Loop Impedance

แชร์
ฝัง
  • เผยแพร่เมื่อ 21 ก.ย. 2024
  • Loop impedance, why it matters and typical values expected for smaller installations (100A or less).
    ► Support this channel:
    Patreon: / jwflame
    PayPal Donations: xo4.uk/?PPP
    ► Social Media:
    Twitter: / jwflame
    Facebook: / jwflame
    Instagram: / jwflame
    ► Contact info, sending stuff in: etc.:
    xo4.uk/?YTT
    ► Website - More on this video and many other subjects
    Website: www.flameport.com
    Page for this video: xo4.uk/?Zes

ความคิดเห็น • 198

  • @tspirit99
    @tspirit99 7 ปีที่แล้ว +6

    Hi john, currently studying to become a fully qualified pat tester along with my 17th edition professional course... i have 5 weeks total time for this course and i have faith with passing the course because of your great and easy understanding videos. Thank you! all the best!

  • @garethpreston8275
    @garethpreston8275 7 ปีที่แล้ว +21

    As a registered electrician this would have to be the most straight forward explanation of loop impedance I have heard. As a colonial it would also be the hardest compliment I have ever had to give. Well done Mr Ward.

    • @Japanese_one_Tokyo
      @Japanese_one_Tokyo 5 ปีที่แล้ว

      Gareth Preston I’m currently studying level 2 Electrical installation and I’m forced to stuff my brain with BS! This is painful to obtain without day dreaming here and there.
      As a registered electrician do we really need to know this stuff out in the real world?

    • @L.C.Sweeney
      @L.C.Sweeney 2 ปีที่แล้ว

      @@Japanese_one_Tokyo you should probably not be an electrician if you think this is BS

  • @mohamedbaghdadi778
    @mohamedbaghdadi778 4 ปีที่แล้ว +3

    Many thanks John honestly you are the best teacher who's given electrical lessons.

  • @guyfriday6066
    @guyfriday6066 6 ปีที่แล้ว +8

    1st year apprentice here, these videos are amazing, really helping me to grasp everything being thrown at me. Thanks, John.

  • @jimim8514
    @jimim8514 5 ปีที่แล้ว +6

    Superb work Mr Ward yet again, your the teacher I never had until now, thank you for your time, guidance & sharing your knowledge

  • @Brainchild110
    @Brainchild110 8 ปีที่แล้ว +6

    Dear JW, I spent my day repairing some terrible electrics in a rented house, and testing the system once built. Only to realise I don't feel confident doing the loop impedance test and calculations yet, which are necessary here. I manage to delay this for my next visit, get home, and lo-and-behold you have released a very useful video, almost specifically for me!
    Thank you!... Now excuse me while I watch this 10 more times.

    • @iang3802
      @iang3802 8 ปีที่แล้ว +5

      If your loop impedance tester (or the loop function of a multifunction tester) gives a reading for the Prospective Fault Current (PFC) in Amps (or KiloAmps) as well as the actual loop impedances (Ze and Zs) in Ohms and the voltage between L and E in Volts, the PFC reading that you see may be less than the value that you obtain from your calculation. SOME (but not all) test meter manufacturers 'build in' an assumed power factor of 0.84, so you MAY need to multiply the Fault Current value that you get from following JW's excellent tutorial by 0.84 for it to agree with your meter's PFC indication. Hope this helps.

  • @oliverhill113
    @oliverhill113 6 ปีที่แล้ว +6

    Thank you John for giving this very clear explanation. My electrician has said the Ze test was high. I now know what that means!

  • @grahamworthy100
    @grahamworthy100 4 ปีที่แล้ว +2

    Hi John just to say a BIG THANK YOU on your help in passing on knowledge to all us electricians out here in the field doing our day today stuff 👌

  • @cerealkiller4248
    @cerealkiller4248 3 ปีที่แล้ว

    I’m a mechanical engineer and I fault find on many differing pieces of kit. Now boiler technicians should be carrying out impedance checks. This has clarified what previously felt a complex topic, thanks for taking the time to explain it.

  • @fieldsofomagh
    @fieldsofomagh 8 ปีที่แล้ว +18

    Best insight into loop impedance that I've seen.Great handle on all things electrical.

  • @peterstiles1
    @peterstiles1 5 ปีที่แล้ว +2

    You think you know all this but these videos settle it clearly in your mind. Wish I'd seen them when I was at college.
    Great stuff, thanks for posting.

  • @CarlosArruda77
    @CarlosArruda77 8 ปีที่แล้ว +2

    JW, mate, another great video. It's good to refresh memory after having finished my level 2 and 3, 17th edition and inspection and testing a year ago! Very interesting!!! Keep them coming mate. Many thanks. Albert

  • @byronjones3579
    @byronjones3579 6 ปีที่แล้ว +4

    Thanks John better than my teachers at college

  • @ekul8766
    @ekul8766 6 ปีที่แล้ว +3

    Wow I always got ze and zs mixed up now I know what they stand for ill remember it THANKS

  • @alizeray3569
    @alizeray3569 6 ปีที่แล้ว

    Wel done John Ward!!!!! I had been struggling to understand this concept before I fond your explanation. I admire your precise and clear English usage as English my second language, the language of BS7671 was very difficult for me. Now I get it!!!

