TESTING ZE - TNCS - TNS - TT - WHAT ARE THE DIFFERENCES BETWEEN THE EARTHING SYSTEMS

แชร์
ฝัง
  • เผยแพร่เมื่อ 21 ก.ย. 2024
  • In this video from Learn Electrics, we will look at the differences between the common earthing systems, the things that you need to know when testing ZE. Although the testing of ZE is similar in each case, as we have shown in previous videos, there are physical differences between these systems: and it does affect the earth path for fault currents.
    Some of the more frequent questions that we have been asked have included …
    What is Ze?
    Which part of an electrical system is Ze and which part is Zs
    Why is Ze so very different in TT systems and is Ze different between TN-C-S and TNS systems?
    In fact, what is a TNCS system
    So in this video we will address these questions
    To view all of our videos type in LearnElectrics all one word into the TH-cam search bar.
    This is video No.166 on our TH-cam channel where we have videos on a wide range of electrical topics.

ความคิดเห็น • 94

  • @3789gaz
    @3789gaz ปีที่แล้ว +14

    Just want to say a huge thanks for this and all of the previous content you've made available. It's been no end of help to me whilst re-training into the electrical industry on the C&G 2357 and 2391. Brilliant reference material explained clearly, it is very much appreciated! Thank you.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +5

      That's good to know Gareth and so happy it helped. Never stop learning, its a great trade to be in. Good luck with your future career, go get it! Dave.

  • @ItsShayn3_
    @ItsShayn3_ ปีที่แล้ว +4

    I’ve always had an idea of TNS and TNCS but not TT, thank you learn electrics!

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +2

      That's great that you've found it useful. Thanks for watching Smoovy, appreciated.

  • @richierich8334
    @richierich8334 ปีที่แล้ว +3

    Not even 6am on a monday and they uploaded a video. That's devotion ;)

  • @john2181
    @john2181 ปีที่แล้ว +2

    Great videos, I'm working through them one by one and finding them a huge help. Thank you 👍

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      Glad you like them John, lots more to come. Dave.

  • @mouni2008ify
    @mouni2008ify ปีที่แล้ว +2

    The Best lessons electrical, thanks.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      Glad you think so, much appreciated. Thanks for watching.

  • @alancooper7018
    @alancooper7018 ปีที่แล้ว +1

    Another first rate teaching video! Thanks

  • @ashfaqahmed-jh1yu
    @ashfaqahmed-jh1yu หลายเดือนก่อน

    Very informative and well explained video

  • @iqbalnuthoo1566
    @iqbalnuthoo1566 หลายเดือนก่อน

    Simply the best, as always

  • @philrichmond7567
    @philrichmond7567 ปีที่แล้ว +1

    Thank you for sharing. Your video's are always welcome. 👍🏼

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      That's good to know Phil. Thanks for supporting the channel. Dave.

  • @heron9524
    @heron9524 ปีที่แล้ว +2

    Brilliantly explained.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      Glad you liked it Denis and thanks for the feedback. Dave.

  • @michaelwaheeb4998
    @michaelwaheeb4998 ปีที่แล้ว +2

    Always great lesson

  • @MRMSB
    @MRMSB ปีที่แล้ว

    Your video is very informative and better than paid courses

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Nice of you to say that, thanks. Very much appreciated.

  • @clydegibson2850
    @clydegibson2850 8 หลายเดือนก่อน

    Excellent explanation

  • @cardinal24
    @cardinal24 ปีที่แล้ว

    It's fun to watch these, since TT aren't allowed in Sweden where I live, and unless the building is from the early 50's or older, all houses regardless of there use are 3 phase here, a normal house hold have 3 x 16 Amp fuses, since we never use single phase anymore and haven't done so for some 60+ years here. Most have TN-C too the meter and then we make them TN-C-S inside the houses. Greetings from Sweden 😁

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Thanks for the info and thanks for watching. Dave.

  • @testingtechnicians6751
    @testingtechnicians6751 ปีที่แล้ว

    You nailed on my doubts Dave, thanks again

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Glad it was useful, thanks for watching the channel.

  • @Dibbo1979
    @Dibbo1979 ปีที่แล้ว +2

    Great video

  • @kingofthetrowel1725
    @kingofthetrowel1725 ปีที่แล้ว +3

    Nice one dave another brilliant video 👍👍 can I ask, maybe a silly question but what happens if the Ze is well over maximum value (does it ever happen) do you just notify the dno and leave it with them .cheers dave 👍

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      Its never happened to me but yes, we should notify them because our own work won't pass the tests.
      I know of one sparky who contacted them, told them the customer was in danger and they were there in an hour,
      Dave.

