6 Electrical Code Myths people Should Stop Believing

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 436

  • @BackyardMaine
    @BackyardMaine  3 หลายเดือนก่อน +4

    FlexiSpot is having their anniversary sale now and a chance to win free orders! 🌟 Use my code ''24AUGE7PLUS” for extra $50 off on E7 PLUS! Trust me, it's a rare treat!
    FlexiSpot E7 Plus Standing Desk: bit.ly/3WUcJGW Garage Rack: bit.ly/3M7YMQV

    • @shawnshurtz9147
      @shawnshurtz9147 3 หลายเดือนก่อน

      Splices terminating in the panel are fine. A panel isn't a junction box however.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      @@shawnshurtz9147 Agreed. I don't think a splice would be necessary very often during initial installation. But often time we want to add a sub panel or we may need to more some circuits around and splices will be our only option.

    • @michaelbrown1133
      @michaelbrown1133 2 หลายเดือนก่อน

      where can I get the NEC code book?

  • @johneastmond9092
    @johneastmond9092 3 หลายเดือนก่อน +13

    Two other factors governing the use of anti-short bushings:
    1, Some agencies require the use of all supplied components from the manufacturer.(whether actually required or not.)
    2. Some jurisdictions still have the requirement on the books from decades ago. (Hence, why they're still shipped.)
    Legacy; code, standards, and requirements exist all over industry!

    • @dracula3811
      @dracula3811 3 หลายเดือนก่อน +4

      My boss requires the use of them and he supplies all the materials so I use them.

    • @thomasmarable6818
      @thomasmarable6818 2 หลายเดือนก่อน +1

      Last rolls I bought didn't have any come to think.of it never have gotten any on the 1000 foot rolls.

    • @johneastmond9092
      @johneastmond9092 2 หลายเดือนก่อน

      @@thomasmarable6818 , Interesting. That's information. That'd release some from the obligation. Others would order them specifically.

  • @jensschroder8214
    @jensschroder8214 3 หลายเดือนก่อน +19

    If copper is clamped onto aluminium it can cause corrosion.
    WAGO allows to use its clamps with aluminium only with anti-corrosion paste.
    WAGO offers anti-corrosion paste for this purpose.
    Omitting this paste is a violation of the manufacturer's specifications.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +7

      The new AA-8000 aluminum conductors are rated for copper lugs with no antioxidant paste. But if you find the manufacture has not caught up and still requires it then you should use it with their equipment.

    • @MrUbiquitousTech
      @MrUbiquitousTech 3 หลายเดือนก่อน +4

      Just using a wago is asking for a fire

    • @OrdinaryDude67
      @OrdinaryDude67 2 หลายเดือนก่อน +2

      @@MrUbiquitousTechthe entire rest of the world uses wago-type connectors just fine. 🙄

    • @MrUbiquitousTech
      @MrUbiquitousTech 2 หลายเดือนก่อน +1

      @@OrdinaryDude67 🤣😂

    • @charliesullivan4304
      @charliesullivan4304 2 หลายเดือนก่อน +1

      ​@@BackyardMainethe code section you showed says that aluminum is one of the conductor types allowed, and that aluminum has to be an 8000 series alloy unless it's bigger than 1000 MCM. It does not say that AA-8000 is interchangeable with copper. If you have a device with terminals that are spec'ed for copper wire only, you cannot use AA-8000 in it. Whether NoAlOx is required also goes by the manufacturer instructions.

  • @arthouston7361
    @arthouston7361 3 หลายเดือนก่อน +39

    When I first started learning the Code, one thing became very clear: it is not a guide to the best practices for using and installing electrical devices. It is the base requirement that can be approved. Do you have to install a redhead when installing armored cable? Nope. But, you are a fool if you do not. A proficient worker could find dozens of such examples. Don't confuse code requirements for good methodologies.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +9

      So even though NEMA says don't use them, they are not required by code, the connectors are not listed for their use, and the reason people think they're needed is because they confuse the requirement with what's required for BX we should still use them... The code is far from a minimum standard. I have been in the business as an electrician or an electrical engineer for 40 years and have spend considerable time writing best practice methods and procedures for a semiconductor manufacturing company. There are very few instances when the code needs to be exceeded.

    • @shawnshurtz9147
      @shawnshurtz9147 3 หลายเดือนก่อน

      ​@@BackyardMainehave you seen fools using dykes to cut it instead of a mc cable stripper. Leaves that nice sharp edge.

    • @arthouston7361
      @arthouston7361 2 หลายเดือนก่อน +9

      @@BackyardMaine In that case sir, you need to talk to somebody who knows more than you do. Apparently, you think I don't. It's fine, I started doing electrical work in 1964. So whose is bigger? It doesn't matter whose is bigger, it matters what the best practice is. Any person with one working eyeball can see a sharp edge and a conductor that needs to be protected. Is there a functional distinction between the sharp edge of BX and the sharp edge of AC or MC??? If NEMA can't see that, then perhaps they should visit a good eye surgeon. The code clearly states that all work should be done in a workmanlike manner, and that is the coverage for this approach of best practice. HTH.

    • @stevedonovan22
      @stevedonovan22 2 หลายเดือนก่อน +4

      like you said code is bare minimum

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +2

      @@stevedonovan22 Not even close.

  • @sidlives2672
    @sidlives2672 3 หลายเดือนก่อน +3

    I was surprised by the splicing in the panel. I was watching my electrician doing a panel upgrade and saw him doing a ton of splices in the panel. It was a combination of old wiring and the panel length increasing that required him to splice a bunch of wires just to get them to reach the new breakers. I guess people forget that splices always need access (in addition to what you read as code) and you certainly have access in the panel. Thanks for keeping us informed.

    • @dadgarage7966
      @dadgarage7966 3 หลายเดือนก่อน +2

      It would be horribly impractical if splices weren't allowed. What's the alternative? Putting a bunch of boxes outside the panel?

    • @AndrewMoizer
      @AndrewMoizer 2 หลายเดือนก่อน +2

      I was surprised too. When i installed my new panel I had a few circuits where I was short of wire on the old runs so did the extensions in a box outside the new panel. Would have been simpler inside for sure. I live in Ontario so it might be different, something I’ll have to check if I ever need it again.

  • @libertarian1637
    @libertarian1637 3 หลายเดือนก่อน +7

    Liked the info; it’s funny to me that perceptions can be just so strong and at times even defy code. I know where I am if you don’t use no Alox you’ll fail an inspection and won’t get a service sticker to allow equipment to be energized. You can show a code section but the gist is safer rather than sorry and it’s not hurting anyone. I was so glad to get out of the commercial space as industrial/municipal is so much better and more sane, at least as far as code compliance. The biggest thing to try to convince people of is following torque spec, as it is required but, seemingly rarely followed, at least outside of larger equipment.

    • @ronblack7870
      @ronblack7870 3 หลายเดือนก่อน +3

      6 months ago i installed a new I-line panel 480 v 800 amp and used a torque wrench on every connection and breaker. it's surprising how much torque it actually takes to tighten up the lugs. 300 - 500 inch lbs is a hell of alot.

    • @wdmm94
      @wdmm94 15 วันที่ผ่านมา +1

      There is a youtube electrician in Florida that has all kinds of vids replacing burnt out breakers / panels. I assume from aluminum oxidation and no oxidation preventative being used.

  • @Sylvan_dB
    @Sylvan_dB 3 หลายเดือนก่อน +5

    Good info, thanks!
    I encourage you to get a padded mat under your feet while standing at your desk. That concrete floor will damage you.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      Thanks. I was actually thinking that while I was recording this video. Much appreciated.

  • @ElectricRob
    @ElectricRob 3 หลายเดือนก่อน +8

    Hey John! Thanks for this one - I must admit that the 15A/20A receptacle on a 15A breaker was new to me. I've never tried to do this (we use 15A recepts on our resi projects), but my internal "common sense" would have told me that there was no issue (similar to putting 20A wire, or #12 AWG, on a 15A breaker - it's still protected). But the point about "encouraging" the use of higher-wattage (20A cord cap) equipment from a receptacle/load point of view does make perfect sense!

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +3

      Very welcome.. When I talk about code compliance I try to provide some context. Thanks for watching and for commenting.

    • @ElectricRob
      @ElectricRob 3 หลายเดือนก่อน +1

      @@BackyardMaine Totally agree - helps us all to remember those codes as well when we understand a "why".