  • @ferventheat
    @ferventheat 6 ปีที่แล้ว

    I like that you explain slowly and make it clear. It all makes sense
    In addition, TT systems need RCDs for fault protection due to low values of PFC, TNS and TNCS have RCDs as additional protection not for fault current protection which the MCBS, when of suitable [B] type, handle well.
    Thanks for your videos. All the best

  • @56jmack
    @56jmack 8 ปีที่แล้ว +2

    finally explained in a way i understand,Thanks John

  • @lukeleaflif999
    @lukeleaflif999 7 ปีที่แล้ว

    My new hobby is watching your videos and I've been off the tools for ten years.

  • @michaelcosgrove7769
    @michaelcosgrove7769 8 ปีที่แล้ว +2

    Always enjoy watching your videos JW, very informative and thank you for posting.

  • @ashishkumar542
    @ashishkumar542 3 ปีที่แล้ว

    Explained in simplest way. Thanks for sharing.

  • @robertsaka8943
    @robertsaka8943 7 ปีที่แล้ว

    Hi John your theoretical applications are brilliant I can now solve what i thought were problems for the last 15yrs. thanks.

  • @trajo189
    @trajo189 7 หลายเดือนก่อน

    this info is connecting it all together. great video. thank you for making them!

  • @alunroberts1439
    @alunroberts1439 3 ปีที่แล้ว

    Good work reminds me of day at college were we had a test board were we added load slow on 32 Amp MCB also re wire type pulling 40 45 50 Amps looking at thermal camera showing it don't trip at 40 Amp to 45 Amp for a long time. It did trip faster with a inrush current but with slow build up did stay on for a long time. When 1st training I had it that MCB's would trip with 40 Amps. Like watching an taking notes as am renewing my qualifications there are bits I forget about a good re fresh is always good.

  • @gurkankaracan8418
    @gurkankaracan8418 5 ปีที่แล้ว

    Super explaination this also shows how the given zs values of bs7671 are obtained by IET well done.

  • @josephking1947
    @josephking1947 3 ปีที่แล้ว

    Informative clearly explained and a bit of humour thrown in...

  • @MBBeier
    @MBBeier 7 ปีที่แล้ว +4

    Preparing for an exam, watching your videos as inspiration, funny differences in Denmark the TT can be up to 1666.6 Ohm for private residence and 833.3 Ohms for farms
    50V 30mA
    50/0,03 = 1666.6 Ohm
    25/0,03 = 833.3 Ohm
    Didnt know we set the bar extra ordinary low for the earth electrode.
    All of this is on the other side of the RCD/RCCD.
    Next up; We don't have B-C-D rating on 'MCB' here, we have two types, but that is related to AC and AC+DC, its only the fuses that are B-C-D, and B isnt used, C with x10 is used close to always.
    I find it interesting with the differences between the Euro countries in how we do the safety.

  • @DCElectrixPembury
    @DCElectrixPembury 8 ปีที่แล้ว +16

    You cannot connect your multimeter to the earth fault loop because "it will blow up in a ball of flames and be destroyed" . Now that's a proper warning! Also true

    • @jmx318
      @jmx318 3 ปีที่แล้ว

      I dont get it? Why

    • @brendamayfuller8803
      @brendamayfuller8803 3 ปีที่แล้ว +1

      @@jmx318 Because a multimeter set to measure resistance assumes the circuit is dead ie no voltage or current. When measuring resistance, your multimeter puts voltage into the circuit to work out resistance. And by trying to measure the resistance on a live circuit you are going to effectively create a short inside your multimeter. And since the wiring/circuit inside the multimeter is a lot smaller and more fragile than mains coming in, it is going to fail. Spectacularly in some cases. This is one of those areas that requires specialized equipment and shouldn't be done by anyone without the correct training.
      I have tried to simplify my explanation as much as possible, so no one throw rocks at me please for leaving out some details.

    • @Dog-whisperer7494
      @Dog-whisperer7494 3 ปีที่แล้ว

      @@brendamayfuller8803 the same will happen if you set a multifunction tester to measure continuity and try to test the loop impedance Ze or ZS your MFT will need a costly repair

  • @motorone5301
    @motorone5301 5 ปีที่แล้ว +2

    Great video again. The colleges should bring back the City & Guilds Part C Electrical Installation courses. JW great lecture .

    • @ianmalone8053
      @ianmalone8053 4 ปีที่แล้ว

      Not everyone passed or was able to complete, better with a multiple choice and everyone passing. We live in a different world.

