[ENG SUB] Replace Battery to Fix FO4 Fault Code On ProLink UPS
ฝัง
- เผยแพร่เมื่อ 7 มี.ค. 2022
- Hello everyone! In this video I changed the battery of my 3 year old UPS, a ProLink Pro 700SFT, which I bought in March 25, 2019 to provide backup power to my Wi-Fi router. The other day, it beeped continuously, and displayed the F04 Fault Code, which according to the user's manual means that the battery is already dead or severely discharged. I decided to replace it with the same size of battery and that fixed the problem.
The other thing I found out is that even though it's nameplate rating says that it's output frequency was 50Hz, when I tested it with a Hioki CM3286 AC Power Clamp Meter, the output was actually 60Hz. This is good since it is the same as the local utility service voltage of 230V, 60Hz, nominal.
Thanks for watching and subscribing!
00:10 UPS not working with F04 Fault Code
00:46 Nameplate rating of the Pro700SFT
01:40 Removing the old battery
02:00 Rating of old ProLink battery
02:20 Terminal voltage of old battery
02:45 Replacement battery Newstar 12V DC, 8.0AH
03:08 Terminal voltage of new battery
03:52 Powering up the UPS with new battery
04:11 Testing the UPS with a desk fan
05:17 Actual output voltage and frequency on battery power - วิทยาศาสตร์และเทคโนโลยี