    • @ronblack7870
      @ronblack7870 3 หลายเดือนก่อน +4

      no only an electrician would know the difference. ave consumer wouldn't know . they just plug in whatever they got

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +5

      @@ronblack7870 A 20A plug will not physically connect to a 15A receptacle.

  • @David0lyle
    @David0lyle 3 หลายเดือนก่อน +3

    I understand why the no ox requirement was waived as I live in Colorado where the weather is as dry as a popcorn fart. The thing is, I’ve dealt with low voltage RJ45 connectors in marine environments and the air alone in that environment is aggressive enough that anti oxidation materials are prudent regardless of code recommendations.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I would agree that it’s a good idea in a corrosive environment although it’s not required.

  • @brianbuddy2ACP
    @brianbuddy2ACP 3 หลายเดือนก่อน +3

    There's still a few questions I have.
    1. Related to re-identifying a white wire as a hot wire. What does code define as a "permanent" marking? Electrical tape can be peeled off after it's applied, and to me, isn't permanent. I've thought of using heat shrink tubing for this, because it doesn't suffer from the problems that electrical tape or permanent markers have, and also wraps 360 degrees around the wire, but it can also be removed once it's applied, just like electrical tape.
    2. Related to the 20 amp receptacle on a 15 amp circuit. Does the same apply to switches too? Could it be the situation with switches is actually reverse of receptacles? Or something else?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      Electrical tape is an approved method listed in 200.7(C) in the code.
      The NEC allows a 15A-rated switch to control loads on a 20A circuit as long as the switch is used to control a lighting load or other device that does not exceed the switch's rating. This is because switches are designed to handle the current drawn by the load they are controlling, not necessarily the full capacity of the circuit.
      NEC 404.14: The relevant section of the NEC (404.14) indicates that snap switches, such as typical light switches, are allowed to be used on circuits with a higher ampacity than the switch rating, provided the load does not exceed the switch rating.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน +1

      The NEC does not say the marking method must be permanent, as in not removable. It says "permanently reidentified...by marking tape, painting or other effective means..."

  • @mdunbar008
    @mdunbar008 3 หลายเดือนก่อน +10

    The code may not require anti-ox, but there are still manufacturers that require it, and the code states if anti-ox is required by the manufacture, then it is required by the code.

    • @weavercattlecompany
      @weavercattlecompany 2 หลายเดือนก่อน +2

      If the inspector wants to be a pain in the ass then that's one of the first things they try to enforce. Best practice is to smear a little bit of paste on the front side of the wire insulation to make it look as though it was used hence you avoid the hassle to begin with

    • @DavidBTB
      @DavidBTB 2 หลายเดือนก่อน

      110.3(B)?

    • @shakere101
      @shakere101 2 หลายเดือนก่อน

      @@weavercattlecompany that is a half ass deceitful scabby way to do things

    • @shakere101
      @shakere101 2 หลายเดือนก่อน

      @@weavercattlecompany that is not a "best practice".

  • @bigdog8008
    @bigdog8008 3 หลายเดือนก่อน +2

    Many of these may not be required but reflect better installation practices when used. It is always best if you can have workmanship that always "meets or exceeds code" than simply "meets code".

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +2

      I completely agree with better workmanship and best practices. But I don't agree with doing something that provides no value to the customer and actually is not recommend by the manufacturer. In this case it does not exceed anything other than possibly the bill. If your plumber painted all your copper pipe would than exceed code since its not required?

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      @@BackyardMaine Exactly. Too many have the belief/perception that "minimum" code (perhaps we should stop using the word minimum, with all its connotations) is exactly one small step away from a disaster so exceeding the minimum gets you farther away from that disaster. Nonsensical.

  • @Sparky-ww5re
    @Sparky-ww5re 3 หลายเดือนก่อน +4

    In every dwelling unit I've worked in, it is a universal practice to install 15A receptacles on the required 20A kitchen, bathroom, laundry room and garage receptacles. Equipment with NEMA 5-20 plugs are very seldom encountered in a typical family home, so I've only installed single NEMA 5-20R devices in homes to identify it as a 20A individual branch circuit for something like a large refrigerator or expresso machine if the manufacturer's instructions specify a 120V 20A individual branch circuit regardless of whether the equipment in question has a 15 or 20a plug, since per the NEC a single receptacle outlet on a branch circuit must match the rating of the overcurrent protection device.
    In the unlikely event you see an appliance with a 120V 20A plug, such as a commercial grade microwave oven for example, even if the electrician had installed 20A devices on the 20A circuits, you should check the instruction manual because it will probably say something like "FOR USE ON AN INDIVIDUAL 120VAC, 60Hz, 20 AMPERE BRANCH CIRCUIT ONLY" in which case 110.3 (B) applies.
    As always, we need to also be aware of any local codes which may be more stringent than or have requirements that go beyond the NEC. For example some jurisdictions could require 20A devices to be installed on 20A circuits even though the NEC permits 15 or 20A devices on 20A circuits.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      I agree with everything in your comment. Thanks for adding to the conversation.

    • @greggpurviance7252
      @greggpurviance7252 หลายเดือนก่อน

      Never seen any jurisdiction require 20amp receptical on 20 amp branch circuits

  • @jonjohnson3027
    @jonjohnson3027 3 หลายเดือนก่อน +6

    When reidentifying a wire with tape, I recommend NOT using black tape. Black tape can be mistaken as a repair of the insulation rather than a reidentification. If you must repair the insulation on a neutral conductor, use white tape so someone doesn't mistake it for a reidentified wire.
    The above isn't a code requirement; it's just a best practice.

    • @thecorzofamily9483
      @thecorzofamily9483 2 หลายเดือนก่อน

      A better way would be not using the white wire as live, just run new romex. Stay safe

    • @pld8993
      @pld8993 2 หลายเดือนก่อน +1

      @@thecorzofamily9483 Sometimes not practical, and a tape repair meets code requirement and provides moire than sufficient electrical insulation.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน +1

      Actually, a black tape repair on a white conductor and using it as a neutral would be a code violation. Grounded conductor must be white its entire length and a 1" wide piece of black tape renders it not white along its entire length.

    • @chuckholmes2075
      @chuckholmes2075 2 หลายเดือนก่อน

      thats why i use RED heatshrink and then I label it as well

  • @m0ondoggy
    @m0ondoggy 3 หลายเดือนก่อน +24

    My grandparents had a new house built in 2004 in Arizona. In 2007 an aluminum wire feeding the AC Compressor corroded at the panel and started a cascade failure, melting the wire. It left burn marks on the trusses and other framing; it damn near burned down the house. Noalox was not used on either end. I learned 2 things from this incident. If I have AL wire, I use Noalox, period, regardless of code. Also, when I built my new house, I spent the extra money and used copper for feeding subpanels, ovens and HVAC. Was it expensive? Yes. Am I ever going to have to worry about it? No.

    • @RobertBeck-pp2ru
      @RobertBeck-pp2ru 3 หลายเดือนก่อน

      Iv'e seen examples of aluminum wire feeding manufacturing plants corroding to the point of catastrophic short and explosion. And there have been many a mobile home burning to the ground because of aluminum wiring. I would never even consider it's use in ANY building or equipment. It should have been outlawed decades ago.

    • @kenbrown2808
      @kenbrown2808 3 หลายเดือนก่อน +1

      copper isn't even that much more expensive in smaller sizes.

    • @charliesullivan4304
      @charliesullivan4304 2 หลายเดือนก่อน +1

      And follow the instructions on the NoAlOx bottle, and torque to spec.

    • @kenbrown2808
      @kenbrown2808 2 หลายเดือนก่อน

      @@charliesullivan4304 and use any actual brand but Noalox.

    • @timroberts6046
      @timroberts6046 2 หลายเดือนก่อน

      More than likely it was a loose connection.. that caused that. Not the lack of nolox. Alot of fires could be prevented if people properly used a torque wrench when installing.

  • @garbo8962
    @garbo8962 3 หลายเดือนก่อน +8

    I know that anti short bushings are not required on MC cable but always use them. After stripping any armored cable jacket cut the sharp edge at a 45 degree angle When cable companies supply undersized anti short bushings will install two of them staggered around wires.Can remember the coated flimsy paper anti short bushings from the 1960's. Often after a few short years in a damp location they would fall apart.