    • @Prawnchowmein
      @Prawnchowmein 4 ปีที่แล้ว

      Ian Malone so true I done this years ago and it ain’t even recognised by most employers however the IET do still recognise it if anyone is looking for their accreditation’s

  • @MrNorthj
    @MrNorthj 7 ปีที่แล้ว +1

    Thanks for the video John. It gave me a full understanding of the topic :)

  • @jacquisunflower1
    @jacquisunflower1 7 ปีที่แล้ว +1

    Hi John. Your videos are very clear and easy to understand...a picture paints a thousand words and I particularly like the explanations of why things are as they are as well as how. Have you got any video explanations on how AC works physically as none seem to be around good enough to explain to a thicko like me new to the electricity story. For example, if the electrons travel in both directions, why is the Line 230V and the Neutral 0 volts, surely the potential difference in both wires should swap round with the hertz frequency....I'm obviously confused and demented, hence why I need a video and some pictures to explain! Congrats on a great series of really informative talks.

  • @johnschlesinger2009
    @johnschlesinger2009 5 ปีที่แล้ว +8

    A good, clear explanation. However, students might further their understanding if you had included the earth electrode at the substation transformer.

  • @Sparks9133
    @Sparks9133 5 ปีที่แล้ว

    Thanks John keep educating us please

  • @dhadumia
    @dhadumia 5 ปีที่แล้ว

    Great video. I love the stuff you put up and the way you explain things.

  • @mule4541
    @mule4541 4 ปีที่แล้ว

    The best explanation ever. Thank you

  • @matejunsagris
    @matejunsagris หลายเดือนก่อน

    In latvia tnc in domestic is between 4-10ohm. Law is saying domestic should be not more than 10ohm

  • @KazKasozi
    @KazKasozi 2 ปีที่แล้ว

    Fabulous explanation JW. Thank you.

  • @bc82870
    @bc82870 4 ปีที่แล้ว

    best i hv seen so far. thank you, John!

  • @jodiebrown4603
    @jodiebrown4603 5 ปีที่แล้ว +2

    Thanks John for such a clear explanation .
    Btw when are you going to make a video of you playing that organ?

  • @deniscotter525
    @deniscotter525 6 ปีที่แล้ว

    Excellent, Lecture, very well explained.

  • @quadrantheatingelectricspl2907
    @quadrantheatingelectricspl2907 5 ปีที่แล้ว

    Excellent video, very detailed thanks Jw

  • @muamerho01
    @muamerho01 5 ปีที่แล้ว +1

    Great explanation, thank you.

  • @Monkey3353
    @Monkey3353 2 ปีที่แล้ว

    We learn to manage think from your video

  • @sbusweb
    @sbusweb 8 ปีที่แล้ว +3

    +John Ward
    Zs makes sense as the 'minimum fault current' that may flow -- wrt Maximum Sizing+Type of circuit-breakers....
    BUT what about the 'maximum fault current' (which notably may be the L-N path [e.g. in TT]), may be important for that MCB 'breaking capacity' etc. ?
    Is there an equivalent ''Zn'' (or whatever) measurement used to calculate that 'maximum fault current' especially in the case of TT supplies where the Zs reading won't be meaningful for L-N faults?
    [more generally, maybe testers/designers ordinarially consider the Zs/Ze for L-N L-E faults separately i.e. 2 sets of values in all cases?]

    • @TeamSimpsonRacing
      @TeamSimpsonRacing 5 ปีที่แล้ว +1

      After you have carried out a ZE test at the board the next Tests are PFC (prospective fault current) and PSCC (prospective short circuit current). The PSCC is between line and neutral and will give you the measurements you asked for above.

  • @tochriss
    @tochriss 5 ปีที่แล้ว +1

    When you said short out the mains and things go bang, I was reminded of the occasion I'd made an electro magnet at junior school from a battery, winding and a nail. I decided to make a much more powerful one with a winding powered by the L and N of the mains! Bang. Parents not amused!

  • @SKraus-pb1ii
    @SKraus-pb1ii 3 ปีที่แล้ว

    Thanks very much, great explanation. Love your channel, have learned a lot so far!

  • @christastic100
    @christastic100 5 ปีที่แล้ว

    Just to mention that BS7671 says for TT systems 200 ohms is the maximum ZS in the UK . Regs table 41.5 note2 states for 30 ma and 100 ma RCD device a value not exceeding 200 ohms may not be stable.

  • @vernonjones3613
    @vernonjones3613 6 ปีที่แล้ว

    Brat video John has usual you explain it so even I can understand thanks

  • @jamesbrooks6130
    @jamesbrooks6130 7 ปีที่แล้ว +4

    great video John. however I feel that there are a few things are incorrect with you TT earthing arrangement. the current regulations and on-site guide states a maximum Ze of 200 ohms and makes no reference to the 100 ohms stated in your video. the 21 ohm reference is at the supply transformer not at the installation (page 11 on-site guide also on page 60 table 41.5 BS7671) if you use 200 ohms which is the worst case scenario your external earth loop impedance is 1.15amps. also you make reference to protective device tripping which is not correct terminology they infact disconnect. also you also mention MCB's these are only valid if you install a miniature consumer units, they are referenced as circuit breakers in part 2 definitions and throughout the BS7671 and ON-SITE GUIDE. other than that your videos are great and explain the points very clearly.

