- To understand the difference between Neutral, Ground and Earth, we must understand the need of these things first.
Neutral
Neutral is return path for an AC circuit which is supposed to carry current in normal condition. This current may be because of many reasons, primarily because of phase current imbalance and some time because 3rd and 5th harmonics also.
There may be others reasons too but the magnitude of this current is in fraction of phase current and in few case it can be even double of phase current. So Neutral wire is always assumed to be charged (in active circuit). This neutral wire is given to ground (by grounding) to make the second terminal of neutral wire at zero potential.
Earth or Ground
Earth or Ground is for safety concerns against leakage or residual currents on the system via least resistance path. While phase and neutral is connected to main power wiring, earth may be connected to body of equipment or to any system which in normal condition doesn’t carry current but in case of some insulation failure, is supposed to carry some minor current.
This current is not directly coming from live or phase wire, but is from secondary links which was not in touch with live system in normal condition. This current is usually much lesser than main line current or phase current and mostly is in order of mA. But this leakage current is good enough to kill someone or may risk fire. Such current are being provided a low resistance path and sent to earth via earth wire.
Thank You for watching
பார்க்க கல்வி கண் திறந்த காமராஜர் ஐயா போல் இருக்குறீர்கள்,, அதே போல் மாணவர்களுக்கு கல்வியை எளிய முறையில் கற்றுத்தருகுறீர்கள்,, வார்த்தைகளே இல்லை,, நன்றி
He's HOD for me... Good knowledge person Mr. Arumai Nathan....
Which clg
@@todforce9357 muthaiah polytechnic from Chidambaram
Diploma college la than anaithu genius staffs m irukkanga....great
Evaroda students ellam romba puniyam pannavaga
Eppadi oru staff enaku illa
ஐயா வணக்கம் உங்களுடைய வகுப்பறை விளக்கம் மிக அருமையாக உள்ளது நீங்கள் எனக்கு ஆசிரியராக கிடைக்காமல் போனதற்கு மிகவும் வருந்துகிறேன் ஐயா மிக்க நன்றி ஐயா
An excellent teacher. Making people understand the subjects. Students under him are blessed. I missed the chance 45 years back
I am also .
I'm an ECE student....! I like your Excellent Explanation 👍👍👍
Sir, I'm your 2010 batch student. Thank you for your good job.
I'm 2011 batch good deeds👍👍💯👌🙏🙏🙏
@@MobileStudio enta college bro
@@Keiths708 muthaiyah polytechnic college. Chidambaram
0
Sir arumai arumai🙏🙏🙏 I completed degree in 2003 and watching your videos..
No words sir.... even a non technical person can understand well.....🙏......
மிக அருமை சார் தெளிவான விளக்கம்
Easy understanding..Super explanation sir..Thanks...
Thanks for the clear explanation
Crystal Clear explanation sir....tq
அருமையாக உள்ளது. தொடரவும்
thanks sir about neutral and earth explanation
Dear Sir, your explanation has helped non electrical people like me understand the basics of electricals very easily. May God bless you and let your tribe increase.🇮🇳🇮🇳🇮🇳💕💕💕🙏🏽🙏🏽🙏🏽
Super sir neenga solrath nalla puriyuth thank you sir
Great and humble explanation 👍
ஐயா நன்றாக கற்று கொள்ள முடியும் நீங்கள் ஆசிரியராக இருந்த நன்றி ஐயா
Clàrified about voltage and current thank you sir
Tnx sir clear about double earthing
நல்ல விளக்கம் ஐயா.
1.சார் ஜெனரேட்டிங் ஸ்டேசன்ல இருந்து நியூட்ரல் வருவது இல்லை
மூன்று பேஸ் மட்டுமே வரும் என்பதை அறியவும்.
2.ஜெனரேட்டிங் ஸ்டேசன்ல ஸ்டார் கனெக்ஷன் அல்டர்னேட்டர் பயன்படுத்தப்படுகிறது எனவே நியூட்ரல் எர்த்திங் செய்யப்பட்டு இருக்கும் நான் ஒப்புக்கொள்கிறேன்.
3.கண்ஸ்யூமர் என்ட் பொருத்தவரையில் டிரான்ஸ்பார்மர் எர்த்திடு நியூட்ரல் மட்டுமே கிடைக்கும்
Correct
Distribution transformer la secondary coil la than neutral edupom
Invetersupply nutural multimeter la pottu pattha 243 244 voltage varuthu but test lamp potta trip aguthu ena falut....sollu ga sir
..main bord la 2pole Rccb vachurukean but EB phase nutural work aguthu ena falut sollu ga sir...
@@Electricalplumbing1994 நீங்க கொடுத்த தகவல் போதாது நண்பா 9790091294 இல் தொடர்பு கொண்டு விளக்கம் பெறலாம்
அருமையான கருத்துக்கள்.
Sir fantastic explanation
அருமையான விளக்கம் சார்
செம்ம சார்👍👍👍
Clear explanation super sir
EEE Student I like Excellent sir..❤️❤️
Thanks for video sir ✍️
Good explanation . 😊
Tq for your brief...🙏
Super ayyya clear explain panninga🙏🙏🙏👍👌👌👌
Super explain sir very useful sir thank you siy
Great 🙏 sir, can you please tell me what kind of camera u r using
Excellent sir
Super explanation sir
Good teaching very helpful
Thank you sir 🙏🙏
Super sir 🙏🏻...