  • @nicholassmi4091
    @nicholassmi4091 2 หลายเดือนก่อน +2

    You can use and reidentified white conductor as a phase conductor only if it’s part of cable assembly

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I put up 200.7 in the video.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Close. You are allowed to re-identify a white wire that's not part of a cable (making it a hot or ground, for example) as long as the color is changed along its entire length.

    • @nicholassmi4091
      @nicholassmi4091 2 หลายเดือนก่อน

      @@pld8993 where i can find it in the NEC book ?

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      @@nicholassmi4091 There is no explicit allowance in the NEC that addresses it the way I have, but there is no prohibition. This is a clear example of the importance of comprehensive NEC knowledge (as opposed to knowing just the rule you're focusing on). The NEC says a grounded conductor must be white its entire length, for example. Changing that entire length color to black now disallows it as a grounded conductor and allows it to be used as an ungrounded conductor (which can't be white, gray or green). Changing a black conductor to white along its entire length allows it to be used as a neutral. There is nothing in the NEC that says conductor color must be directly from the manufacturer. Field markings are allowed unless otherwise prohibited.

    • @nicholassmi4091
      @nicholassmi4091 2 หลายเดือนก่อน

      @@BackyardMaine when we have an electrical conduit we are not allowed to pull an individual white color conductor and re-identify it . If i am wrong please send me section of NEC that can proof that i am mistaken. And Section 200.7 saying that we can re-identify only if it is (1) part of cable assembly , (2) A flexible cord. Thank you

  • @weaselhead6771
    @weaselhead6771 3 หลายเดือนก่อน +1

    good stuff. you answered most of the questions I could never find. Thanks!!

  • @HowToHomeDIY
    @HowToHomeDIY 2 หลายเดือนก่อน

    In depth but also simple to understand. As always, great video John!

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Much appreciated my friend.

  • @BartlettTFD
    @BartlettTFD 3 หลายเดือนก่อน +1

    This is REALLY some good information❗️Thanks for keeping us updated👍

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      My pleasure. Thanks for watching.

  • @bortLives
    @bortLives 2 หลายเดือนก่อน +1

    For reidentifying white wires as hots, you might want to add that while you can do that to a cable assembly such as romex or MC- you cannot do this for THHN in a conduit. (Unless the wire is #4 or larger)

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Correct. I did show the text in 200.7 detailing that fact but maybe I should have said it as well. I was showing and talking about NM cable so I didn't think it was necessary.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Close. You are allowed to re-identify a white wire that's not part of a cable (making it a hot or ground, for example) as long as the color is changed along its entire length.

    • @jeffsaxton716
      @jeffsaxton716 2 หลายเดือนก่อน

      That's why I use blue THCC and tape-label them at all terminations. Seems legal, amirite?

  • @treepop1550
    @treepop1550 3 หลายเดือนก่อน +2

    Love your professionalism!! Thanks good information!!

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +2

      I appreciate that! Thanks for watching friend.

  • @richardsherman152
    @richardsherman152 3 หลายเดือนก่อน +2

    It’s incredible how much extra work is done because an inspector one time told an electrician that they had to do something even though it had no basis in reality

    • @MrAncientAstronaut
      @MrAncientAstronaut 2 หลายเดือนก่อน

      The code defers to the AHJ, I believe

    • @richardsherman152
      @richardsherman152 2 หลายเดือนก่อน

      @@MrAncientAstronaut you’re not wrong, but I think that this is pretty widely misinterpreted.
      Just because the individual inspector is a representative of the AHJ doesn’t mean that they can just make stuff up.
      I can picture a piece of 2 inch pipe with a 90 in the middle of it supported with a one hole strap and inch away from the coupling. Wow this might technically meet the code requirements that sagging 90 is going to put pressure on the coupling and should be supported.
      Requiring anti-shorts where the manufacturers have repeatedly and specifically addressed the matter isn’t open for interpretation.

    • @jovetj
      @jovetj 2 หลายเดือนก่อน +1

      @@MrAncientAstronaut And some As are AHs.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน +1

      @@MrAncientAstronaut An individual inspector is not the AHJ and should be called out for made-up code requirements every time.

  • @Rai_Te
    @Rai_Te 3 หลายเดือนก่อน +2

    I always find videos diskussing the do's and dont's of electrical installation interesting. They are highlighting the different practices used at different times, at different location, etc. This video is nicely done, I miss however one important piece of information: The area where the contend of this video applies.
    I'm located in Europe, and obviously, while the information provided in this video is interesting (and certainly correct) ... it doesn't apply to me. Are laws regarding electrical wireing the same in the whole US, or do they vary per state? Do they apply to Canada as well? ... I would be simply good to say the one important sentence right in the beginning: The content of this video applies only in --- insert region here ---

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      Thanks.. I often don't think to say that but it's a good idea. Here in the USA we have a national electrical code that has been adopted by all 50 states. Some states will have a few amendment but they are usually minimal. I think the state of Maine where I live has five minor amendments and they are more about terminology rather than standard. Some cities and counties will have more amendments which I think is ridiculous and would love to see that change. Canada has their own code but it is very similar to ours here in the USA.

  • @Patty-qh3lm
    @Patty-qh3lm 3 หลายเดือนก่อน +8

    I can't imagine not using red-heads on any m/c cable. The clamps can still squish the armor.

    • @JeffPenaify
      @JeffPenaify 2 หลายเดือนก่อน

      the pop in connectors dont

    • @merlinious01
      @merlinious01 2 หลายเดือนก่อน

      ​@@JeffPenaifypop in? Do you mean screw in?

    • @JeffPenaify
      @JeffPenaify 2 หลายเดือนก่อน

      @@merlinious01 no the snap on connectors

    • @thomasmarable6818
      @thomasmarable6818 2 หลายเดือนก่อน +1

      You are over tighten them please read the instructions before installing.

  • @greenbudkelly2820
    @greenbudkelly2820 2 หลายเดือนก่อน

    Good channel. You explain things in a down to earth fashion, classic Mainah.

  • @scottkolaya2110
    @scottkolaya2110 3 หลายเดือนก่อน +1

    Great video and I agree about the 20 receptacles on a 15 amp circuit, but in my 60 years, I've actually never seen a 20 amp plug on any appliance. I know they exist, but the toaster oven example isn't one of them. We used to install 20 amp receptacles under the impression that they were built better, but haven't done that in decades.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน +1

      You will not find any consumer appliances with 20 amp cord caps. What you will find is certain areas requiring a single 20 amp receptacle (dedicated circuit) for appliances like a permanently mounted microwave or similar because some draw 1800+ watts and could be considered as continuous draw even though they are within the 80% rule. That outlet also qualifies as a service disconnect.

    • @kenbrown2808
      @kenbrown2808 3 หลายเดือนก่อน

      commercial grade plugs are rated for plugging and unpluggind things more frequently, but that's pretty much it.

    • @KameraShy
      @KameraShy 3 หลายเดือนก่อน +3

      As a DIYer my biggest mistake was not using commercial grade receptacles, especially for locations with frequent plug-ins. These just don't last and I am having to replace them.

    • @scottkolaya2110
      @scottkolaya2110 3 หลายเดือนก่อน

      @@KameraShy they weren't that easy to get years ago.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน +1

      @@scottkolaya2110 that depends on how long "years ago" was. In the 70s / 80s we didn't have the flood of units made with Chineseium. If you are talking maybe 25 years ago, that's another story.

  • @stringlarson1247
    @stringlarson1247 3 หลายเดือนก่อน

    I was doing some MC recently in the attic and my old Greenlee cutter was in the basement, but my little M12 bandsaw was at hand. I tried it on the MC and obviously, it cut the MC. Just then I used my good ol Klien reamer/debur to remove any edge (there was almost none), I have a ton of old single screw fasteners (not the new ones you show). The protector goes in nice and smooth.
    It looks like the collar/clap type connectors for use without the bushing may cause issues as the clamp could squeeze down on the cable and bushing too much.
    BTW: The little M12 bandsaw is great for EMT, RMC, MC, copper, AL, etc.