  • @manwithnoname408
    @manwithnoname408 3 ปีที่แล้ว +1

    John I really enjoy the way you teach. I am trying to change profession at 60 years of age.🥺. I want to be a Domestic electrician, in as short a period as possible (self-employed, small jobs around domestic environments).I have a reasonable knowledge of electrical physics & maths. I have been told I need to do the 18th Edition + 1 or 2 other C&G courses (?) to legally practice. Also an electrician friend will let me shadow him for practical learning . But, only after acquisition of relevant certificates for Domestic electrician. Can you please advise on Domestic electrician:
    1.which basic certificates do I need .(so as to work self employed)
    2. Is there a place (on line) where I can learn to pass ( somewhere ,where it is Taught the way you teach).
    I am having to watch another channel & it’s doing my head in. You guidance will be gratefully appreciated.

    • @jwflame
      @jwflame  3 ปีที่แล้ว

      The options are described here: www.electricalcareers.co.uk/joining-the-industry/training-routes/
      It's essential to obtain experience actually working with another electrician while doing the Level 2 and 3 courses, they are not intended to be taken on their own without doing practical work.

  • @barryg3431
    @barryg3431 4 ปีที่แล้ว

    This has been a great help. very well explained

  • @akguest5551
    @akguest5551 2 ปีที่แล้ว

    Awesome video very nicely explained 🙌🏼

  • @Rafal_Drapiewski
    @Rafal_Drapiewski 6 ปีที่แล้ว

    W polskiej normie PN-HD 60364-6:2008 dopuszczalne jest Z

  • @pedrojardim325
    @pedrojardim325 ปีที่แล้ว

    Thanks John
    For. A. Very good explanation
    On. This. Videos

  • @jamesslingsby9005
    @jamesslingsby9005 3 ปีที่แล้ว

    Thanks John. That is very informative. I have a couple of questions.
    1. Does the Ze need to be low enough to blow what is most commonly likely to be a 100 amp BS88 fuse?
    2. If so, what is the requirement for this to occur? For 60898 types B,C and D you multiply the current rating of the fuse by 5,10 and 20 respectively. What is the requirement with BS88 fuses?
    3. Where in the regs can I find this information?

    • @jwflame
      @jwflame  3 ปีที่แล้ว +1

      1 - It often is, but doesn't have to be, and certainly won't be on a TT system.
      2 - Depends on the fuse type and rating, it's not a linear relationship as it's relying on a piece of wire to heat up and melt.
      3 - Figure 3A1 on page 364 of the blue 18th edition BS7671. BS88-3 fuse system C. 580 amps for a 5 second disconnection time with a 100A fuse, which would need a Ze of 0.4 ohms or less. More detailed info can be obtained from fuse manufacturers.

  • @johnburns4017
    @johnburns4017 3 ปีที่แล้ว

    John, you mention using type C (x 10 amp cut out, while type B is x 5). You mention that if the cut out lag is too long an RCD (RCBO) would cut in anyway. So it looks like the long lag of a type C is negated by an RCD?

  • @angelofranklin1
    @angelofranklin1 3 ปีที่แล้ว

    The explanation is good but would have been a lot better if you had included the time/current curves with the adiabatic equation showing the minimum size of earth required, particularly where the fault current time is not instantaneous. Sorry if I'm the bug in the works John.

  • @dominikgrabowski7448
    @dominikgrabowski7448 2 ปีที่แล้ว

    Why we multiple by 5 times Current for type B breaker and 10 times for type C.
    I dont get it why we must multipy those values. Could you explain please ?. all rest very well explained, i am much apraciated.

  • @jackson1981uk
    @jackson1981uk 7 ปีที่แล้ว

    Thank you John really good video

  • @marcuscicero6029
    @marcuscicero6029 8 ปีที่แล้ว

    Excellent video. Thanks.

  • @rodabod
    @rodabod 6 ปีที่แล้ว +1

    Hi John. Thanks for the excellent lesson. I currently have a 2.1 Ohm Ze measurement at my TNS incoming line. It previously used a sweated earth braid but has a later clip. UK Power Networks measured directly at the lead sheath and say it’s still in excess of 0.8 Ohms so the clip is not responsible. They are currently refusing to rectify the situation saying that they are not responsible for providing an earth. However, an earth was originally provided, and I note that the Electricity Act 2002 states: “A distributor or meter operator shall ensure that each item of his equipment which is on a consumer’s premises but which is not under the control of the consumer (whether forming part of the consumer’s installation or not) is-
    (a) suitable for its purpose;
    (b) installed and, so far as is reasonably practicable, maintained so as to prevent danger”.
    Do you know if there is any reason why they would legally not be required to maintain the earth? They originally told me it had to still use the original sweated earth braid, but I see that they suggest using earth clips themselves in their own earthing guides(!).
    Thanks.

