3 Phase Balanced vs 3 Phase unbalanced system / load | Explained | TheElectricalGuy

แชร์
ฝัง
  • เผยแพร่เมื่อ 13 ก.ค. 2018
  • Three phase balanced system or load and Three phase unbalanced system or load are the two most commonly used concepts in power system. But, what do we really mean by a balanced or unbalanced 3 phase system? What are the parameters that decide whether a system is balanced or unbalanced? So, if you want to get the details and the basics of a 3 phase balanced and unbalanced system, watch the video.
    Star & Delta Connection - • Star and Delta Connect...
    For more interesting videos & articles about electrical engineering visit - www.theelectricalguy.in
    Find me:
    Facebook - / iamtheelectricalguy
    Instagram - / the_electricalguy
    LinkedIn - / gaurav-r-joshi
    TH-cam - / gauravj
    Google + - plus.google.com/u/0/+GauravRJ00

ความคิดเห็น • 226

  • @elguapo1507
    @elguapo1507 4 ปีที่แล้ว +18

    That was a smashing explanation which reminded me of my training in ac theory many years ago. Nicely done!

  • @bhuvanakrishna1960
    @bhuvanakrishna1960 6 ปีที่แล้ว +3

    Thanks for doing these videos....! Expecting more videos

  • @claytonharrop
    @claytonharrop 5 ปีที่แล้ว +3

    I watch HVAC SCHOOL channel to continue learning about my HAVC trade. I'm so glad I've finally found someone of the same quality to continue to learn about my Electrical trade! Thank you for these videos!

  • @MissionFitnessCTC
    @MissionFitnessCTC ปีที่แล้ว +6

    Good video. I would have liked to see more explanation around how the unbalance creates current flow in netural.

  • @glennmacabuhayvillas9461
    @glennmacabuhayvillas9461 4 ปีที่แล้ว +2

    Thanks for the video.

  • @etechnanban6478
    @etechnanban6478 5 ปีที่แล้ว +1

    Very clear explanation thank you....

  • @manjuchauhan2777
    @manjuchauhan2777 3 ปีที่แล้ว +2

    This is fantastic explanation I had never seen is in english

  • @abdulmughniabuzainah2561
    @abdulmughniabuzainah2561 6 ปีที่แล้ว +2

    You can’t imagine how useful your videos are to me..
    Keep going bro

    • @GauravJ
      @GauravJ  6 ปีที่แล้ว +1

      Thank you friend. Do share the video with your friends, so that it will also help them. 😊

    • @1994anandhu
      @1994anandhu 5 ปีที่แล้ว

      I too have Mr Gourav.. u r videos r so clearful.. Understandable.. I often recommend these videos to my students.

  • @prabakaranpk3291
    @prabakaranpk3291 5 ปีที่แล้ว +1

    Superb explication 👌👏

  • @mohammadpathan4668
    @mohammadpathan4668 6 ปีที่แล้ว +2

    very nice explanation!

  • @syamsreedevada2783
    @syamsreedevada2783 3 ปีที่แล้ว

    The best explaination that never heard

  • @KH4N0607
    @KH4N0607 3 หลายเดือนก่อน +1

    Thankyou for these videos ❤️

    • @GauravJ
      @GauravJ  3 หลายเดือนก่อน

      Glad you like them!

  • @sudhirpatil3434
    @sudhirpatil3434 5 ปีที่แล้ว +1

    Good explanation!

  • @thisukainol
    @thisukainol 11 หลายเดือนก่อน +1

    thanks a lot man

  • @Grumpytoolguy1959
    @Grumpytoolguy1959 5 ปีที่แล้ว +1

    Thank you, this series has been a great refresher for me!

  • @madhubandi2358
    @madhubandi2358 ปีที่แล้ว

    Thank you so much

  • @shijudas1184
    @shijudas1184 5 ปีที่แล้ว +1

    sooperb video bro

  • @emmanuelmawulikorve7805
    @emmanuelmawulikorve7805 3 ปีที่แล้ว +1

    You are awesome... Thanks for the video

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      My pleasure!! Do share and subscribe to my channel ✌🏻

  • @geethag3420
    @geethag3420 3 ปีที่แล้ว +1

    Superb sir...tqq soo much sir...😊😊

  • @radhakrishnans785
    @radhakrishnans785 5 ปีที่แล้ว +1

    Very easy to understand

  • @ajaytentu9904
    @ajaytentu9904 3 ปีที่แล้ว +1

    Thank you sir

  • @lpndoro
    @lpndoro 3 ปีที่แล้ว +1

    Excellent explanation.

  • @reeshamaniyath6937
    @reeshamaniyath6937 4 ปีที่แล้ว +1

    Thank u sir...ur videos very useful

  • @sububalan
    @sububalan 2 ปีที่แล้ว +1

    Thank you. This was a good refresher.