  • @JasonCougar-k5r
    @JasonCougar-k5r 2 หลายเดือนก่อน +3

    When you got two different metals in contact is when you use the antioxidant and most of what you're saying may not be cold violations but they are really good practices. Fairly certian you cant reidenfied green and white or grey 2023 no grounding or grounded conductor. Also you have to have a neutral in every box. Even if myths its the way it should be done.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      The neural only needs to be at one switch box for 3-way and 4-way switches as per 404.2 in the 2023 code. You cannot re-identify a ground wire but you can a neural wire per 200.7 of the 2023 code. AA-8000 conductors can only be connected to connectors that are listed for aluminum wire. Almost all these connectors or lugs used in load centers are listed for copper and aluminum. AL/CU. For a listed a AL/CU lug antioxidant is not required.

    • @jovetj
      @jovetj 2 หลายเดือนก่อน

      The point is there are other legit reasons to re-identify a white wire that do not involve avoiding a neutral in a switch loop's switch box.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      @@jovetj I talked about them in the video.

  • @donm1547
    @donm1547 3 หลายเดือนก่อน +1

    When a conduit type system is installed, the minimum conductor size for re identifying is number four or larger

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +2

      I put up article 200.7(C) where it states in a cable 1- If part of a cable assembly and 2- If part of a flexible cord.

  • @michael931
    @michael931 3 หลายเดือนก่อน +1

    Reidentifying/recoloring of the white wire is only allowed in Romex and other multiconductor cable. Not individual conductors.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      I showed that in the video. 200.7(C) 1 and 2.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Close. You are allowed to re-identify a white wire, or any wire, that's not part of a cable (making it a hot or ground, for example) as long as the color is changed along its entire length.

  • @jeffsaxton716
    @jeffsaxton716 2 หลายเดือนก่อน

    I'm not a licensed electrician but at my own home, I follow the code book. I was an electronic tech, and know enough to follow the book.

  • @arudanel5542
    @arudanel5542 3 หลายเดือนก่อน

    Loving my Flexi spot desk. It's only a 2 legged model, but holy cow it doesn't wobble at all.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      I was blown away by this desk. Top quality in a world when everything you buy is disposable.

  • @MarkCarson-e5f
    @MarkCarson-e5f 2 หลายเดือนก่อน

    Yes the white wire (or neutral) can be re designated ( or colored for conducting electricity if needed)

  • @MarkCarson-e5f
    @MarkCarson-e5f 2 หลายเดือนก่อน

    Check first with your inspector (AHJ) about anti shock inserts, and either flex or Mc wiring.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      No, find out what the local code is and follow it. An inspector is not the AHJ; he is enforcing the written codes that the AHJ has adopted.

  • @MyClutteredGarage
    @MyClutteredGarage 3 หลายเดือนก่อน +2

    Very interesting about the MC cable anti-short protectors, John!

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +2

      I used them for years until I had to prepare to teach a code class and found out they were not actually required.

    • @eds6569
      @eds6569 3 หลายเดือนก่อน

      Our crew sticks with snap/push-in barrel style mc connectors which already has the plastic bushing wire protection but I still use the anti shorts sometimes or pull a tiny bit of slack from the mc cable and wrap a piece of tape over the conductors then retract 'em back into the metal armor if my cut is questionable (I'm often OCD on things though and hate potential mistakes).

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      @@eds6569 I have used them as well. The bushing on those doesn't actually go up inside the armor at least not the ones I've used.

  • @rayjackson4547
    @rayjackson4547 2 หลายเดือนก่อน +1

    JOHN- Nice job and info as usual. The desk pitch is a little of a stretch

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      Thanks. I don’t care what anyone buys but I love the desk.

  • @AlfredHodgekins
    @AlfredHodgekins 21 วันที่ผ่านมา

    Good information on your channel though curious why no box offsets and clips on your EMT in your shop?

    • @BackyardMaine
      @BackyardMaine  21 วันที่ผ่านมา

      The nipples are approximately 30 inches long which is under the 36 inch requirement in article 358.30 of the NEC. Since not straps are needed it would make no sense to bend box offsets

    • @BackyardMaine
      @BackyardMaine  21 วันที่ผ่านมา

      The nipples are approximately 30 inches long which is under the 36 inch requirement in article 358.30 of the NEC. Since not straps are needed it would make no sense to bend box offsets

  • @deadmanswife3625
    @deadmanswife3625 3 หลายเดือนก่อน +3

    Thank you very helpful

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      You're welcome! Thanks for watching.

  • @Jack_of_1_Trade
    @Jack_of_1_Trade 2 หลายเดือนก่อน +1

    Here’s a good one…how many NM wires can a 3/4 metal romex connector hold??

    • @jovetj
      @jovetj 2 หลายเดือนก่อน

      As many as it's rated for!

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Connectors for NM cable will be listed for a certain number and size cables. This listing or rating needs to be followed by the installer to meet 110.3 (B)

  • @briandish1787
    @briandish1787 3 หลายเดือนก่อน +1

    Backyard Maine, What is your opinion on Fuses vs Circuit breakers? Are not fuses more positive to open on the overcurrent rating then Circuit breakers?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      Circuit breakers have become very reliable and I would rather have them than a fuse in a residential setting. A breaker can be reset easily and be used to turn off and on a circuit safely if needed. Fuses are pretty much fool proof when it comes to reliability. The issue with them in residential use is they can't be easily and safely replaced by an inexperienced person. They cannot be reset so you will need to buy a fuse when one blows and an inexperienced person could easily put in a larger fuse to keep it from tripping not knowing they have created a hazard. I hope this helps.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      I'd always trust a fuse and a newer breaker equally, but I'd trust a 50 year old fuse before I'd trust a 50 year old breaker.

  • @PhillyFixed
    @PhillyFixed 3 หลายเดือนก่อน

    Clear and concise. Thank you!

  • @Calico5string1962
    @Calico5string1962 3 หลายเดือนก่อน

    Great stuff!
    Thanks for sharing.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Thanks for watching!

  • @CognitiveHeatsink
    @CognitiveHeatsink 3 หลายเดือนก่อน +4

    My favorite thing to do is ask people to show me the specific article in the code that allows or forbids something. It feels like many professionals have never even read the code and only know what they were taught as an apprentice.
    *I was typing this out as the video still played. As I was typing you just said "that's what I was taught as an apprentice" 😂

  • @brianhulben1695
    @brianhulben1695 2 หลายเดือนก่อน

    So because we found a way around the old minimum of pipe, we have created so many more problems and also new minimums, that in the long run cost more, but now code allows it, but 1/3 as much wires, afi and, fire alarm equiptment in every home. While it does provide job security, the quality, and effort goes down with every step we take away.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Since when is pipe the old minimum? Ever hear of knob and tube?

  • @Crasoum
    @Crasoum 3 หลายเดือนก่อน +2

    200.7(C)(1) is in relation to cable assemblies, so Romex/mc/cable tray etc. is fine. But pulling a white THWN-2 in a conduit and then reidentifying it is not.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      Yes I believe I showed that in the video. It also applies to flexible cords as well.

    • @freedomer342
      @freedomer342 3 หลายเดือนก่อน

      You're correct

    • @Crasoum
      @Crasoum 2 หลายเดือนก่อน

      @@BackyardMaine You showed Romex, but didn't mention it. Also didn't mention it's strictly in relation to cable assemblies.
      Not that a lot of home owners would use individual conductors, the point is still the same.
      200.7(C)(2) would be for flexible cords, at least in the 2023 revision.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      @@Crasoum I actually showed the code article in the video which states its for cable assemblies and below that was (2) for flexible cords.. The reasoning is that with conduct you can pull in the correct wire color.

    • @Crasoum
      @Crasoum 2 หลายเดือนก่อน

      @@BackyardMaine No argument there, my sticking point had more to do with how people tend to approach information (they take it at face value and don't read the fine print.)
      You say anything confidently enough and most people will take it in without a second thought.

  • @billbrown6526
    @billbrown6526 3 หลายเดือนก่อน

    As always, great content, flyboy.

  • @guytech7310
    @guytech7310 3 หลายเดือนก่อน

    Use the antishorting bushings!. I have MC in my home, and even with the MC cable connectors its still possible for the clad to cut in to the wire and cause a short! The bushings are cheap & easy to install why take a risk & cut corners for something as cheap & easy?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Absolutely use them if you want. I doubt if many inspectors will fail the use based on 110.