    • @jwflame
      @jwflame  6 ปีที่แล้ว

      They should maintain / repair it, but they will be relying on the 'reasonably practicable' part to do nothing, as in most cases the repair would involve digging up the road to locate the faulty joint, which is probably an ancient cast iron box and the fault being corrosion where the outer sheath of the cable was jointed to the cast iron. Doing that is expensive, and if one has failed it's likely that the whole street is in the same condition.
      There are a number of locations in Poole and Bournemouth with the same problems, and the 'fix' there is that SSE just install a 2 pole 100mA time delay RCD after the meter to ensure disconnection if a fault occurs, effectively making it into a TT install and using the lead cable outer as the earth electrode (being buried in the ground it is suitable for that.).
      It's therefore unlikely you will convince them to repair it properly.

    • @rodabod
      @rodabod 6 ปีที่แล้ว

      John Ward Thanks for the quick reply. I’d rather not convert to TT with an earth spike for various reasons, but mainly because I don’t see why the supplier shouldn’t maintain their connection rather than expecting me to pay. I had a similar situation with unacceptable lead levels and Thames Water; they eventually agreed to dig up the road and replace with plastic. I guess I may have to go down the legal route.

  • @aidancilialacorte5177
    @aidancilialacorte5177 6 ปีที่แล้ว

    you are simply the best!!!! thanks

  • @greywolf271
    @greywolf271 4 ปีที่แล้ว

    John, at 6:33 you mention that an impedance test of the supplier's side might make use of a generator to inject current into the supply side. Now I assume you say this for an inactive supply side where the supplier makes the measurement themselves and informs the electrician of the value measured ? Or did you mean something else ? The other question is if you put a load across the supply and do it yourself, you would be hard pressed to load the supply and get a range of measurements to work out the supply internal impedance. Can you elaborate on this if possible ?

  • @ហ៊ន់វណ្ណធី
    @ហ៊ន់វណ្ណធី 5 ปีที่แล้ว +1

    Short Circuit is 287A something, then why circuit breaker's Breaking capacity is up to 6kA, 10kA..?

    • @jwflame
      @jwflame  5 ปีที่แล้ว +1

      0.8 ohms and 287A is a typical maximum value for a TN-S supply. In reality it can be much lower, and fault current much higher.

    • @sbusweb
      @sbusweb 5 ปีที่แล้ว +1

      @@jwflame I was about to ask about the minimums in practice you come across!.
      What about people who live right next door to the substation transformer? -- Do the DNO wire then 'backwards' from some distance away to increase the impedance to a sensible minimum? -- Do they put in an intentional impedance-block in series with the supply to those nearest the station? Does the transformer winding itself provide sufficient impedance to be an acceptable-minimum?. Is there a ESQCR-like regulation or other regulation for impedances provided to customers, anyhow? -- i.e. where do these 0.35 0.8 etc. magically come from?!?!?.

  • @pyotrleflegin7255
    @pyotrleflegin7255 8 ปีที่แล้ว

    I really appreciate your videos; this one is particularly appropriate as I helped the electrician working on my property yesterday to carry out these very tests! btw -- do you teach at a Tech College?
    Thanks again,
    PL

  • @ivandrago8299
    @ivandrago8299 8 ปีที่แล้ว

    Great video John, I think you should explain how the maximum permitted Ze on a TT system depends on the Touch Voltage Formula and how the result has to be less than or equal to 50Volts. Just saying anything over 100ohms should be investigated doesn't explain why the measured reading is acceptable or not.
    I've been testing for 10+ years on the daily, mostly EICRs, and I'd love to hear your guidance on Maximum Demand.

    • @jwflame
      @jwflame  8 ปีที่แล้ว +1

      Maximum Demand & Diversity: th-cam.com/video/Wq0uODypaGI/w-d-xo.html

    • @Error-hv4on
      @Error-hv4on 8 ปีที่แล้ว

      Your allowed up to 1666 ohms on a TT BUT anything over 200 ohms should be investigated.

    • @ivandrago8299
      @ivandrago8299 8 ปีที่แล้ว

      Electric Pulse Not correct. Your reading must comply with the Touch Voltage Formula.
      This is the only acceptable reading.
      200Ohms is just a generally accepted reading for a 'stable earth'.
      The 1667 ohms you are referring to is for a TT system with a 30mA RCD on the Mains.
      500ohms is for a TT earthing system with a 100mA RCD on the Mains.
      But all must comply with the TVF.

    • @Error-hv4on
      @Error-hv4on 8 ปีที่แล้ว

      +Ivan Drago I was talking about domestic TT installations so of course they are all 30mA rcd protected so 200 ohms & under is ok,but 1667 is acceptable using the 50v safe touch voltage.50v/0.03=1667.You don't have to explain too much,I'm a sparky not a plumber ha ha

    • @carl190379
      @carl190379 7 ปีที่แล้ว +1

      bunch of fukin geeks get a life who cares about testing load of old rubbish it works or it doesn't, if a fault occurs then a fault is there that's life

  • @jamesrobinson5450
    @jamesrobinson5450 8 ปีที่แล้ว

    outstanding presentation of material, Please tell me your a lecturer? if only i had lecturer like your self at my college,lol.
    great video brilliant explanations in very clear manor. please keep these coming i would imagine these videos could be a game changer for many struggling to understand .

