gas boiler with high c.o. levels fixed

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 ต.ค. 2024

ความคิดเห็น • 130

  • @KW86.
    @KW86. 10 ปีที่แล้ว +2

    Your high CO video, extremely helpful, people have no idea how dangerous CO levels can hurt family members, your testo 320 class, the simple way you teach saves lives.
    I can see a marketing venture here, students will sign up for your course, I'll sign up.
    Thanks
    Gilbert

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      gilbert de la torre the testo 320 is a great tool .there are some students watching my videos ... thanks for the comment gilbert

  • @kdog323
    @kdog323 10 ปีที่แล้ว +2

    There's nothing like the work of a professional. Job well done Steve!

  • @dcrickerson9775
    @dcrickerson9775 10 ปีที่แล้ว +4

    Nice job, the customer was very friendly. So important to have your furnace or boiler checked every year.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      DC Rickerson i agree very important to have yearly service

  • @walterh.porembski6161
    @walterh.porembski6161 4 ปีที่แล้ว +1

    Steve your really good at your profession and very easy to watch

  • @Fireship1
    @Fireship1 10 ปีที่แล้ว +2

    Good job Steve. Another safe boiler thanks to you and the 320.
    -Jack

  • @SteveSam66
    @SteveSam66 10 ปีที่แล้ว +1

    Steve, Nice Job. The adjustable gas valve made a huge difference. Cool Customer

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      S Sam yes the adjustable gas valve is a must

  • @letseeitplease
    @letseeitplease 10 ปีที่แล้ว +3

    this was interesting to watch how all the testing and everything was done, very good video, i like this, keep up the good work steven and be safe,

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว +1

      letseeitplease i will be doing more videos like this

  • @joekjr.3693
    @joekjr.3693 10 ปีที่แล้ว +1

    You are definitely good at what you do Steve. Just by watching you I got my boiler running great :))))

  • @ncooty
    @ncooty ปีที่แล้ว

    I grew up in Texas and I get such a kick out of listening to you yankees kvetch at each other and bust each other's chops. :)

  • @jonathanflynn618
    @jonathanflynn618 6 ปีที่แล้ว +3

    Hey Steve, love your videos! So the manifold pressure for these is usually 3.5 in. wc. and when you back off the outlet pressure you are probably bringing it down below that number. Are there any other adjustments you can make to improve efficiency? I just adjusted my gas valve down to 2.4 in. wc. because my CO was around 3500 ppm at the factory pressure which is 3.5 in. wc. That is a whole in. wc. lower than factory spec, kinda freaked me out.

  • @rumboldj1
    @rumboldj1 10 ปีที่แล้ว +2

    Very nice Steve! Word of mouth is priceless.

  • @leanorlando
    @leanorlando 9 ปีที่แล้ว +2

    The customer is hilarious. Great job Steve.

    • @stevenlavimoniere
      @stevenlavimoniere  9 ปีที่แล้ว +1

      leanorlando he was a good guy father of the homeowner

  • @gabrielvillanuevaiii3926
    @gabrielvillanuevaiii3926 5 ปีที่แล้ว +3

    I like the customers voice. He sounds like a character from Sesame Street. Or a muppet

  • @jhhvacplumbing1944
    @jhhvacplumbing1944 10 ปีที่แล้ว +5

    Old man just wanted someone to talk to , that's cool , great job Steve .

  • @hvacrcole
    @hvacrcole 10 ปีที่แล้ว +3

    It looks like I have a video I can use in my combustion class next week. Good Job as usual

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      Larry Cole thanks larry for the support brother

    • @aryankabir4167
      @aryankabir4167 3 ปีที่แล้ว

      I guess Im randomly asking but does someone know of a way to log back into an instagram account?
      I was dumb forgot my login password. I appreciate any tricks you can give me

    • @robertodamian7544
      @robertodamian7544 3 ปีที่แล้ว

      @Aryan Kabir Instablaster ;)

    • @aryankabir4167
      @aryankabir4167 3 ปีที่แล้ว

      @Roberto Damian thanks so much for your reply. I found the site on google and im waiting for the hacking stuff now.
      I see it takes a while so I will reply here later when my account password hopefully is recovered.