    • @kingofthetrowel1725
      @kingofthetrowel1725 ปีที่แล้ว +1

      @@learnelectrics4402 cheers dave good to know 🙌🏻🙌🏻 not sure if you have done one yet but will you be able to do a video on multi function testers functions 2 lead high etc especially a merger as that’s one I’ll probably invest in when the time comes 👍👍

  • @mdmvukengineer4873
    @mdmvukengineer4873 ปีที่แล้ว +1

    Excellent 👍

  • @murrayedington
    @murrayedington ปีที่แล้ว +1

    We had a TT system in our house in Cambs (overhead supply). The earth was bonded to the copper water pipes instead of an earth rod. Problem was, the incoming water (and gas) pipes were plastic. With a typical collection of appliances connected up, there was enough leakage current to earth to give a fine belt when touching the taps. It now has a proper 1m long ground rod.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Yes, some of the old methods left a lot to be desired. I stopped in a chalet on a remote Scottish island that was like that. Thanks for watching. Dave.

  • @johnkeys368
    @johnkeys368 ปีที่แล้ว

    Always excellent explanations thank you.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Glad you like them and thanks for the feedback, appreciated.

  • @lllCANDYMAANlll
    @lllCANDYMAANlll ปีที่แล้ว

    The solder blob picture at 10:36 to me looks like a tncs system as the supply cable is combinig the two and then it sepeartes at the earth bar. Im sure ive misunderstood somehow? I appreciate your videos, ive learned so much.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Trust me, its a TNS and the best clue to identifying TNS systems. But its good to question. Thanks for watching. Dave.

  • @shorty57red
    @shorty57red ปีที่แล้ว +1

    Absolutely Love Learn Electrics explanations. But audio is often awful!

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      Thanks for the feedback Kevin, I do take it seriously. I've listened to this video on the laptop, on the ipad and on my Samsung phone and cannot find a problem with it. I know a couple of folk have said the audio is bad and over this year I've tried two new microphones (expensive ones) and a new laptop. I've also tried listening on two different sets of headphones but still can;t get bad audio. I've tried to resolve it Kevin, but can't find a problem. Thanks again for the feedback and for supporting the channel, appreciated. Dave.

    • @shorty57red
      @shorty57red ปีที่แล้ว +1

      @@learnelectrics4402 Thanks Dave for investigating audio quality, probably a Gremlin, I am listening on a n iPad with apple headphones & listen to various you tube videos after each other & this one was quite bad audio wise, won’t stop me listening to you as your explanations are superb. I should have retired last year but still love what I do. Never too old learn in my experience.

  • @christopherblomeley6925
    @christopherblomeley6925 ปีที่แล้ว

    Brilliant video nice and clear, great pace...

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Thank you Christopher and thanks for watching. Great feedback. Dave.

  • @ssathish9120
    @ssathish9120 ปีที่แล้ว

    Thank you for sharing the video.

  • @musangobi2079
    @musangobi2079 ปีที่แล้ว +1

    Most pple in my country use TNC. S but with earth rod on building . So in case of fault which path does the fault current use back to the transformer, neutral or earth rod then to soil upto transformer

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      The fault current will share itself along both routes according to the conductance, so most will flow along the metallic neutral/Earth. The earth rod could be there to balance any potential differences around the building. Thanks for watching. Appreciated.

    • @musangobi2079
      @musangobi2079 ปีที่แล้ว

      Thank you

  • @velusamypothiraj2300
    @velusamypothiraj2300 ปีที่แล้ว +1

    Sir, you missed earth symbol at transformer neutral point I tns and tncs system.

  • @williamcorcoran8842
    @williamcorcoran8842 11 หลายเดือนก่อน

    Fantastic video!!! Brilliant!

    • @learnelectrics4402
      @learnelectrics4402  11 หลายเดือนก่อน

      Many thanks, glad you enjoyed it. Dave.

  • @IAmThe_RA
    @IAmThe_RA ปีที่แล้ว +1

    What if we have TT like in the video but we also combine neutral and earth in the meter? I think that's what we have here, in fact the earth and neutral terminals in the meter are linked by design. I used a multimeter to confirm the continuity between both terminals of the new meter (uninstalled).

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      In the UK there are only Line and Neutral connections in the meter. Thanks for watching. Dave.

    • @okaro6595
      @okaro6595 3 หลายเดือนก่อน

      Then it is not TT. It is TN-C-S. A multimeter is not a proper tool for such measurements.

  • @nkoyoyojohnpaul7089
    @nkoyoyojohnpaul7089 ปีที่แล้ว

    Thanks so much

  • @Gh0stt007
    @Gh0stt007 ปีที่แล้ว

    This channel is so good! I learn a lot about electrics with every your video! But please - buy a better microphone or just adjust current one.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      I've tried a new mic and now I'm on a new laptop so let's see. Thanks for watching. Dave.