  • @-PaulT-
    @-PaulT- 8 ปีที่แล้ว

    great video as usual, thanks.

  • @loveswinhate
    @loveswinhate 2 ปีที่แล้ว

    Good lecture in whole you tube.

  • @maximohuertas4101
    @maximohuertas4101 6 ปีที่แล้ว

    Great video John. Have a question: Why would you install 2-pole and 4-pole breakers in a TN-C-S three phase system and not 1-pole and 3-pole like we do in USA (same TN-C-S system)?

  • @davidcanham272
    @davidcanham272 3 ปีที่แล้ว

    Hi John and all sparkys. This may be a dumb question from a novice. What you have explained makes perfect sense but how is my supply at home separated from my neighbors supply if we are on the same circuit from the street. Is the Zs affected but this.

  • @samdavati5718
    @samdavati5718 2 ปีที่แล้ว

    Awesome job.

  • @levoss7717
    @levoss7717 3 ปีที่แล้ว

    Very well done

  • @travoltasbiplane1551
    @travoltasbiplane1551 3 ปีที่แล้ว

    Great video John. What's your view on ADS provided by the supplier fuse when a metal split load consumer unit is installed (single insulated connecting cables to RCDs) Obviously going to be an issue with TNS (100A 1361 fuse) if ze is approaching .8 so an upfront RCD necessary there. But what about a tncs with a ze of .35. This is less than the maximum permitted zs for a 100A 1361 fuse (bs7671) but not when the 80% value is applied. Would you consider the application of the latter necessary for Ze given the network is beyond our control/sphere of influence and the resistance of any meter tails (3m) is pretty negligible even when accounting for a rise in operating temperature?

  • @danstark205
    @danstark205 7 ปีที่แล้ว

    Very helpful. Much obliged

  • @emmanuelsang213
    @emmanuelsang213 2 ปีที่แล้ว

    Nice presentation, is the type of MCB indicated on the circuit breaker or how can one differentiate?

  • @JK-ck5gg
    @JK-ck5gg 5 ปีที่แล้ว

    Superb video as alway JW.

  • @anastasiosmichaelkoutoumba9384
    @anastasiosmichaelkoutoumba9384 5 ปีที่แล้ว

    Excellent. Thanks

  • @vernonjones3613
    @vernonjones3613 7 ปีที่แล้ว

    John many thanks for your informative videos could you explain something for me on on the electrical installation condition report / schedule of test results top left hand corner it asks for the zs at db how is that measured many thanks

  • @guineafowl8029
    @guineafowl8029 8 ปีที่แล้ว +2

    Interesting to know about the different earthing systems and how they affect MCB choice. My supply is an old rural one, and I have TT earthing. However, I have some dedicated poles running to me, and the nearest two have the neutral tapped to earth down the pole. Is this an attempt to reduce Ze? What sort of impedance should I expect, given that the earth path from my earhting rod to the tapped pole is only 20m or so?

    • @sbusweb
      @sbusweb 8 ปีที่แล้ว +2

      +Guinea Fowl
      I'm fairly sure, this is more likely just the network being routinely upgraded to PME requirements, potentially allowing your earthing to become TN-C-S later and reducing the touch-voltage in the case of a lost neutral.
      I friends' house in Western-Power region certainly has TN-C-S from individual overhead wires with at least the first pole having a rodded tied to the neutral.
      Your question also raises another confusion left by the video -- hence my wider question relating to thinking about L-E and L-N impedances separately and Maximum L-N fault currents let alone Minimum L-E fault currents....

    • @Error-hv4on
      @Error-hv4on 8 ปีที่แล้ว

      +sbusweb PEFC & PSSC should both be measured & the highest reading recorded on an EICR,one been short circuit to earth & the other been short circuit to neutral,

  • @titmando1199
    @titmando1199 5 ปีที่แล้ว

    @John Ward
    Preparing for an exam and one of the questions is baffling my head, I probably over worrying and it's a molehill of a question I'm turning into mountain hope I explain it properly here goes:
    I have six circuits protected by a type B cb:
    40A / 32A / 32A / 20A / 16A / 6A
    0.5 / 1.25 / 0.96 / 1.62 / 2.0 / 7.3 are the measured loop impedance's for the circuits respectively.
    1.15 / 1.44 / 1.44 / 2.3 / 2.87 / 7.67 are the maximum values of loop impedance for the circuits respectively.
    It's asking me to refer to the maximum values and show by calculation if these values of acceptable. How do you work out loop impedance if you only know the circuit amps and the measured loop impedance?

    • @jwflame
      @jwflame  5 ปีที่แล้ว +2

      This is about the 80% rule of thumb, you are just calculating whether the measured values are less than 80% of the maximum permitted values.
      For the first one, 1.15 x 0.8 = 0.92, 0.92 is still larger than 0.5, so that is acceptable.
      For the rest, some are acceptable and some are not.

