  • @michaelcave9071
    @michaelcave9071 3 ปีที่แล้ว +5

    ⛔⛔No gas and go here⛔⛔
    Thanks for sharing, your videos are appreciated I watch a lot of catering and refrigeration videos and you give the best technical explanation, that's from catering and refrigeration technician with over 30yrs experience. 👊

    • @fret2fret221
      @fret2fret221 3 ปีที่แล้ว

      “Low charge” is not the problem. It’s a symptom of an actual real issue. Hate when guys just say “oh it’s a low charge just give it some gas...” 🙄

  • @hvactrevv23
    @hvactrevv23 3 ปีที่แล้ว +7

    Thank you for the video man. You explain everything so well it’s greatly appreciated. Nice break down and good job finding that small leak.

  • @shine-cg9uf
    @shine-cg9uf 3 ปีที่แล้ว

    Great video 📹 as always 👍. Thanks for taking the time to show n educate.

  • @sunnyeh1627
    @sunnyeh1627 ปีที่แล้ว +1

    You are a Pro Sir. Thank you for the informative video.

  • @khayberadil
    @khayberadil ปีที่แล้ว +1

    love the way you explain and cover everything.

  • @jayzzz1234
    @jayzzz1234 3 ปีที่แล้ว +1

    As usual well explained great video.

  • @AErefrigeration
    @AErefrigeration 2 ปีที่แล้ว +1

    You have good technique. I had been recovering freon to see how low it is or if a restriction has occurred. I'll start following your procedure. I've been in the field for 12 years. Never too late to improve. Thank you

  • @saltrue1555
    @saltrue1555 10 หลายเดือนก่อน +1

    What’s awesome finding, even having so small leak, thank you, I’ve been watching all your videos, always learning from your videos, I’m way more confident doing my troubleshooting, thank God bless you and your family.

  • @davejohnsonnola1536
    @davejohnsonnola1536 2 ปีที่แล้ว +3

    Good to see you back online. Know that your original intended audience is your own staff and very much appreciate your sharing.
    I got the AAS HVACR degree from community college in 1990 but remained a bartender and later F&B manager for far too long. Finally got the EPA five years ago and have been taking care of most of the equipment at my facility for the past five years.
    Davejohnsonnola

  • @philipdumond2044
    @philipdumond2044 3 ปีที่แล้ว

    Good find thanks for sharing.

  • @abdulhvac2395
    @abdulhvac2395 ปีที่แล้ว

    Thank you for sharing

  • @unknownsf0
    @unknownsf0 2 ปีที่แล้ว

    Great video

  • @IceMachine411
    @IceMachine411 2 ปีที่แล้ว

    Thank you for the video!

  • @neilvestervictor180
    @neilvestervictor180 3 ปีที่แล้ว

    great job

  • @Straw_hat_luffy2523
    @Straw_hat_luffy2523 2 ปีที่แล้ว +2

    Brother your videos are amazing I’m new In work like this I’m 26 I’m from Chicago. I’ve learned fairly skit working Rn for a service company. Going out diagnosing. I would love if you can help me read wiring diagrams like you I’d pay you. I didn’t go to school god gave me a chance and I’m sticking with it. I would love to be able to trouble shoot like you.

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  2 ปีที่แล้ว +2

      I’m thinking of doing some TH-cam lives on Saturdays breaking down schematics. My computer I was making videos on broke in the summer so I’ll see if the boss can get me a new one.

    • @Straw_hat_luffy2523
      @Straw_hat_luffy2523 2 ปีที่แล้ว +2

      @@REFRIGERATIONKITCHENEQTECH awe man I would love that an appreciate it I wouldn’t even mind paying you to show me knowledge big brother. I just want to be great out here

  • @sungkim7579
    @sungkim7579 3 ปีที่แล้ว

    Thank you

  • @mainj54
    @mainj54 3 ปีที่แล้ว

    EPA allows nitrogen pressurization with a trace gas for leak checks, which can then be vented .When you recover the full charge with nitrogen mixed in and what do you do with it?

  • @dgsrks102030
    @dgsrks102030 3 หลายเดือนก่อน

    How do you remove leak detector from schrader valves ? I usually use cap without gasket , then soap cap .

  • @bigdaddy4975
    @bigdaddy4975 4 หลายเดือนก่อน

    how do you know what to add for ambient for the coil?