  • @ja_adam_
    @ja_adam_ ปีที่แล้ว

    Love your vids. I’m currently studying.. please could you do a video explaining how neutral and earth are connected together yet no current flows back on the earth and down all your cpc’s? I don’t understand how earth and neutral are connected together and also I don’t get how current can flow through the ground in a TT to disconnect when soil is an insulator
    Thanks

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Thanks Jake. Watch the video again, it tells you what happens to the fault current in a TT system.

    • @okaro6595
      @okaro6595 3 หลายเดือนก่อน

      The resistance of the PEN-wire is so low that only minimal current goes other routes. If the PEN wire breaks then it is another matter.

  • @ja_adam_
    @ja_adam_ ปีที่แล้ว +1

    Also what is an IT system ? Could you do a video please
    Thanks

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      IT is an insulated earth system and a specialised earthing system.

  • @tonyp2878
    @tonyp2878 ปีที่แล้ว +1

    There should be an isolator in that meter box

  • @usoip8482
    @usoip8482 10 หลายเดือนก่อน

    I NEED HELP, I need to understand why and how, in a fault the cpc becomes live and takes current to the transformer and due to the lower resistance there is an imbalance in the neutral/Live so the breakers trip, THATS WHAT IVE BEEN TOLD, doesn’t make sense because if the cpc cable is smaller in size there would be more resistance not less right? And how would that affect the breakers, does the mechanism in breakers trip become the neutral does not have a return path or something else

    • @learnelectrics4402
      @learnelectrics4402  10 หลายเดือนก่อน

      Have a look at these videos. the answer lies in the loop impedance. The LearnElectrics.com website also has a search box to find videos on specific topics.
      th-cam.com/video/A9Zze4uNgRw/w-d-xo.html
      and
      th-cam.com/video/QWr-ilqW67A/w-d-xo.html

  • @tahamirzakhani4587
    @tahamirzakhani4587 ปีที่แล้ว

    Thanks 🙏

  • @brianhewitt8618
    @brianhewitt8618 ปีที่แล้ว +1

    👍

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +2

      Thanks for watching Brian. Always appreciate good feedback. Dave.

  • @damss2724
    @damss2724 ปีที่แล้ว

    What do you call the earthing system in metro Manila where two hots/phases(L1&L2) and PE is going through to the CU?

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      These videos are aligned to the UK Wiring Regulations. Much of the information is also relevant to electrics elsewhere but not every situation can be covered by them. Thanks for watching though, appreciated.

    • @damss2724
      @damss2724 ปีที่แล้ว

      Do you know sir European country doing this L1,L2 + PE? Thnx

  • @spelunkerd
    @spelunkerd ปีที่แล้ว

    In the UK, if a home has a whole house RCD, is it likely the home is on a TT system? Or, are whole house RCD's implemented so widely, one can't make any inference about the underlying earthing system?

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +2

      Nowadays, it can be any earthing system as RCD devices have become so common and the prices have dropped. All new domestic installations now will have RCDs for all circuits. Once you learn how to recognise the different systems, you don't forget. Hope this helps.

    • @spelunkerd
      @spelunkerd ปีที่แล้ว

      @@learnelectrics4402 Thanks, your video helped to clarify my past understanding. I live across the pond in Canada, where TNCS dominates. When we visit our daughter north of London, I've often wondered what system they are using in the old British country home they live in now.

    • @deancook2123
      @deancook2123 ปีที่แล้ว

      The narrator sounds very much like my old tech college teacher John West 🤔 brings back memories, he was a great teacher in simplifying electrical installation & theory

  • @saysles
    @saysles ปีที่แล้ว +1

    voice is overloading the mic resulting in very distorted audio
    This is very common when no broadcasting experts are employed

    • @MS-Patriot2
      @MS-Patriot2 ปีที่แล้ว

      Only recently has this overload been apparent. Dave might have a new microphone?

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      I've not got a studio Les but thanks for the info. Dave.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      Thanks Mike. I've just got a new lap top, the old one was starting to play up (it was 12 years old). That might have been part of the problem. Thanks for the support.

    • @MS-Patriot2
      @MS-Patriot2 ปีที่แล้ว

      @@learnelectrics4402 It was about 6-8 weeks ago that I noticed some distortion on your narrative. Prior to that it was very clear. With digital stuff you don’t want to peak at 0dB like analogue, better to peak around -20dB if you have a means of monitoring your audio level.

    • @marlonw5429
      @marlonw5429 ปีที่แล้ว +2

      Employ a broadcast expert? Are you having a laugh?
      Yes it’s a bit grainy but is fully comprehensible and is full of decent content!

  • @vachikyadegarian1403
    @vachikyadegarian1403 ปีที่แล้ว

    Hi Dave ,is it common to convert an existing TNS to a TNCS TO upgrade the earthing and how is it done without removing the TNS Part of the system pls.Big Thank you.

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว +1

      This is something you need to discuss with your supplier as this will require changing the supplier's cables.
      Thanks for watching. Dave.