  • @peterweeds4682
    @peterweeds4682 3 ปีที่แล้ว

    Is it just me, but why do they call it a 32A MCB if it only trips at 5 times that value? Oh, and only if it is a type B... a type C is even higher! This smacks of USB standards where the U stands for Universal but is anything but. Safe working loads I remember as an engineer 'knowing' that the safety factor on lifting equipment was enough to enbrave myself to lift 2 tonnes on a 1 tonne hoist. Is it the same kind of thing?

    • @jwflame
      @jwflame  3 ปีที่แล้ว +1

      The 5x, 10x and 20x for types B,C and D only refers to the magnetic trip part, which is there to disconnect if a short circuit fault occurs. It's set significantly above the normal operating current so that it won't trip when equipment is switched on - some devices have a much larger inrush current when switched on, and for those a type C or D would be used.
      However type C and D also require that the circuit impedance is low enough to still disconnect when a fault occurs, so those would not be used on circuits which have low or no inrush current.
      For overloads, the thermal part of the MCB is used - a metal strip which heats up and trips the mechanism. That works between 1.13x and 1.45x rated current, and is the same for all types. However it's very slow to operate, typically minutes to hours, but that doesn't matter as cables are not damaged by small short term overloads, as the cable also takes a reasonable time to heat up.

  • @chompchompnomnom4256
    @chompchompnomnom4256 8 ปีที่แล้ว +1

    Hi John, what could cause a kettle base to catch fire on a dual voltage travel kettle? If it shorted out, would the fuse not just blow? Thanks.

    • @jwflame
      @jwflame  8 ปีที่แล้ว +2

      If it has a voltage selector, setting it for 120V and connecting to 240V.
      If not, then switching it on while empty, or letting it boil dry.

  • @BB-vj4tt
    @BB-vj4tt 5 ปีที่แล้ว

    Thank you sir

  • @azajakal9614
    @azajakal9614 8 ปีที่แล้ว

    brilliant
    thank you mate

  • @alan4cult
    @alan4cult 8 ปีที่แล้ว

    Great video John as usual. Quick hypothetical question. If every grid transformer in the UK was an isolating transformer (i.e. no earth) would there be any need for an earth protective conductor at all? I understand that in a TNS/TNCS system the neutral is connected to earth at the transformer leg, but if this was never done (on every transformer in the UK) and we ran on a two wire system (Line and Neutral) then why would we need earth at all? One's body would never complete a circuit if there was no earth (effectively line and neutral both floating)

    • @jwflame
      @jwflame  8 ปีที่แล้ว +1

      Such an isolated system would work, but only while there was no connection to earth anywhere. As soon as any fault between either conductor and earth occurred, the system would be referenced to earth. No one would know this had happened, but if someone until someone touches a wire or a second fault occurred.
      As one transformer typically supplies a whole street of properties, it would be impossible to ensure the system remained isolated at all times.

  • @jtk1ify
    @jtk1ify ปีที่แล้ว

    Thanks john for an excellent and easy to understand explanation.
    is there any requirement for a live test if the Ze can be obtained from the DNO and the R1/R2 is obtained by measurement. which when added together will give Zs at the farthest point of a final circuit
    does the live test have any other reason other than measurement of the loop such as applying a current to test the integrity of the cpc and main earthing conductors and their points of connections? if not can it be omitted if the EFLI is established by enquiry and measurement of R1R2

    • @jwflame
      @jwflame  ปีที่แล้ว

      Ze should always be tested. The DNO will only give generic values which may be very different from reality. There is also the possibility of a faulty supply or faulty earth connection, which can only be found by testing.
      Zs testing should just be to confirm what is already known, the comparison between Zs and Ze+R1+R2 being just to confirm the value of Zs is what would be expected. The two may not be the same due to parallel paths back to the supply, so it's fairly common to find that Zs is less than Ze+R1+R2. However if the two were totally different or Zs was greater than Ze+R1+R2 further investigation would be required as that would suggest something is wrong.

  • @fahraf1
    @fahraf1 8 ปีที่แล้ว

    @John
    that is really hlepfull many thanks.
    I do the same to my Arab tudents in my channel but in Arabic ,,
    cheers

    • @Crazy2011People
      @Crazy2011People 4 ปีที่แล้ว

      What type of earth system do you have?

  • @roadeycarl
    @roadeycarl 4 ปีที่แล้ว

    Why do the maximum measure EFLI values apply to 60898 and 61009 devices?

  • @gwilsonmail
    @gwilsonmail 8 ปีที่แล้ว

    Can you show installation examples of the 3 types of supply? So a householder could identify what type of supply they have.

    • @jwflame
      @jwflame  8 ปีที่แล้ว

      Some examples in this video: th-cam.com/video/AWxeb2MI37c/w-d-xo.html

  • @Bodragon
    @Bodragon 6 ปีที่แล้ว

    Hi John. I've often wondered whether there are electricity meters installed i these small sub-stations dotted around all over the place.
    Please John, are there?