  • @StormyITO
    @StormyITO 27 วันที่ผ่านมา

    Nolox may not be required by code, but it is required by some jurisdictions. Mine specifically does require it

  • @peterb.mahnke1068
    @peterb.mahnke1068 2 หลายเดือนก่อน

    Anti shorts are very much required on all Ac/90 and teck cables in the Canadian regs.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Like I said in the video the anti-shorts are required for type AC cable here as well.

  • @marvinostman522
    @marvinostman522 หลายเดือนก่อน

    I like your site because you go to the code book. I have a question about using a GFCI outlet to replace a two wire outlet. I believe that it meets code and supposedly will trip as designed but I believe it still does not give you a path to ground. I think I heard that you should not put a ground and neutral under the same screw in the buss bar in a panel. Under no circumstances should a ground use the neutral back to a panel. Please direct me to a verified authority.

    • @BackyardMaine
      @BackyardMaine  29 วันที่ผ่านมา

      You can install a GFCI on a circuit without a ground wire and it will still work. Yes always keep the neutral and ground separate and never use a ground wire as a neutral. All of this is detailed in the NEC.

    • @marvinostman522
      @marvinostman522 29 วันที่ผ่านมา

      Yes I knew you use the GFCI to replace a two wire outlet. However doesn’t it need to be labeled “no equipment ground.” This tells me you still do not have a path to ground. Grounds and neutrals do not do the same thing, is that correct. They go to the same place but they are not the same. That is why you shouldn’t put a ground and neutral under the same screw on the buss

    • @BackyardMaine
      @BackyardMaine  29 วันที่ผ่านมา

      @@marvinostman522 Yes it does need to be labeled like you mentioned. The neutral wire also called the grounded conductor is used to carry current back to the source. So it's a current carrying conductor. The ground wire is used to bond conductive surfaces in order to provide a path for fault current. Its not considered a current carrying conductor because in does not carry current during normal operation. When a fault occurs the equipment ground wire carries fault current back to the panel where it travels across the system bonding jumper to the system neutral and back to the source. Remember the ground rod is there for surge protection (primarily cause by lightning) and is not a very good path for fault current. As a matter of fact without the bond to neutral the ground rod or electrode would not allow enough current to flow to trip a standard 20A breaker.

  • @robertsteich7362
    @robertsteich7362 3 หลายเดือนก่อน

    For when using a switch leg. I've always been taught to use the white wire from the light to the switch. So that the black wire gets connected to the light. Is that a code thing or just safe practice?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +2

      200.7(C) If used for single-pole, 3-way or 4-way switch loops, the reidentified conductor with white or gray insulation or three continuous white or gray stripes shall be used only for the supply to the switch, but not as a return conductor from the switch to the outlet.
      This is to prevent any confusion at the light about which wire is actually the neutral.

  • @matthewrichards9487
    @matthewrichards9487 2 หลายเดือนก่อน

    Code requires installation per MFG instructions. Anti short bussings are required accordingly.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      NEMA stands for National Electrical Manufacturers Association. They do not require Anti-shorts for MC cable. And since the connectors are not listed for use with anti-shorts you could be in violation of 110.3(B) by using them.

  • @Jonacarpenter
    @Jonacarpenter 3 หลายเดือนก่อน

    Thanks for another great piece!!!!

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      My pleasure! Thanks for watching..

  • @sjpropertyservices3987
    @sjpropertyservices3987 3 หลายเดือนก่อน

    Thank you for sharing.

  • @garypoplin4599
    @garypoplin4599 2 หลายเดือนก่อน +1

    8:51 - This is a common sense requirement: a 20 amp receptacle will accept cords connected to equipment that may draw higher currents than the 15 amp breaker can handle safely.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      And yet some people are arguing in the comments that its acceptable.. lol

    • @jovetj
      @jovetj 2 หลายเดือนก่อน

      Installing a 20A receptacle on a 15A circuit is just lying to the end-user. Seeing a 20A receptacle should tell you that circuit is sized and properly wired to deliver 20A. You wouldn't install a 50A receptacle on a 30A circuit either. Edit: And you wouldn't install a 3ɸ receptacle on a 1ɸ circuit.

    • @garypoplin4599
      @garypoplin4599 2 หลายเดือนก่อน

      @@jovetj Well said.

  • @vince6829
    @vince6829 3 หลายเดือนก่อน

    Thank you for sharing your knowledge

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      You bet! Thanks for watching my friend.

  • @edbouhl3100
    @edbouhl3100 3 หลายเดือนก่อน +1

    A lot of this kind of grief can be avoided by reading the manufacturer’s instructions. But that’s contrary to human nature.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +2

      Many will study the code to get licensed and then take a code update every three years as required. They don't read the manufacturers instructions and they don't read the code. Then they argue with those that do..

  • @KevinCoop1
    @KevinCoop1 3 หลายเดือนก่อน +1

    Here are a few more myths. General purpose receptacles in dwellings are calculated at 180 watts or 1-1/2 amps. You can only put 10 receptacles on a circuit in a dwelling. Voltage drop is “required” to be no more than 2% on a feeder and not more than 3% on a branch circuit. Conductor ampacity ratings must always be at 60C in 310.15(B)(16) for 15 amp through 60 amp circuits. The “ONLY” place that grounded conductors and equipment grounds are bonded is at the first means of disconnect in the system. The device that you plug your appliance into is called an “outlet”. Circuit breakers will trip as soon as they go over their rating, IE 21 amps on a 20 amp rated breaker. Ground fault current on equipment grounds goes to the grounding electrode system for protection. These are just a few more for you. If you need clarification, just ask a question.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      You’re correct. I can come
      Up with many more too.

    • @jovetj
      @jovetj 2 หลายเดือนก่อน

      Those are some good ones, better than this list, I'd say, of which only one was something I didn't know but never really thought about (and I'm not a licensed electrician). The Ground fault current one is common enough I've had to explain it to multiple people before.

    • @KevinCoop1
      @KevinCoop1 2 หลายเดือนก่อน

      @@jovetj So if not a licensed electrician, what do you do? Many do not know where a ground fault goes.

  • @Little_bane
    @Little_bane 2 หลายเดือนก่อน

    I get apprentices and journeymen that argue these things with me all the time, they claim that because the code does not require these practices, they should not have to do them.
    I demand certain standards of work, and my argument is why should our goal be the laziest, shittiest install we can get away with?
    Kinda funny that these same guys are the ones who are willing to ignore actual code requirements at times and try to get away with it, then bitch and whine when they fail inspections.
    Aluminum anti-ox is not required sure, but over time it still prevents corrosion. Anti-shorts are not required, but we still use them to avoid wire abrasion.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Do you also install conduit bushings on all EMT connectors and oversize your wires by a couple sizes? That would be a little better right.

  • @JeepinMaxx
    @JeepinMaxx 3 หลายเดือนก่อน

    Thank you - great information!

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Our pleasure! Thanks for watching.

  • @RodDay
    @RodDay 2 หลายเดือนก่อน

    Thanks for keeping me updated 😂

  • @TwilightxKnight13
    @TwilightxKnight13 3 หลายเดือนก่อน +1

    It is important to remember that the NEC is only the minimum requirements and the AHJ/inspector can impose additional requirements that you must comply with. If your inspector says you have to apply anti-oxidant to your cable connections, you must do so. So, before you decide to do things that are considered against the "industry standard" you should consult your inspector to make sure they do not require it. I know my local inspector requires anti-oxidant and does not allow spices to be install in a new-install service panel. It is not worth the aggravation to argue code with the inspector. As long as it meets NEC minimums, if the inspector requires more, just do it.
    The anti-short bushing issue is a tricky one. Many/most manufacturers of MC cable "suggest" the use of the bushing even with the approved, listed fitting. So, many inspectors/AHJ will require them under the NEC code that demands you must follow the installation recommendations and requirements of a product's manufacturer, even if/when those recommendations are not specifically required by individual NEC code listings.
    The receptacle issue is fairly straight forward. You cannot install a 20amp receptacle on the 15amp circuit for obvious reasons. It allows you to plug in a 20amp rated appliance/device that will demand up to 20amps which is more than the overcurrent protection device (breaker) and wire (#14 typically) is rated for. Therefore, it would at best trip the breaker, or at worse, over-heat the wiring causing the insulation to fail and creating a short.
    OTOH, installing a 15amp receptacle on a 20amp circuit is perfectly fine for one main reason. The receptacle configuration (lack of a horizontally opposed slot) does not allow you to plug a 20amp device into the outlet which would overload the rating of the receptacle. Devices/appliances rated less that 15amps have two parallel tabs on the plug, while devices/appliances rated 15-20amp have one tab turned 90 degrees.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      I get that stance but certainly you know that the AHJ is there for code compliance not to write code. I know they can make life difficult if you argue but they really need to stick with code enforcement. I think you may have misunderstood my last point which was you cannot install a 20A receptacle on a 15A circuit. You can absolutely install a 15A receptacle on a 20A circuit as long as it's not a single receptacle.