    • @aryankabir4167
      @aryankabir4167 3 ปีที่แล้ว

      @Roberto Damian It did the trick and I actually got access to my account again. Im so happy!
      Thank you so much, you really help me out :D

  • @bmkolb
    @bmkolb 5 ปีที่แล้ว +1

    Verify inlet gas pressure then manifold pressure and check chimney draft .
    Note-
    If the pressure is turned to far DOWN you might have issues with the burners lighting correctly at some point and flash out when it lights the main burners or not lighting main burners across evenly.
    Lots of times people change the vent pipe with the incorrect Diverter pipe height is critical at skirt to boiler

  • @ch003pe
    @ch003pe 6 ปีที่แล้ว

    I did not see you doing the soap suds test to see if the gas connections were leaking.Sorry if I missed it, did you use a meter?

  • @jimbola77
    @jimbola77 8 ปีที่แล้ว

    excellent job steve I wish I had your knowledge or at least the baby mama's!!!!

  • @eric4467
    @eric4467 9 ปีที่แล้ว +2

    Very informative.You really know your stuff.

  • @EminHVAC
    @EminHVAC 10 ปีที่แล้ว +1

    Great job Steve. Like everyone else I liked the customer. good Chatt. You're really good with that Testo I'm still learning how to use it properly. It sucks that I never received the cheat sheets it must of got lost in the mail.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว +1

      Emin HVAC i sent them out to the adress you gave me

    • @EminHVAC
      @EminHVAC 10 ปีที่แล้ว

      Yeah I know. My mail likes to loose shot lol. Thank you though Steve I appreciate the time you took out to do so

    • @EminHVAC
      @EminHVAC 10 ปีที่แล้ว

      Justin Mikola cool thanks man. Appreciate it

  • @natashapatterson7653
    @natashapatterson7653 8 ปีที่แล้ว +1

    steven on a hydronic boiler the flames are very low do you think its the C O on the gas valve or is it the unit is dirty

  • @nittlenits101
    @nittlenits101 8 ปีที่แล้ว +1

    just subscribed man, love the vids...I'm a 4th year plumbing and heating apprentice up here in Canada. I love all these trades, and after I'm done plumbing I'd like to get my hvac as well!! I'm an old guy just starting as I wanted to learn something new hahaha. A quick question, that little digital machine, how does that thing work, is there a probe that measures the gas mixtures and stuff? what make and model is it? I'm always looking for new tech tools to buy!!

  • @hannarye
    @hannarye 10 ปีที่แล้ว +2

    Them old guys love to talk your ear off. LOL. Great job on that Steve.
    Charles

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว +1

      hannarye thanks charles for the support brother

  • @phillipgroom9187
    @phillipgroom9187 10 ปีที่แล้ว +1

    Good video! Customer was funny. Good job, keep up the good work. Phillip

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      Phillip Groom thanks for the comment phillip

  • @tomh6779
    @tomh6779 3 ปีที่แล้ว

    Sickness has no age. Good statement

  • @HM-yp8sd
    @HM-yp8sd 10 ปีที่แล้ว +1

    great video right here! on a boiler like that does it matter if new replacement gas valve is a slow acting or fast acting? is there a big difference?

  • @KW86.
    @KW86. 3 ปีที่แล้ว

    Steve, what's the difference between checking co2, and pressure on gas valve, same adjusting screw? Testo 320 $1000, manometer $150. Which one? You didn't use manometer on this job?

  • @TandNServices
    @TandNServices 10 ปีที่แล้ว +3

    I like customers like him

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      T&N Services LLC. he was cool

    • @glennharrison9605
      @glennharrison9605 10 ปีที่แล้ว +2

      That old valve IS adjustable, the small slotted screw next to the phillips screw on the top right corner of the valve is the regulator adjustment.

  • @harrydickson4575
    @harrydickson4575 10 ปีที่แล้ว +2

    Nice job Steve love the customer relations LOL

  • @genegarneau3822
    @genegarneau3822 5 ปีที่แล้ว

    Good video.
    And how much was the bill?