  • @sarahclark5447
    @sarahclark5447 4 ปีที่แล้ว

    Please may I ask a question? when you said the impedance (resistance) would be the same if you were to measure between L an E and L and N on a TN-C-S system since the wires are joined locally would it not be the same on a TN-S system since the wire in the E and N would be the same length so the same resistance hence the resistance from L to N and L to E would be the same. what am I missing? Further, if the loop resistance was say 0.8 ohms and a load of 8 ampers was applied that's what our kettled consumes which my dad said takes a lot of electricity then that 8 amps would be a resistance of r=v/I which would be nearly 29 ohms. which would v=IR, V=8*0.8 which would be 6.4 volts and on a 0.35-ohm system it would be less than 1/2 that. so how does it measure the resistance accurately since how to they know the voltage was stable? the correct way of doing it it seems to me is that a resistance is applied across L and N and its lowered until the voltage is exactly 1/2 of what it was then the resistance to achieve that would be the resistance Ze. we have resisters at school where you can turn a dial and make the resistance whatever you want it to be so you would turn it to either 0.8 or 0.35. or a value to make the voltage half. do I get a prize if this worked?

  • @davindersingh798
    @davindersingh798 2 ปีที่แล้ว

    Please advise, should we consider Ze as standard values given by u or how to measure it because external impedence we can't measure bcz supply is always ON. However we can measure Zs. Please advise

  • @m.b-ee8815
    @m.b-ee8815 5 ปีที่แล้ว

    When testing a circuit that has parallel earth paths eg a boiler or a related item do you remove that path. I know you do with r1+r2 tests, but what about achieving a maximum zs test result. This also applies with heating spurs off the ring main etc.

  • @syproful
    @syproful 8 ปีที่แล้ว

    Great video !

  • @jeffitoelporquinho335
    @jeffitoelporquinho335 6 ปีที่แล้ว

    very good, thanks for that!!!!!

  • @acoustic4037
    @acoustic4037 7 ปีที่แล้ว +1

    What am I missing? Super low impedance between ground and the hot leg? Doesn't sound right.

    • @warrengray610
      @warrengray610 7 ปีที่แล้ว

      I noticed that too, but then I figured he must have meant under fault conditions

    • @TheEulerID
      @TheEulerID 6 ปีที่แล้ว

      No - it's correct. It's the Impedance between the live/hot and the earth/ground as it enters the building (where there's a supplier-provided earth/ground). It has to be that way, or if there's a live/earth fault condition it won't carry enough current to blow the supplier fuse. Look at the circuitry and it's clear it will be like that as the circuit back to the supply is connected via an enormous local distribution transformer connected to the property using very large gauge wiring.
      Of course the load side is a different matter. Unless there is a fault, there should be no current flowing from live to earth/ground which means, of course, that impedance will be pretty well infinite.
      For TT systems with a ground rod, then that's a completely different game as he explains. In the UK the preferred distribution system tends to be

  • @Sparks9133
    @Sparks9133 5 ปีที่แล้ว

    Hi john need to pick your brain you say in the video 200 300 olhms is believed not to be acceptable which is what I thought when looking in the regs book and it says anything over 200 means it could be unstable anyway went to a job got 253 olhms on a tt spoke to Nappit who I’m registered with and the chap on the phone said it’s fine because I’m within 1667 olhms but put it down as a code 3 and recommend to go back in the summer and test it again. My problem is spoke to another chap there before about a year ago and he said to me Nappit requires you to be within 200 olhms nic 100 olhms so I’m left scratching my head is anything over 200 olhms satisfactory or unsatisfactory in your opinion.great video by the way

    • @jwflame
      @jwflame  5 ปีที่แล้ว

      In theory anything under 1667 ohms is acceptable, that value being derived from the maximum touch voltage 50 volts and the 30mA RCD rating (50V / 0.03A = 1667 ohms). However in reality the value need to be much less, as it will change due to soil moisture content, so the advice about testing again in the summer is valid.
      The main thing is to ensure the value is low enough all of the time, which is why 200 or 100 is suggested, that being low enough to ensure that even with dry soil the value won't increase above 1667.

    • @Sparks9133
      @Sparks9133 5 ปีที่แล้ว

      Thinking I’m gonna just buy a new earth rod and stake it again as old rod connection is buried under some type 2 gravel and probably corroded cannot be going back there in the summer as never want to go back to this job ever again lol. John so in my max permitted zs box do I put 1667 ohms?

    • @jwflame
      @jwflame  5 ปีที่แล้ว

      @@Sparks9133 Yes, 1667 ohms, assuming the RCD is a 30mA one.
      You can leave the old rod connected, just put a new one in somewhere else, at least 2x the length of the new rod away from the old one (so if the new rod is 1m long, it needs to be at least 2m away from the old one).

  • @tutnallman
    @tutnallman 3 ปีที่แล้ว

    Interesting, Following EICR I have TN-C-S and TT on a house- What should I retain? the installation is 27 years old in good condition with Amdt 3 DB...

  • @taktak4893
    @taktak4893 5 ปีที่แล้ว

    Great stuff

  • @michaelcostello6991
    @michaelcostello6991 2 ปีที่แล้ว

    My Robin KTS 1620 tester trips every time i do a loop test at a socket. Is the reading i get in ohms accurate as a result ?