Demonstration of Moisture Removal in a Vacuum

แชร์
ฝัง
  • เผยแพร่เมื่อ 7 ก.ย. 2016
  • Demonstration of Moisture Removal in a Vacuum using the BlueVac Professional Plus and the iManifold system showing the characteristics of moisture in a vacuum and the related removal times.

ความคิดเห็น • 42

  • @MyBallzGotShocked
    @MyBallzGotShocked 3 ปีที่แล้ว +1

    Its amazing what you learn when you actually test and verify proper evacuation techniques. I find in residential systems moisture stalls at about 2000-1900 microns. Ive also learned to verify my equipment and hoses before every evacuation. Saved me lots of headaches and also gives a good reference if the hoses are leaking or its actually the system.

    • @RATCHETMAN1001
      @RATCHETMAN1001 13 วันที่ผ่านมา

      try teaching an automotive guy this. they just wont get it

  • @tomboice929
    @tomboice929 5 ปีที่แล้ว

    Amazing video. Thank you for posting this. Very educational and how you did it makes it easy to understand.

  • @HVACShopTalk
    @HVACShopTalk 7 ปีที่แล้ว +4

    really puts moisture removal in perspective. imagine a line full of water compared to a teaspoon. good video

  • @jameso873
    @jameso873 6 ปีที่แล้ว +1

    Wow, What an awesome video. Now I completely get it. Thank you !

  • @JasonStromhvac
    @JasonStromhvac 7 ปีที่แล้ว +2

    Great Video Jim, to see the moisture boiling out. Most systems you can't see that happening. I wish we could lol.

  • @mike-yp1uk
    @mike-yp1uk ปีที่แล้ว

    Great video on moisture and it's effects on the page oil. Now I understand what moisture in a system can do

    • @RATCHETMAN1001
      @RATCHETMAN1001 13 วันที่ผ่านมา

      i have did this test with pag oil and water. its even longer to get it out and i have watched it freeze in that scenario. then i had to heat it to get it to work. it let me see what we cant see in the system.

  • @Badnella
    @Badnella 7 ปีที่แล้ว +4

    After I have done a lot of homework, which
    is surprising that all my questions are about the iManifold but none of
    my answers came from their site or from them. I found out that the
    bluvac pro+ will connect with the iManifold system via Bluetooth. I'm
    sure i'm not the only one that watches these videos at 10:30 at night
    and think "That's awesome how accurate it shows my vacuum pull, but what
    all do I have to own in the setup to get these same results?". Then
    when I look in the video description I find exactly what I saw, but
    nothing telling me that "Hey, the BlueVac Professional Plus, is actually
    connected via Bluetooth to the manifold and it is giving us this
    awesome reading!". I thought the bluvac was just on there to give us a
    comparison, you know to show us accuracy of the iManifold is. So now it
    is well after 11:30 and I still have to go to work in the morning. SO
    can you put a little more info in your descriptions that actually tell
    us what you did to achieve what it is you are demonstrating in your
    videos. All that aside I still really find your videos enlightening.

  • @JoseCarlos-ti7so
    @JoseCarlos-ti7so 3 หลายเดือนก่อน

    muito bom esse vídeo, parabéns!!!

  • @joeshearer1247
    @joeshearer1247 7 ปีที่แล้ว

    I would add to the troubleshooter if refrigerant is off gassing or if it is a new system that service valves may be leaking through.

  • @tuyishimireelie3538
    @tuyishimireelie3538 6 ปีที่แล้ว

    thank u for this method us now going to be applicable because is easiest to use an not take much time to wait

  • @jerrodwilliams6789
    @jerrodwilliams6789 5 ปีที่แล้ว

    Nice demo. Would love to see how contaminated that vacuum pump oil is

  • @Ron30528
    @Ron30528 7 ปีที่แล้ว +4

    I believe iManifold is coming out with a micron gauge in the next month or so is what my rep told me today.

    • @JasonStromhvac
      @JasonStromhvac 7 ปีที่แล้ว

      Yes Accutools Bluvac Professional +. In October. Will be a bluetooth connection to pull into iManifold or use as a standalone gauge.

    • @vedantgg7084
      @vedantgg7084 5 ปีที่แล้ว

      Sir please your what up number

  • @u2ooberboober
    @u2ooberboober 4 ปีที่แล้ว

    When there is moisture in a system I say Aya aye aye many fold!