  • @SovereignTroll
    @SovereignTroll 5 ปีที่แล้ว

    Most people will not experience any symptoms from prolonged exposure to CO levels of approximately 1 to 70 ppm but some heart patients might experience an
    increase in chest pain. As CO levels increase and remain above 70 ppm, symptoms become more noticeable and can include headache, fatigue and nausea. At sustained CO concentrations above 150 to 200 ppm, disorientation, unconsciousness, and death are possible. I guess the short answer is 70 ppm but 0-8 ppm the normal background is best or get curious why. I just read CO detectors start alarm at 50 ppm. Quoted from US Product Safety Commission. Your videos are dead serious important.

  • @emutiny
    @emutiny 9 ปีที่แล้ว +6

    amazing how you deal with customers. i cant be bothered while im working. im working on it though.

    • @stevenlavimoniere
      @stevenlavimoniere  9 ปีที่แล้ว +2

      emutiny dealing with the customer is important so your on the same page as them

  • @ncooty
    @ncooty ปีที่แล้ว

    @11:14: My eyes nearly popped out of my head. 2300 ppm CO AF?!
    EDIT: And you dropped that to 11? Wow. Well done.

  • @beefcurrywithrice
    @beefcurrywithrice 4 ปีที่แล้ว

    Do you just adjust the manifold pressure on the gas valve to fix this problem ?

  • @forzamilan07
    @forzamilan07 7 ปีที่แล้ว +1

    Just curious why you were not checking gas pressure at the same time as CO test? Just curious for my own practice no hate lol

  • @shahsmerdis
    @shahsmerdis 6 ปีที่แล้ว

    seems like this just has a set screw thats it right?
    can you adjust based off the output gas pressure to manufactures spec (say 3.5 WC) with manometer or do you need combustion analysis device? is the readings off because the output pressure was out of spec, or because you did some very fine tuning?
    i did a good deal of calling and i havent been able to find some one who does combustion anaylsis in my area. I would like to just buy a manometer and check the gas pressure and call it a day .

    • @nsboost
      @nsboost 5 ปีที่แล้ว

      Bardia Ghajari I walked into a boiler yesterday that the manifold pressure was dead on at 3.5” and the co reading was over 10,000ppm. Setting gas pressure isn’t enough

  • @Brad1237202
    @Brad1237202 10 ปีที่แล้ว +1

    As usual, nice job Steven!!! A little snow on the truck this morning?

  • @nsboost
    @nsboost 5 ปีที่แล้ว

    I’m curious what you would have found if you clocked the meter after your adjustments

  • @seang402
    @seang402 8 ปีที่แล้ว

    Hey steve i have exact burner and valve you did not show how to remove VR800 valve.and i thout that new valve 4506 was good right outta box wish you could come here to whitman Great vid thanks i could use yeah

  • @remcovantriest4357
    @remcovantriest4357 10 ปีที่แล้ว +1

    Nice video Steven, No offence but you dont need to do a sooth test on gas fired equipment, sooth tests are only done on oil burners.
    As you mentioned before complete combustion is the key, i would have this customer nominated for a new boiler in the near future O2/CO2 level can be much higer O2 3.0/4.0% CO2 9.5/10 a lot off extra savings.
    Testo 308:
    The digital smoke tester is a hand-held instrument for
    determining the smoke number of oil firing installations.
    These systems can be monitored using the testo 308 and
    checked for compliance with the applicable limit values.

  • @pomz3604
    @pomz3604 8 ปีที่แล้ว +1

    Hey Steve, I have the Testo 310, I wish I would have bought the 320. I like the colour screen.

    • @stevenlavimoniere
      @stevenlavimoniere  8 ปีที่แล้ว

      +Gerry Pomanti yea the 320 is way better i believe

    • @pomz3604
      @pomz3604 8 ปีที่แล้ว

      Just wondering what the manifold pressure was with the old gas valve if it was over-firing that was causing the high CO?

    • @stevenlavimoniere
      @stevenlavimoniere  8 ปีที่แล้ว

      i could not adjust the old valve thats why i changed it

  • @chairde
    @chairde 3 ปีที่แล้ว

    A real professional.

  • @donnierobertson3088
    @donnierobertson3088 3 ปีที่แล้ว

    Great job and video like always

  • @bahopik
    @bahopik 7 ปีที่แล้ว +2

    you got lucky meter didn't lock up, i have 310 and it looked up for 24 hours after like 1800 ppm, so i had to wait a day to finish what i was doing. Generally they don't recommend to keep probe in if it's that high, just check it quick and if reading going up, decrease pressure and recheck

    • @lh98
      @lh98 ปีที่แล้ว

      The ppm reading is done in the smoke stack or just in the vicinity of the boiler?