    • @georgeburns7251
      @georgeburns7251 3 หลายเดือนก่อน

      If your inspector can’t follow code, time to call his supervisor. I’ve never met an inspector who was an electrical engineer. They are not there to make up their own code. They are not qualified to do so by education, training, or the law.

    • @TwilightxKnight13
      @TwilightxKnight13 3 หลายเดือนก่อน

      @@georgeburns7251 in my experience most inspectors are tradesmen who wanted out of the daily grind of climbing ladders, kneeing on the floor, or lugging around 4-6” rigid pipe so they are generally as knowledgeable as the people they are inspecting. And while the inspector themselves are not specifically writing the code, the building board often adopts additional requirements beyond the code that the inspector must enforce even if you disagree with it. I’m just saying that at the end of the day, it best practice to know your inspector and to comply with the requirements they demand. It is so much less hassle than fighting with them and perhaps gaining a reputation as being argumentative. There is a big difference between the inspector asking for something that violates code, and asking for something that exceeds code. For example, requiring that anti-short bushings be used does not violate code, it exceeds code. So, it is perfectly reasonable for them to ask for bushings since it could only increase the level of safety. Just because the code does not specifically demand it, does not mean it is against code for the inspector to do so. The code is just the minimum standard by which work is to be completed, and the AHJ is free to add whatever additional requirements they want. In fact, the AHJ is under no requirement to adopt the NEC code at all. It’s just good practice. In Illinois, for example, the state does not recognize any plumbing code. It is completely left up to the local municipality to adopt their own plumbing standards and many have the bare minimum of rules. A few areas have no official “code” at all.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      The individual inspector is not the AHJ. The AHJ is usually the building/electrical dept. The way to consult with the AHJ regarding requirements is to seek out the written , published codes that have been formally adopted. Inspectors don’t get to make up and enforce personal preferences as a substitute for the legal code requirements. Some localities have one inspector, some have 50 or more, and some don’t have any and require third party inspectors for hire so personal preferences are unenforceable. There are also inspectors that aren’t and have never been electricians. Following the adopted, published code is what professionals do. Most inspectors are normal and reasonable and don’t have a god complex and know they can’t just make things up.

  • @NightNDay2.0
    @NightNDay2.0 2 หลายเดือนก่อน

    Can I also run two Romex wire in the same knockout hole in a plastic two gang box. Three gang box, four gang box also
    Also add NEC code for that would be nice

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      I don't find anything in the code that specifically prohibits two cables in the cable clamp. However it is implied since it does say that single gang non-metallic boxes without clamps can contain multiple cables. I think it comes down to 110.3 (B) where we need to follow the manufacturers instructions which would depend on the box manufacturer. This one on those things that comes down to the interpretation of the AHJ if you cannot find what the manufacturer recommends. I could be missing something... There are plenty of clamps in these boxes so the need to add two cables to one clamp should not be required.

    • @NightNDay2.0
      @NightNDay2.0 หลายเดือนก่อน

      ​@@BackyardMaine ah I see understand thank you very much

  • @smarthome2660
    @smarthome2660 3 หลายเดือนก่อน +1

    At 9:40 you should also mention the load restriction of a 20 amp breaker. This load shall not exceed 80% of the breaker. The standard for most household circuits are rated either 15 amps or 20 amps. An important note to remember is that circuit breakers can only handle about 80% of their overall amperage. That means a 15-amp circuit breaker can handle around 12-amps and a 20-amp circuit breaker can handle about 16 amps.
    The National Electrical Code (NEC) doesn't specify how many outlets can go on a 20-amp circuit. Instead, it focuses on the circuit's maximum power capacity-2,400 watts in this case-and recommends a safety margin of 80% of that load's total capacity. Jun 26, 2024

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +7

      That's maximum continuous load. For example a toaster is not considered a continuous load. Also a circuit breaker is designed to carry full circuit load indefinitely. The breakers trip at their set rating and time curve but is list for it's full load.

    • @jayztoob
      @jayztoob 3 หลายเดือนก่อน

      ​@BackyardMaine I see that you're getting a good grasp of the NEC. Thank you.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน

      @@BackyardMaine yes, the continuous load is the new benchmark on so many things now that we commonly see permanently installed microwaves and EVs in the garage.

  • @DonnieBodacious
    @DonnieBodacious 2 หลายเดือนก่อน

    You can use a 20amp outlet on a 15 amp circuit so long as it’s not a dedicated circuit and the breaker is 15amps.
    You 100% use anti shorts on the mc flex especially since a lot of dudes out there don’t get the connectors with intergraded anti shorts.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      No you cannot by code (showed in video) install a 20A receptacle on a 15A circuit. You can probably use anti-shorts as long as an inspector doesn't ding you on 110.3(B)

  • @carlospacheco6674
    @carlospacheco6674 3 หลายเดือนก่อน

    Awesome video!

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Thanks for the visit

  • @projectswithjw
    @projectswithjw 2 หลายเดือนก่อน

    Good stuff. 👍👍
    Time to cook some popcorn and go read the comment section 😆😆

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Hope you enjoy. Same deal with the forums.. Arm chair experts who don't read the code.

  • @DaddyBeanDaddyBean
    @DaddyBeanDaddyBean 2 หลายเดือนก่อน

    When re-identifying a wire, it must be permanently marked on some way: how is applying some electrical tape "permanent"? I cant really think of any other plausible method that ISN'T permanent, aside from tape. I scribble them black with a Sharpie. 🤷‍♂️

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      The tape will come off with a little bit of effort but the code accepts this as a permanent method. It won't fall off or become unreadable over time.

    • @DaddyBeanDaddyBean
      @DaddyBeanDaddyBean 2 หลายเดือนก่อน

      @@BackyardMaine ok then. Thank you.

  • @MarkCarson-e5f
    @MarkCarson-e5f 2 หลายเดือนก่อน

    In my experience in my part of the world it is required by the AHJ!

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I would ask them to point out the code reference..

  • @MarkCarson-e5f
    @MarkCarson-e5f 2 หลายเดือนก่อน

    No, you can make splices in panels as long as you don’t have too many splices on the same breaker, check your load requirements!

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I believe I stated we can make a splice in a panel.

  • @greenmoxy
    @greenmoxy 2 หลายเดือนก่อน

    After watching this video it's official, I'm a certified DIY electrician.

  • @lesterwatson8519
    @lesterwatson8519 3 หลายเดือนก่อน

    Is a duplex receptacle considered a single receptacle. Also is there a code that says no device shall be used in a circuit that is of a lower amperage rating than the overcurrent device supplying power to that circuit.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Good questions. First a duplex receptacle is two receptacle on a single device yoke as per article 100. A single receptacle has just one receptacle per device yoke. Also 15A receptacles are rated for 20A passthrough current per their uL listing. So they can safely carry 20A and are permitted to be installed on a 20A circuit as long as it's not a single receptacle. 15A receptacles are designed so a 20A plug cannot be connected. A 20A plug will have one horizontal blade and will not physically connect to a 15A device. I hope this helps.

  • @jonathanhughes380
    @jonathanhughes380 2 หลายเดือนก่อน

    You also forgot cable sizes 4 or larger can be re-identified cable sizes 6 and smaller can be re-identified if they're part of a cable assembly. If I remember correctly.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      You are correct but I didn't forget that. I was referring to cables for home wiring. I showed 200.7 in the video. I didn't show 200.6 since that was really not the point of the video. I may do another video covering marking since so many seem to not understand what you clearly do understand.