Thank you sir
Diesel generator install seiyumbodhu, ground neutral kodukirom, .. return supply adhu vazhiyaga groundukku poguma, alladhu, eb neutral vazhiyaga ..supply transformerku poguma sir?..
super sir ethumari enga sir solli iruntha engiyo poirupom
I like your explanation
Invetersupply nutural multimeter la pottu pattha 243 244 voltage varuthu but test lamp potta trip aguthu ena falut....sollu ga sir
..main bord la 2pole Rccb vachurukean but EB phase nutural work aguthu ena falut sollu ga sir...
Good explanation sir intha madri vaathiyaar enga kaalthula illa sir
3 phase unbalance voltage time which one is return path sir
Excellant sir
Thx u sir Vera level
Good teaching sir
One of phase return path ,and what will happened if unbalance voltage condition in induction motor ? Coli heat up and damage how the return phase is decided inorder to voltage level
Good explanation
Sir pls make a video of Difference between Isolated neutral and earthed neutral system
Super explain sir
Good explanation. Sir and how to calculate the earth allowed voltage 0-5 ur told
Great sir
Sir oru veetla earth nutral eppati kantupetikerathu.nutral kuntupoie earth link pannie irnthal.eppadi ithu ground earth kantupeetikerathu.
V useful sir
Super sir thanks
Thanks
Sir one doudut ippo netral and earth different ok but rendumey earth akiruku ok but why earth and neutral touch painah Spark varuthu ELCB trip aguthu...
Ground earth and neutral line board la joined pannalaama allathu panna koodatha ella board kum thaniyave kodukkanuma
அய்யா உங்கள் விளக்க உரை செய்திகள் தெளிவாக இருந்தது
sir ups la neutral earth kku voltage yevalavu sir?
Good explain sir 😘
நெகட்டிவ் சார்ஜ் ஒரு சாதனத்தில் சென்று நியூட்ரல் செல்லும் போது நியுட்ரலிலலும் நெகட்டிவ் Phase current இருக்குமா
Actually Iam Telugu ur class super sir
Earth loop impedance means what sir
Hi sir...just a doubt.. If the transformer side nutral is not grounded, will the earth work as return path in equipment side...
Good morning sir, i from Malaysia, Selangor. I am rewinder i got experience in winding 38 year sir i am interested to stady in part time class or on line class sir can you maked sir tq
Super ❤️
Super👌
Super sir
Sir definitely u reach 2million subscribers
Now iam subscribed
How do determine phase and nutral
Dear sir neutral ngurathu return path ok, yen sir load use pannakulla mattum return path laa supply pass aguthu neutral laa , load use pannamaa phase neutral layum connect panna short circuit aguthuu I can't understand kind request explain sir
Super 😊😍
சார் வீட்டுக்கு ELCB MCB எவ்வாறு கணக்கிட்டு வாங்க வேண்டும் .
Can explain about CT calculation?
Sir What is Good earth and Dirty earth?
very interesting, its really great your video, best regards Nasy
Share ur friends
Thank u
அருமை விளக்கம் நன்றி ஐயா.... !
Sooooper sir
Good sir
Invetersupply nutural multimeter la pottu pattha 243 244 voltage varuthu but test lamp potta trip aguthu ena falut....sollu ga sir
..main bord la 2pole Rccb vachurukean but EB phase nutural work aguthu ena falut sollu ga sir...
9790091294 க்கு call பண்ணுங்கள் நண்பா
Super one sir
Sir Wein bridge oscillator pathi sollunga
Who is this sir guys? Where is he? Wonderful explanation.
Super class
Yentha schl sir neenga
Phase neutral mathi kuduthal ena aagum... Adhu edhum agalana adhuku ena reason ??
👍
Double earthing wire use pannum pothu epadi parallel connection agum. Example one diagram and explain .. Double earthing use panrathuku pathil Earthing wire size phase wires size veda double ah podalama?
yes.. But if one earth is damaged, the another earth will pass the leakage to earth..
Watts pathi podunga bro....
Hi sir good evening
3phase 4 wire
In house wiring system main neutral will be open what are the faults are coming sir please give me reactions & solutions please sir
Thank you sir
If you give a load, the neutral line conduct the phase till the cut of neutral line. So the load will not work.
Direct answer. Your db load completely become 440 &.ur loads may be surely damage. So u should use proper nutr al link.
Nice
எங்கள் வீட்டில் சகேட்ல் எர்த் ஒயர் இருக்கிறது அந்த ஒயர் இந்த எர்த் லிங்கில் கனெக்சன் குடுக்கப்பட்டது அதன் பின் எங்கள் வீட்டில் இண்டக்ஷன் பவர் வரவில்லை ஆனால் கரண்ட் பில் அதிகமாக வருது என்ன காரணம் சொல்லுங்கள் நண்பரே
1.bro electrons flow device reach anathum natural la y charge illa ma varuthu
2.bro electrons natural la return agum pothu y humans teach panna stock adika matiguthu
3.bro general people electricity generate panna government ku appudi sell pandrathu
Sir neega enthe clg ka professor ??
Sir Incase unbalance voltage what will happen sir
Ur main nutral will become heat and burnt out dear.(unbalanced load.pls note the point)
🙏🙏🙏🙏
🙏🙏🙏
Neutral coming from transformer only?