  • @PlausableApple4
    @PlausableApple4 10 ปีที่แล้ว +2

    Nice work Steve. I've been working with steel pipe at vocational school lately.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว +1

      PlausableApple4 steel pipe is all part of the trade. i am sure you will do well ..

    • @PlausableApple4
      @PlausableApple4 10 ปีที่แล้ว

      I'm doing pretty well right now. I need to work on my measurements, that's about it.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว +3

      take every thing from center to center then deduct your fittings

  • @paokoma
    @paokoma 10 ปีที่แล้ว +1

    Have you looked into the testo 308? It gives you a digital reading and also paper sample. You can sync it up with the 320 too for printouts. Nice video.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      ***** i will have to look into it

    • @paokoma
      @paokoma 10 ปีที่แล้ว

      steven lavimoniere Having a number value is invaluable.

  • @codymon100
    @codymon100 10 ปีที่แล้ว +1

    Nice job Steven

  • @dklucas1
    @dklucas1 9 ปีที่แล้ว +2

    Yeah i have heartburn..its called customers and neighbors LOL

  • @BoilingPointMechanic
    @BoilingPointMechanic 10 ปีที่แล้ว +1

    I just did a PM on that same boiler on Saturday. I was getting a slightly high CO reading too ( around 150) couldn't adjust that shitty gas valve they put on that Burnham. All of a sudden it dropped to around 50 so I let it be. I'm not sure if maybe my meter wasnt reading correctly cause I left it in the cold truck overnight.

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      Robert Doherty we are going to have to bring our meters in now it getting cold out ..

  • @waynehensley132
    @waynehensley132 10 ปีที่แล้ว +1

    good job Steven

  • @jsbrodhead2999
    @jsbrodhead2999 6 ปีที่แล้ว

    Did that furnace have a fixed regulator and fixed orifice?
    I have a 23 year old Trianco Heatmaker-M2 boiler, which started kettling 3-4 years ago. I added a temperature controller, which monitors the water temperature at the input to the boiler and interrupt the heating cycle, before kettling can begin (beats waking to a cold house).
    Yesterday the exhaust CO was measured at 100ppm, according to the tech from the gas company. Then I throttled the gas supply, by partially closing the ball-valve - just enough to hear a change in the flame, the tech told me the CO dropped to "0". The tech was concerned about operating the boiler with the ball valve partially closed, but we are in a cold snap (who isn't right now). Since the boiler CO is acceptable ("0ppm"), I'm not shut-down, but need to service/resolve the issue.
    Trianco is defunct; sold off to Waterpik, then ???? There is a 3rd party parts supplier, or two), but Trianco-trained service techs aren't going to be available, nor will support.
    My boiler has a NON-ADJUSTABLE valve/regulator [description: "gas valve, negative pressure, White Rodgers"], which looks very much like the one you replaced. It also has a fixed orifice, for which replacements can still be purchased, in a set of three (different sizes, I assume(?)).
    The kettling issue came on suddenly and the water in the system is almost 100% the same water I filled it with 23 years ago, so mineral accumulation in the boiler coils shouldn't be the cause.
    After watching your video, I'm thinking that maybe the regulator wore out and is no longer regulating properly, is at all, so the gas flow is too high. (Orifice replacement won't fix that.)
    Seems that maybe an adjustable valve/regulator would be better than the non-adjustable original! THANKS!

  • @TheChipmunk2008
    @TheChipmunk2008 10 ปีที่แล้ว +2

    With levels that high, and having to back the gas way off, I wonder if his gas company meter regulator was off?

  • @mcbreartyfull
    @mcbreartyfull 2 ปีที่แล้ว

    Is that homer Simpson in the background?

  • @chadmoore9336
    @chadmoore9336 3 ปีที่แล้ว

    Pipe dope -- brand/type?

  • @mikeacong719
    @mikeacong719 5 ปีที่แล้ว

    Any help around Baltimore and dundalk area for gas (steam) boiler heater?