  • @jerrydemas2020
    @jerrydemas2020 3 หลายเดือนก่อน

    John, You said that you would address the requirements for ground rods with generators?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Sorry Jerry I have had some commitments to take care of. I have one more video and then I'll make the one on grounding.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      The bottom line is this. A neutral can only be bonded to ground in one location usually at the first service disconnect. So when connecting a generator for back up, the generator needs to have a floating neutral meaning it's not bonded to ground. This way the bond is still in one location as required by code. If not you can have all sorts of issues. It is possible to remove the bond if your generator is bonded. For a connection like I showed in a previous video the generator needs to be floating. In this case a ground rod is not required or recommended. Some generators, often whole home backup systems will have a bonded neutral. In this case the transfer switch needs to also switch the neutral conductor along with the hots to maintain a single bond. Then the generator would be considered a separately derived system. These system are required to be connected to a grounding electrode if not already connect to an existing electrode. Since we're not switching the ground wire we would still be connected to the building electrode, so it would still not be required. It is a common practice to install a ground rod with these system but we need to be far enough away from the existing electrode as per 250 in the code.

    • @jerrydemas2020
      @jerrydemas2020 3 หลายเดือนก่อน

      @@BackyardMaine Wow, Thanks John.

  • @MarkCarson-e5f
    @MarkCarson-e5f 2 หลายเดือนก่อน

    The reason why we need to use antioxidants to aluminum wires is when they are subjected to weather or moisture.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      No, exposure to oxygen is why it's used. Prevents aluminum oxide from forming.

  • @jimsvideos7201
    @jimsvideos7201 3 หลายเดือนก่อน

    Here I just saw a jiffy marker type tool that had a donut-shaped nib that you can feed the wire through to mark the whole thing at once.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      I just saw that as well. lol

    • @kenbrown2808
      @kenbrown2808 3 หลายเดือนก่อน

      I've often wanted one with a hook, a closed loop just seems like more bother than benefit.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      25 years ago I saw that tip in a magazine, drill hole in tip of marker for easy wire id. Tried it on one job and even though I trimmed out days after I marked them, went home with sharpee ink all over my hands. The first time was the last timeNeat idea, not so great in practice.

  • @jonjohnson3027
    @jonjohnson3027 3 หลายเดือนก่อน

    Bonus myth: On a 20A circuit that terminates in a single location, you can't use a 15A duplex receptacle.
    I can't cite the exact code section, but this is a misinterpretation of the rule that for a 20A circuit supplying a single receptacle, the receptacle must be 20A. However, 15A receptacles are allowed on 20A circuits where there is more than one receptacle, and a duplex receptacle counts as two receptacles on that circuit, so a lone 15A duplex receptacle CAN be used on a 20A circuit.
    Not saying it's a good idea; just saying it's a common myth.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      That is true. I think the terminology in the article is directed toward two or more 15A receptacles on a 20A circuit but it can be misleading as written.

  • @HobbyOrganist
    @HobbyOrganist 3 หลายเดือนก่อน

    I still use the anti short bushing regardless

  • @jefffree6990
    @jefffree6990 3 หลายเดือนก่อน +1

    9:10 Interesting that the chart shows you can't put a 20A receptacle on a 15A circuit (makes sense). But you can put a 50A receptacle on a 40A circuit ???

    • @rupe53
      @rupe53 3 หลายเดือนก่อน

      Trick question... depends on the wire size. You don't want to get caught in the middle with a continuous draw appliance and allow a larger draw than the rest of the circuit can handle. If your wire was rated for 50 amps then why have a 40 amp breaker? The breakers cost about the same.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Wire size is determined by the overcurrent device not the receptacle that's installed. 220.18. Remember that the table I show applies to branch circuits that supply more than one receptacle.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน

      @@BackyardMaine back to my "trick question".... nobody makes a 40 amp receptacle so you are stuck with something else. A 50 amp plug is probably not a good choice on a 40 amp circuit, although some might argue it's close enough because of the 80% rule.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      @@rupe53 Sorry. I was answering comment quickly and I missed your intent. You are correct there is no NEMA 40A receptacles. I was focusing on the circuit rating and wire size.

  • @jonathansands3304
    @jonathansands3304 2 หลายเดือนก่อน

    “The receptacle is higher than the circuit, so it’s protected, right?” Using the breaker as the primary limiter instead of the safety backup it’s supposed to be is like saying “I can drive as fast as I want, because the crumple zones/seat belts/air bags will protect me if I get in a crash.” 🤣

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I think you completely missed the point I was making.

    • @jonathansands3304
      @jonathansands3304 2 หลายเดือนก่อน

      @@BackyardMaine Oh, no, I was totally agreeing with you, just not the person who would have made that comment about the breaker protecting the circuit so the outlet didn’t matter!
      It’s like football helmets becoming safer, so players use their heads as battering rams more, while the designers are saying “No, we did that in case you *accidentally* hit your head!” Safety measures are there in case something goes wrong; they shouldn’t be relied on for normal use.

  • @michaeljavert4635
    @michaeljavert4635 3 หลายเดือนก่อน +1

    That's a nice desk. I wish I had that kind of money. Food would be nice right now. While some things aren't exactly code required, there is still best practices, like no splices in circuit box. Best to avoid it IF possible. Antioxidant paste is also a good practice. Won't hurt anything to go the extra effort. It is also better practice to use bushings and fittings on MC as long as it doesn't violate a code. I am the kind of attitude where it is better to have it, and not need it, than need it, and not have it. And if it exceeds code and doesn't violate it, why not ?
    Also, when people build a house or have a rewire, they should always go with the highest amperes possible. For example, eliminate all 14 gauge wire, the smallest should be 12, and thicker for higher circuits. And kitchen circuits should always have a separate circuit from the top to the bottom portion of the outlet. Prevents overloading when the toaster oven, fryer, coffee maker, simmer cooker, etc are all on at the same time. Also light circuits should be independent so that IF there is a problem, you're not in the dark wondering what happened. Great video. Maybe one day I will be able to afford nice things. Maybe one day, I'll be able to afford food again.

  • @boltonky
    @boltonky 3 หลายเดือนก่อน +3

    The problem were i live is the electrical code isn't available to the public an most electricians are self inspected (so they write the compliance cert sometimes without checking there work or the other worker who is installing it), so until something goes wrong (house burns down, serious injury etc) or a complaint gets put through you can be an might be living in a death trap....The amount of registered electricians i have had that don't do things right boggles my mind, this is why i believe knowledge is key an should be available but state exactly what a DIY person is allowed to do an what requires a certification (as there are grey areas)
    - when i say death trap like installing 3 phase cabling through steel framing with no protection an it cutting the wires (cause they clearly didn't want to spend $50 or so on conduit for a 7k job)
    great video :)

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +4

      You can purchase a code book. Anyone can but I will say without training they can be hard to interpret.

    • @kenbrown2808
      @kenbrown2808 3 หลายเดือนก่อน +3

      if you live in the US, you can buy a copy of the NEC. but it would be nice to have it available in public libraries. it would also be nice if the NFPA would go back to having it available in PDF format.

    • @KameraShy
      @KameraShy 3 หลายเดือนก่อน +2

      File a Freedom of Information Act (FOIA) with your local jurisdiction. Each one writes their own electrical code. They usually adopt the NEC and then enumerate any exceptions. Since the NEC is LEGALLY incorporated into local laws, a copy should be available for public inspection along with the municipal ordinance. There are court cases affirming this; I don't have citations offhand.

    • @jovetj
      @jovetj 2 หลายเดือนก่อน

      Self-inspection is pointless. It's like expecting all computer programmers to write perfectly-functioning bug-free code 100% of the time.

    • @kenbrown2808
      @kenbrown2808 2 หลายเดือนก่อน

      @@jovetj self inspected electricians will obviously "overlook" any violations they WANT to make, but they will also miss most of their errors, as well, just like proofreading your own writing.

  • @Mike__B
    @Mike__B 3 หลายเดือนก่อน

    Damn, I got dinged by an electrician that told me that I couldn't use phase tape to turn "neutrals" into "hots" when I needed to get my box inspected for new solar.