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว +1

      Do also check out other videos on my channel 😊

  • @johntony5421
    @johntony5421 4 ปีที่แล้ว +1

    good explain.....thanks much.

  • @khalidialsaqqa500
    @khalidialsaqqa500 3 ปีที่แล้ว +1

    Hi
    Thanks for your nice explanation.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      You are welcome ☺️ do share the videos!

  • @MrHazahari695
    @MrHazahari695 3 ปีที่แล้ว +1

    Thank you. It's helpful.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thank you ☺️ do share and subscribe to my channel ☺️✌🏻

  • @technicalswag3925
    @technicalswag3925 2 ปีที่แล้ว

    Smashing explanation

  • @DownToEngineer
    @DownToEngineer 2 ปีที่แล้ว +1

    Thanks! great explanation.

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว +1

      Do share and subscribe 😊

  • @naveenrevuri3611
    @naveenrevuri3611 3 ปีที่แล้ว +1

    Exlent explination

  • @Premsai18
    @Premsai18 3 ปีที่แล้ว +1

    Thanks brother for your easy explained I have understand easily❤️😍👍

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Good. Do share and subscribe to my channel ☺️✌🏻👍🏻

  • @sudiptakundu893
    @sudiptakundu893 4 ปีที่แล้ว

    Thank you so much sir

  • @phuzo3320
    @phuzo3320 5 ปีที่แล้ว +1

    U r really superb

  • @thezarina4681
    @thezarina4681 2 ปีที่แล้ว +1

    That was simple ND a neat explanation..keep going...thank q😇

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว

      Thanks 😊 do share and subscribe

  • @alexmrbvlogs
    @alexmrbvlogs 5 ปีที่แล้ว +2

    Thank you for this awesome explanation!!!

  • @sania9842
    @sania9842 4 ปีที่แล้ว +2

    execellent

  • @atemobengbeng
    @atemobengbeng 2 ปีที่แล้ว +7

    thank you for this 🥺 it is hard to learn with yourself specially now Online class i really enjoy watching and at the same time learning, now i have a learnings about 3phase system ❤️ thank you i know that it was 3years ago. but this can help not only me a lot of student will appreciate it thank you

  • @venkatavenkey3842
    @venkatavenkey3842 3 ปีที่แล้ว +2

    Good explanation thanq sir 👍 iam new subscription 🤗🤗🤗...

  • @randomshorts1729
    @randomshorts1729 3 ปีที่แล้ว +1

    Appreciated

  • @rashidchibvuri2036
    @rashidchibvuri2036 3 หลายเดือนก่อน +1

    Nice

  • @viswanathancr2801
    @viswanathancr2801 2 ปีที่แล้ว +1

    good video

  • @desyemoges745
    @desyemoges745 5 ปีที่แล้ว +3

    thank you your language is smooth and easy to understand

  • @jootube773
    @jootube773 3 ปีที่แล้ว +1

    very good

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks 😊 do share and subscribe to my channel ✌🏻

  • @erin4439
    @erin4439 5 ปีที่แล้ว +3

    Great video. Do you have any videos on calculations? I couldn't find one on your channel. I am currently learning Wye and Delta, balanced and unbalanced. It is difficult to find a video that will show how to learn the calculations. Thank you for your videos.

    • @azirulbahrom5438
      @azirulbahrom5438 4 ปีที่แล้ว

      Did u find out already? Im currently looking for it as well

  • @cr7_______....____
    @cr7_______....____ 3 ปีที่แล้ว +1

    perfect explanation.....well explained hats off bro

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thank you. Do subscribe to my channel and also share the video 🙂 you'll get more such easy to understand explanations 🙏

    • @cr7_______....____
      @cr7_______....____ 3 ปีที่แล้ว +1

      i already subscribed ur channel becoz u deserve it.....i hope u will keep providing us with such awesome videos regarding electrical engineering....

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thank you 😊 sure, I'll keep posting the videos

  • @mahadevakumar2104
    @mahadevakumar2104 4 ปีที่แล้ว +2

    Thanks for the video, which is the software u used to simulate ?

  • @akhilchikku1050
    @akhilchikku1050 5 ปีที่แล้ว

    Thanks

  • @pradhankartik817
    @pradhankartik817 4 ปีที่แล้ว

    Sir make some videos on electronic equipment such as rectifier, inverter, and many more...