  • @airecraft1
    @airecraft1 10 ปีที่แล้ว +2

    I had an RTU a few days ago with CO so high my meter shut off to protect itself the manifold pressure was 6.5"

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      airkraft1 i have had my meter shut of many times ...one today manifold pressure was 8.6 on natural gas..it should be 3.5

    • @airecraft1
      @airecraft1 10 ปีที่แล้ว +2

      steven lavimoniere
      It's given me a message a few times to replace the sensor after that shut down its time to order one up gotta take care of the old girl

  • @abecontreras7940
    @abecontreras7940 2 ปีที่แล้ว

    Want to hear something sad.. I’m here watching how to adjust pipes because idk how.. my job just told me to learn and take care of the customer

  • @acechoice45
    @acechoice45 10 ปีที่แล้ว +1

    Cool video Steve

  • @Pinoyphilly
    @Pinoyphilly 8 ปีที่แล้ว

    Steve: you rock in your videos!

  • @stf2400
    @stf2400 9 ปีที่แล้ว +1

    Wish you lived in Iowa, I have an ongoing issue with my water heater, and these jokers can't get it right.

    • @stevenlavimoniere
      @stevenlavimoniere  9 ปีที่แล้ว +1

      +Rick Karns hope you get the problem fixed

  • @anthonyhitchings1051
    @anthonyhitchings1051 2 ปีที่แล้ว

    notice how the design geniuses put a big machine screw head in the way of a wrench on the pilot gas nut at the valve?

  • @chrishasley5614
    @chrishasley5614 7 ปีที่แล้ว

    Way cool video...

  • @Burner2608
    @Burner2608 9 ปีที่แล้ว +1

    Must have been a big squirrel

  • @alivaba83
    @alivaba83 7 ปีที่แล้ว

    Hey steve I got a problem with my boiler, The pilot is on but when I turn the thermostat on the boiler won't ignite, I was braking some concrete on the basement I don't know if that has anything to do with it or is the gas valve, how can I find out?

  • @PedroRodriguez-go1zp
    @PedroRodriguez-go1zp 8 ปีที่แล้ว

    I have a problem with a heater like that
    only ignites the flame but others do not light flames
    valve will be your cambiastes

  • @PedroRodriguez-go1zp
    @PedroRodriguez-go1zp 8 ปีที่แล้ว

    if no valve ?

  • @traviskalinowski3231
    @traviskalinowski3231 5 ปีที่แล้ว

    nice has leak test

  • @thechosen5805
    @thechosen5805 5 ปีที่แล้ว

    Those honeywell valves are the worst! I had two brand new ones out the box that were no good...Use the robertshaw 24v gal valves instead

    • @nsboost
      @nsboost 5 ปีที่แล้ว

      The Chosen Honeywell valves such but the one he used isn’t that bad. I have just as many issues with Robertshaw.
      The small Honeywell valves used on most new modern furnaces (like all the air ease/Armstrong valves) are complete junk though

  • @janetsterno
    @janetsterno 6 ปีที่แล้ว +1

    word to the wise. when using flush pipe adapters always use steel like you see that Steve is using never brass or bronze. i've seen them crack before...t

  • @robertweeks1171
    @robertweeks1171 9 ปีที่แล้ว +1

    Damn bro were you getting sleepy. that was so high CO counts at first. Anything under 80 ppm is much better.

    • @stevenlavimoniere
      @stevenlavimoniere  9 ปีที่แล้ว +1

      +Robert Weeks i usally like to run the unit for a bit before putting in the probe .because of the high c.o. at first on start up

    • @nsboost
      @nsboost 5 ปีที่แล้ว

      Every gas appliance has high co on light off. Best not to put the combustion analyzer into the flue till after it has ran for at least 10-15 sec

  • @AB-sy9tf
    @AB-sy9tf 7 ปีที่แล้ว

    LOL - "Was she Russian."

  • @jasontheplumber3684
    @jasontheplumber3684 10 ปีที่แล้ว +2

    haha "she slap him around"

    • @stevenlavimoniere
      @stevenlavimoniere  10 ปีที่แล้ว

      Jason the Plumber ya she might have been a large woman ... wanting to drive the bus ..wearing the big boy panties

    • @jasontheplumber3684
      @jasontheplumber3684 10 ปีที่แล้ว +1

      lol I was thinking the same thing before you said it "was she russian"?

  • @macthemec
    @macthemec 6 ปีที่แล้ว

    Must be a joisey thing