  • @harrydickson4575
    @harrydickson4575 3 ปีที่แล้ว

    👍👍👍

  • @JaimeGarcia-eg2qv
    @JaimeGarcia-eg2qv 10 หลายเดือนก่อน

    I know this I a few years old but good info. My only question is how exactly were you able to determine the system was 2.5 oz low?

  • @bowen1969
    @bowen1969 3 ปีที่แล้ว +2

    Question ? How do you determine the TD of the different coils in different units/ manufacturers ? Thanks. And thanks again for sharing your knowledge

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  3 ปีที่แล้ว +8

      Most reach ins are 20td for the evap and walk ins are 10td but your superheat will ultimately determine that. For the condenser coil it gets complicated because most of the newer equipment uses a 15Td and a lot of the older stuff uses a 30TD. So it’s very important to understand saturation temps and from there you can make an educated guess as to what TD is being used.

  • @arjunapeiris981
    @arjunapeiris981 ปีที่แล้ว

    Good sir

  • @garypoplin4599
    @garypoplin4599 2 หลายเดือนก่อน

    4:50 - What would the pressures do here while adding refrigerant if there had been a restriction? I’m guessing the low would go back into a vacuum and the high wouldn’t change much? Is that right? Great video, BTW. Thanks.

  • @randomrazr
    @randomrazr 2 ปีที่แล้ว

    do u recomend TRUE coolers?

  • @shine-cg9uf
    @shine-cg9uf 3 ปีที่แล้ว

    Love ur troubleshooting skills. I have a question about line taps. Is there a place u dont put them on like discharge line. Trying to get a better sense on location for putting a line Tap on a sealed system if needed. Any ideas?

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  2 ปีที่แล้ว +1

      There is a stubby that comes out of the compressor, that is where you would hook up your low side. On the filter dryer, it will also have a stubby that has been pinched off. Attach the line tap there for you high side pressure. Do not leave the line taps on the system, they are just for troubleshooting and must be removed.

    • @shine-cg9uf
      @shine-cg9uf 2 ปีที่แล้ว

      Thankyou my friend from the north appreciate the feedback.

  • @rajram9861
    @rajram9861 ปีที่แล้ว

    hello, i would like the brand and model of your leak detector. cause in your video it works really well

  • @andersonecheverria1065
    @andersonecheverria1065 ปีที่แล้ว

    When you do the leak search with nitrogen, you add the nitrogen with the refrigerant in it, like mixingit? Or just nitrogen?

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  ปีที่แล้ว

      We need a trace amount of refrigerant in the system so that the leak detector can pick up the leak

  • @techti8792
    @techti8792 ปีที่แล้ว

    The leak detector you had originally which was that one? Which one you find more accurate the stratus or dtek 3?

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  ปีที่แล้ว

      I don’t have a stratus, only dtek 3. It finds 95% of leaks. For the last 5% the H10 is my go to.

  • @jonjordan6606
    @jonjordan6606 ปีที่แล้ว

    So did you leave the refrigerant in the system and add nitrogen just so you can have enough pressure to find a small leak? And then you will recover the contaminated refrigerant?

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  ปีที่แล้ว +2

      Recover and leave a trace amount then add the nitrogen. Then purge the nitrogen to the air once the leak was located

  • @user-ot3zk5me5l
    @user-ot3zk5me5l 2 ปีที่แล้ว

    The Stratic is a great leak detector. Shows the ppm

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  2 ปีที่แล้ว +1

      I wanted to buy it but couldn’t justify the extra couple hundred dollars for that feature. I am looking to get an H10 next and comparing them.

  • @SombraLocs
    @SombraLocs 2 ปีที่แล้ว

    What type of cooler would this be considered? It's not a reach in.

    • @REFRIGERATIONKITCHENEQTECH
      @REFRIGERATIONKITCHENEQTECH  2 ปีที่แล้ว +1

      Model is TUC, true under counter cooler. So it’s considered an under counter

  • @humberto958
    @humberto958 3 ปีที่แล้ว +1

    Those true Evaps they leak all the time. I have replaced many of those..

  • @tonychavez6756
    @tonychavez6756 2 ปีที่แล้ว

    R u charging with liquid or vapor?

  • @deanmohamed7575
    @deanmohamed7575 2 ปีที่แล้ว

    DTEK 3 is the best

  • @c21meister
    @c21meister ปีที่แล้ว

    Micro leak

  • @phxrus
    @phxrus ปีที่แล้ว

    Leaks don't fix themselves as you proven in your vidios, they will call back and then Tech/componay will look like shit