Recap of TN-S Earthing Arrangements and Measuring External Earth Fault Loop Impedance Ze

แชร์
ฝัง
  • เผยแพร่เมื่อ 2 พ.ค. 2018
  • Recap training aid for correctly identifying a single phase installation earthing arrangements in this case TN-S. The video includes the size of the meter tails, size of the earthing conductor max Ze 0.8 ohms.
    An overview of the intake position of a single phase domestic dwelling looking at the incoming supply authorities cable, cutout fuse size and using the clues to workout the earthing system.
    🔵 Playlist - Earthing Arrangements TN-S, TN-C-S and TT • Earthing Arrangements ...
    Sorry the sound isn’t as good as my later videos but all the points covered in this compilation are required during our installation theory exams thanks Gaz
    Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
    You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical.
    ▶️ FACEBOOK / gshelectrical
    ▶️ INSTAGRAM / brihzmraygdtmjmdb9lunq...
    ▶️ TWITTER / gsh_electrical
    ▶️ TikTok vm.tiktok.com/ZMRBLFdhe/
    #GSHElectrical #Electricaltrainingvideos

ความคิดเห็น • 29

  • @deanchamberlain1910
    @deanchamberlain1910 2 ปีที่แล้ว +3

    Excellent presentation…your videos are a great education thank you!

    • @GSHElectrical
      @GSHElectrical  2 ปีที่แล้ว

      Massive thanks Dean 👍🏻

  • @tombird3032
    @tombird3032 4 ปีที่แล้ว +4

    Legend u explain it so well

  • @roberthatcher2773
    @roberthatcher2773 5 ปีที่แล้ว +7

    Excellent explanation, thanks!

    • @GSHElectrical
      @GSHElectrical  5 ปีที่แล้ว

      Thanks for the fantastic feedback 👍

    • @saningolaizer1645
      @saningolaizer1645 3 ปีที่แล้ว

      This is an excellent explanation

  • @ArjunSingh-fe5sd
    @ArjunSingh-fe5sd 6 ปีที่แล้ว +3

    Quite helpful. Keep the good work going

  • @watsond83
    @watsond83 3 ปีที่แล้ว +2

    Thanks Gaz!

  • @simonmogos44
    @simonmogos44 4 ปีที่แล้ว +1

    Wha can I say just perfect
    Thanks so much for your help it helps me a lot

  • @efixx
    @efixx 3 ปีที่แล้ว +1

    More great content for Gaz on the eFIXX TH-cam channel 👍.

  • @niallers8572
    @niallers8572 6 ปีที่แล้ว +2

    Hi I would like to say this video has been some help

  • @gr8life12
    @gr8life12 6 ปีที่แล้ว

    Thank you Gaz clear as always that has definitely been some help for me as someone currently learning to be an electrician however there is one question I would like to ask. The fuse housed within the DB are you referring it to the circuit protective devices? Because I don't think I have seen any other fuse other than the cut-out fuse.🤔

    • @GSHElectrical
      @GSHElectrical  6 ปีที่แล้ว

      I am talking about the supply characteristics hence the cutout fuse 100, 80 or 60 amps. Thanks for watching and commenting GSH Electrical

    • @GSHElectrical
      @GSHElectrical  6 ปีที่แล้ว

      I am talking about the supply characteristics hence the cutout fuse 100, 80 or 60 amps. Thanks for watching and commenting GSH Electrical

  • @adriantyler1820
    @adriantyler1820 5 ปีที่แล้ว +2

    Samui English electrician working in Thailand, TT is normal.
    The problem of bringing in a 3rd conductor to a single phase building, thus making a TN-S would be the armored cable is not normal here.
    3 core CV cable (SWA without the steel armor) would be a poor choice as neutral could be a disconnect' whilst earth remains intact?

    • @wilsonfernandez5517
      @wilsonfernandez5517 4 ปีที่แล้ว

      Very bad sample demo cannot make good presentation material..

  • @johnoreilly7052
    @johnoreilly7052 4 ปีที่แล้ว

    Gary I always cut the seal of the main fuse and I always reseal the main fuse

  • @alvinashman6371
    @alvinashman6371 6 ปีที่แล้ว +1

    What size meter tails would you record on an EIC or EICR, 16mm or 25mm?

    • @brad30
      @brad30 5 ปีที่แล้ว

      You record the consumers tails which are 25mm

  • @colintatum6872
    @colintatum6872 5 ปีที่แล้ว +1

    Hi is the supply company ever actually asked or do most just pull the fuse and refit the little ties? Cheers

    • @richardfld
      @richardfld 2 ปีที่แล้ว

      should at least be responsible to notify the supplier to come and re-seal the equipment or carry your own seals.

  • @gazdkw82
    @gazdkw82 6 ปีที่แล้ว +1

    Great video as always. Is it ok to calculate R1+R2 by subtracting Ze from Zs?

    • @GSHElectrical
      @GSHElectrical  6 ปีที่แล้ว

      Hi. If you have measured Zs why would you want R1 + R2? I only every record reading I have take by measurement for. Thanks for the question Gaz

    • @gazdkw82
      @gazdkw82 6 ปีที่แล้ว +1

      GSH Electrical I agree. My tutor at college said you can reverse Zs =ze+R1+R2 but I have also been told that is not allowed. And also like you I didn't see the point unless your making half the results up.

    • @GSHElectrical
      @GSHElectrical  6 ปีที่แล้ว

      I only ever record results I measure e.g. I would have to measure Ze and not use the maximum (0.8 or 0.35) in calculating Zs = Ze + (R 1 + R2) also I would measure R1 + R2 and not calculate via length and resistance. Hope this help Gaz

    • @simonaragon1992
      @simonaragon1992 5 ปีที่แล้ว

      You can not calculate R1+R2 by subtracting from Zs because when you test the Zs you have all exposed and extraneous parts included in the test which create parallel paths! When obtaining the R1+R2 for any given cct, you want the resistance of just the Line conductor + CPC under test!. No parallel included giving inaccurate readings.

    • @simonaragon1992
      @simonaragon1992 5 ปีที่แล้ว

      Just to add also, it is permitted by BS7671 to calculate the Zs, the only problem with calculating the Zs is that you will not pick up a high resistance across a protective device/ RCD etc. A direct measurement will give you a true reading of what will actually happen in the system under fault conditions.

  • @aamrs7863
    @aamrs7863 3 ปีที่แล้ว +1

    Terra is in Italian too

    • @GSHElectrical
      @GSHElectrical  3 ปีที่แล้ว

      Thanks for commenting 👍 appreciated