  • @jimgill5706
    @jimgill5706 6 ปีที่แล้ว +1

    Have you ever used a cold trap installed between the vacuum pump and a really wet system? I saw a video about a year ago that showed a long underground water logged line set being evacuated and they must have changed the oil a dozen times over a two day period.

    • @jimbergmann3499
      @jimbergmann3499 6 ปีที่แล้ว

      I have, and that is a great way to trap the water before it gets into the pump.

  • @dannylagramada1417
    @dannylagramada1417 4 ปีที่แล้ว

    Can you show the full set up of this process? Or the diagram how to set up this?

  • @Badnella
    @Badnella 7 ปีที่แล้ว +1

    Great video! But now you leave me with a whole slue of questions about the iManifold system. 1) What are you using to read the vacuum on the iPad? 2) If you are not using the iManifold itself just a prob can you read vacuum in microns if you pulled vacuum using the iManifold through the vacuum port on the manifold?

    • @JasonStromhvac
      @JasonStromhvac 7 ปีที่แล้ว +1

      Using any manifold system to check micron pull down is not really recommended. You need a good micron gauge. Otherwise you're pulling vacuum through high and low side hoses and most aren't vacuum rated.

    • @RATCHETMAN1001
      @RATCHETMAN1001 13 วันที่ผ่านมา

      also vacuum numbers are different its where u put it, but not on manifold. you put it on the furthest side of a system.

  • @RC-Heli835
    @RC-Heli835 6 ปีที่แล้ว

    I'd like to have seen the empty site glass at the end.
    How long exactly did it take to remove the water?

    • @jimbergmann3499
      @jimbergmann3499 6 ปีที่แล้ว

      90 minutes to remove the water.

    • @RC-Heli835
      @RC-Heli835 4 ปีที่แล้ว

      @@jimbergmann3499 Awesome information! Do you suppose you could use that time frame and the the one TeeSpoon of water to calculate exactly how much moisture comes out of an AC system?
      There's probably a lot of variables in there like ambient temp, size of system, humidity, strength of vacuum pump etc.
      If you can draw all of the moisture out of a system and lets say it had a bad filter dryer that can no longer absorb moisture. The system will not work correctly until its changed but where does the moisture come from if you vacuumed it all out?
      Another question... what gas is present inside a line that has been vacuumed down?
      Thanks for your videos!

    • @RATCHETMAN1001
      @RATCHETMAN1001 13 วันที่ผ่านมา

      and that was just evacuating water, if he had added pag or poe it takes way longer

  • @RC-Heli835
    @RC-Heli835 6 ปีที่แล้ว

    How would you determine that moisture is present in a running system with gauges only?

    • @jimbergmann3499
      @jimbergmann3499 6 ปีที่แล้ว

      You cannot, you need a micron gauge. There is no way to tell if it is a leak or moisture without one.

    • @RC-Heli835
      @RC-Heli835 6 ปีที่แล้ว

      Jim Bergmann Thanks Ill get one soon.

  • @brianmutascio8325
    @brianmutascio8325 7 ปีที่แล้ว +1

    Whats the purpose of the tank in your demonstration.

    • @jimbergmann3499
      @jimbergmann3499 6 ปีที่แล้ว +1

      It was just a buffer so the water did not flash freeze due to a small volume.

  • @2purplemartin1
    @2purplemartin1 ปีที่แล้ว

    Can you get moisture out of refrigerant oil?

  • @zhyarn.248
    @zhyarn.248 2 ปีที่แล้ว

    Can you tell me what is name of this Machine please?

  • @vedantgg7084
    @vedantgg7084 5 ปีที่แล้ว

    I want remove juggy powder moisture

  • @portagepete1
    @portagepete1 7 ปีที่แล้ว +2

    No need to throw the old oil away, if it sits in a clear container long enough water will go to the bottom.

  • @jerrodwilliams6789
    @jerrodwilliams6789 5 ปีที่แล้ว

    Lol I jumped the gun.

  • @eklazhward4739
    @eklazhward4739 2 ปีที่แล้ว

    1 teaspoon ~ 30cf !!?? its around 1m3 ? wow u are u sure?

  • @spilbee
    @spilbee 2 ปีที่แล้ว

    Pump sounds choked…