough that the receiver gets drained from it trying to maintain head pressure with those HPR heads?
I am in north Ga. It does get cold enough at time to be a head pressure issue. This it has a headmaster control so instead of dropping out the fans it straight bypasses the coil. Trapping that refrigerant in there does create shortage situations of the receiver isn’t topped off proper tho.
🇺🇸💪❄️👍 multiple offender
Excellent work joe 👍