    • @elijahwaggoner545
      @elijahwaggoner545 3 หลายเดือนก่อน

      For wires smaller than 6awg you aren't supposed to phase tape any conductors

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +3

      Not true check your code.
      (C) Circuits of 50 Volts or More
      The use of insulation that is white or gray or that has three continuous white or gray stripes for other than a grounded conductor for circuits of 50 volts or more shall be permitted only as in (1) and (2).
      If part of a cable assembly that has the insulation permanently reidentified to indicate its use as an ungrounded conductor by marking tape, painting, or other effective means at its termination and at each location where the conductor is visible and accessible. Identification shall encircle the insulation and shall be a color other than white, gray, or green. If used for single-pole, 3-way or 4-way switch loops, the reidentified conductor with white or gray insulation or three continuous white or gray stripes shall be used only for the supply to the switch, but not as a return conductor from the switch to the outlet.
      A flexible cord having one conductor identified by a white or gray outer finish or three continuous white or gray stripes, or by any other means permitted by 400.22, that is used for connecting an appliance or equipment permitted by 400.10. This shall apply to flexible cords connected to outlets whether or not the outlet is supplied by a circuit that has a grounded conductor.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +3

      As long as it's in a cable or cord you can re-identify a white to be used as a hot. The commenter below is incorrect. Many electricians get this wrong because they confuse the requirements in 200.6. Maybe I need to make a dedicated video discussing this subject.

  • @mikesand2996
    @mikesand2996 3 หลายเดือนก่อน

    Using a white wire for hot is only when it's in a cable assembly, otherwise it has to be greater then 6awg

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +1

      I showed that in the video. It also cover flexible cord.

  • @71organicmusic9
    @71organicmusic9 2 หลายเดือนก่อน

    You wouldn't want to put a 20amp outlet on 14 gauge wire....its not so much the breaker but the gauge of wire.....it is only rated for 15 amps max....as far as white wire being used in a switch loop is now not code because a neutral is required at the switch box...and I don't understand why a anti short bushing is absolutely required...because the edges of the armored cable are very sharp....just like you must debur.....emt conduit......hmmmm

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Yes the breaker protects the wire which would be the point. A white wire can still be re-identified and used a loop/traveler. 3-way and 4-way switches only require a neutral conductor at one of the switch locations as per 404.2(C) so one of the traveler wires can be a re-identified white wire. The armor on MC cable is made of aluminum. The edges can still be sharp but not nearly as damaging as AC cable armor. Also MC cable has a thick layer of plastic between the conductors and the armor. This also protects the wires along with the design of listed connectors which protect the conductors from contacting the armor.

  • @deadmanswife3625
    @deadmanswife3625 3 หลายเดือนก่อน

    I live in a spider web of extension cords some of them are actually TENS for my power tools and some 12s😢

  • @garbo8962
    @garbo8962 3 หลายเดือนก่อน +2

    Side note on wasting money on 20 amp receptacles for residential settings. I installed over 25 receptacles in my house and only have one 20 amp receptacle ( because that was they only color I needed in stock for a GFCI ) In the 50 years living in the house and having contractors using large table saws, hammer drills , worm drive 8.5" circular saws. Floor sander, etc never had a 20 amp 120 volt male plug that had to be plugged in. I took a few different companies 15 & 20 amp duplex spec & cheaper grades receptacles apart and they all were made with the same guage & material. So don't waste money on 20 amp dup!ex receptacles.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน

      if you went to an industrial rated outlet, it would be different inside... and three times the price.

  • @andydelle4509
    @andydelle4509 2 หลายเดือนก่อน

    On 200.7C there is a caveat, Note the words CABLE ASSEMBLY. That means it's only OK to re-identify a white wire in Romex, MC, BX, or other manufactured cable assembly. What you can't do is to re-identify a single white, gray, or green, THHN inside a conduit. I assume the reason is that it is just as easy to pull the the right color wire in this case.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      Yes I showed that in the video.

    • @andydelle4509
      @andydelle4509 2 หลายเดือนก่อน

      @@BackyardMaine Sorry, I missed it.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Close. You are allowed to re-identify a white wire that's not part of a cable (making it a hot or ground, for example) as long as the color is changed along its entire length.

  • @johnh9748
    @johnh9748 2 หลายเดือนก่อน

    there are several reasons for not putting a 20 amp receptacle on a 15 amp circuit. Probably the most important reason is that a 20-amp appliance in that receptacle would cause frequent tripping. That will cause the breaker to wear faster. But the home user might try to prevent the tripping by placing a 20-amp breaker to replace the 15. This would result in a dangerous situation where a 20 amp breaker was protecting 15-amp wire.

    • @Progrocker70
      @Progrocker70 2 หลายเดือนก่อน

      I wonder if there even are any consumer grade appliances with 20 amp plugs? I've never seen any. I have a large toaster oven that draws 1800 watts which is close to the 80% limit of 20 amps but it has a standard cord. Of course it doesn't really get any continuous use for more than about a half hour. I have it on it's own 20 amp circuit and a single 20 amp receptacle.

  • @lafamillebrassard7692
    @lafamillebrassard7692 3 หลายเดือนก่อน

    I have a question can I re-identify a red wire as a neutral?

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน +5

      A wire that is part of a cable assembly and is not a neutral conductor (typically black, red, blue or other non-neutral color) can be re-identified as a neutral conductor, provided it is part of a 4-gauge or larger multi-conductor cable. This is done by marking the wire at every termination and at any accessible point along its length with white or gray tape, paint, or another approved means to indicate that it is now a neutral wire.
      For wires smaller than 4-gauge, the NEC requires the neutral conductor to be white or gray, and re-identification is not permitted.

    • @pld8993
      @pld8993 2 หลายเดือนก่อน

      Only if you change the entire length to white, which you can’t do in cable, but you can do with individual conductors.

  • @woodwaker1
    @woodwaker1 3 หลายเดือนก่อน

    Still come for the information and hat. USAF all the way.

    • @BackyardMaine
      @BackyardMaine  3 หลายเดือนก่อน

      Thank you so much.. 🇺🇸

  • @seprishere
    @seprishere 2 หลายเดือนก่อน

    Surely you *NEVER* connect neutral to earth/ground? The Distribution Network Operator routinely does, yes, but the consumer *never* does except for brief tests.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      The neutral (grounded conductor) is required to be bonded to the grounding electrode conductor at the first switch or panel. This bond is crucial to the safety and reliability of the system and can only be done in one location

    • @seprishere
      @seprishere 2 หลายเดือนก่อน

      @@BackyardMaine This is actually illegal in the UK, and can only be done by the DNO (either in the cutout, or not at all because it is TT or TN-S).

  • @insylem
    @insylem 2 หลายเดือนก่อน

    Like the Air Force hat

  • @plandl1
    @plandl1 2 หลายเดือนก่อน

    NOalox us usually applied now after the engineer requires it. They didn't get the memo.

  • @asoteico9528
    @asoteico9528 2 หลายเดือนก่อน

    Great !!!

  • @KaiserTom
    @KaiserTom 3 หลายเดือนก่อน

    If breakers actually tripped at exactly their amp rating and didn't degrade, especially degrading every time they trip, then putting 20A receptacles on a 15A circuit wouldn't be a problem. But that's not reality and a 15A breaker can take hours to trip at something like even 17A.

    • @rupe53
      @rupe53 3 หลายเดือนก่อน +1

      yes, they are rated for both time and internal temp so a slight overload may take an hour or more. Going from memory, I believe it might be like 120% for 30 minutes and 140% for 10 minutes. The testing specs are out there but not easy to find.

  • @Singlepole
    @Singlepole 2 หลายเดือนก่อน

    As a CEC electrician this whole video drives me crazy.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน +1

      I’ve been a licensed electrician for 40 years spending the last 10 working as an electrical engineer. I’ve worked with the code for 4 decades so I don’t know what drives you crazy.

    • @kevinteetzel8837
      @kevinteetzel8837 2 หลายเดือนก่อน +1

      @@BackyardMaine thats because the NEC (US code) and CEC (Canadian code) though very similar differ on all aspects covered by this video and many others as well. People googling this stuff do not know the difference.

    • @Singlepole
      @Singlepole 2 หลายเดือนก่อน

      @@BackyardMaine All of these things are required in Canada

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      @@Singlepole A lot of electricians think they're required here as well.

  • @syntaxerorr
    @syntaxerorr 3 หลายเดือนก่อน

    Great video

  • @othername1000
    @othername1000 3 หลายเดือนก่อน

    I love it when they point to the upper left corner and claim that there's something there. But it's not so I guess I'm not watching the next one.

    • @BackyardMaine
      @BackyardMaine  2 หลายเดือนก่อน

      I believe I said I’ll link it at the end of the video