  • @harishbonthala2494
    @harishbonthala2494 4 ปีที่แล้ว +1

    Sir, will you please upload a video about connections of windings in a power transformer

  • @mr.calculator1207
    @mr.calculator1207 ปีที่แล้ว +1

    Thank u sir.....and sir plz one request plz do video on power system

    • @GauravJ
      @GauravJ  ปีที่แล้ว

      Thank you. Videos available on my channel. Do check it out

  • @ImthiasAhamed
    @ImthiasAhamed 2 ปีที่แล้ว +1

    Good video
    Please explain use of MATLAB

  • @o-techtips3871
    @o-techtips3871 2 ปีที่แล้ว +2

    Nice👏

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว +1

      Thanks 😊 do also check out other videos on my channel 😊

    • @o-techtips3871
      @o-techtips3871 2 ปีที่แล้ว

      @@GauravJ sure bro...☺️👏

  • @Muxik4k
    @Muxik4k 3 ปีที่แล้ว

    Do you have faults analysis in 3 phase, for Delta and Star cases?

  • @manivk7784
    @manivk7784 2 ปีที่แล้ว

    Give the problems for this balenced and unbalenced loads sir thank you

  • @victoredo5115
    @victoredo5115 3 ปีที่แล้ว

    Hi Gaurav, Nice Work here. Can you please explain why we have Open points in a complex distributed power network?

  • @socialhackswithgunther5486
    @socialhackswithgunther5486 5 ปีที่แล้ว

    please add the applications of three phase systems too 🙏🙏

  • @sarathk.b5020
    @sarathk.b5020 4 ปีที่แล้ว +1

    Sir,
    What is the problem if the neutral is earthed in load side inorder to bypass unbalanced current?

  • @mosesezirim4430
    @mosesezirim4430 3 ปีที่แล้ว

    is there any scenario where the earth cable can be used in place of the neutral. if yes, can you do a video on that?

  • @shishirkhanal9131
    @shishirkhanal9131 4 ปีที่แล้ว

    i want video on different type of windings in machine like lap wave star delta etc

  • @suryavishwanath8564
    @suryavishwanath8564 4 ปีที่แล้ว +1

    love you sir !!! it was very helpful during my sem exams !!

  • @nickb1875
    @nickb1875 4 ปีที่แล้ว +3

    Hi sir, really liked your video. I'm not an electrician I am a DIY guy. I was wondering if it is possible to connect 2 or more ac power sources ( alternators or generators for example) in parallel, in order to obtain higher wattage whilst maintaining same voltage. For example, if the source produce 220 each. I want to keep the 220 but with high load capabilities.

    • @philip1541
      @philip1541 4 ปีที่แล้ว

      Yes that is possible and done i many places, the problem is you have to synchronize them meaning that L1 L2 and L3 have to be "in fase" when connected or it will not be possible.

  • @dwipayanmondal3636
    @dwipayanmondal3636 5 ปีที่แล้ว +1

    Thank you sir❤️

  • @sayedrezasadat4881
    @sayedrezasadat4881 11 หลายเดือนก่อน

    thanks it was really helpful but need some examples

  • @lawnwoke4958
    @lawnwoke4958 3 ปีที่แล้ว

    Thanks for the tutorial, kindly permit my to ask question. apart from electrical motors, what other devices do unbalance system affect.
    If a UPS is installed on unbalance system does it affect the output of the ups?

  • @tedlahm5740
    @tedlahm5740 4 ปีที่แล้ว

    Kindly delve into single phase step down transformer operation. With attention
    to the NEUTRAL connection thru the two windings. Primary and secondary.
    Thank you. Also please MENTION how much current is on the Neutral
    of an unbalanced system.

  • @omarsh77
    @omarsh77 4 ปีที่แล้ว

    If both source and load are solidly grounded and if we assume a negligible resistance in the neutral wire, shouldn't the supply neutral and the load neutral be at the same potential i.e. neutral current = 0 A?

  • @krishankantrajput7008
    @krishankantrajput7008 3 ปีที่แล้ว

    Sir please make video of poly phase system

  • @Rakeshjalli
    @Rakeshjalli 6 ปีที่แล้ว +2

    Please do vidoes on power system protection sirrr

    • @GauravJ
      @GauravJ  6 ปีที่แล้ว +1

      Sure my friend..👍🏻

  • @sudheeshss5503
    @sudheeshss5503 5 ปีที่แล้ว

    Sir.. I want to know about Negative sequence protection for generators.Kindly explain

  • @pushpakbhangale2689
    @pushpakbhangale2689 6 ปีที่แล้ว

    Hello sir, there is one question ,What will happen if we connect two AC source of same frequency and magnitude but uneqaul voltage (paralle and series in both case). say, one of 25 kv & another of 27 KV source to 25 KV load. What will be the effect on voltge, Power & current of the circuit as well as to the another 25 KV load? Previously i am working on the same ckt the 25 kv source if from Xmer and another source i am talking about is an induction motor which is connected parallely to Xmer as well as to the other loads. Whenever we require a mechanical energy we used it as a motor but at time of stoping we have used a regenerative braking system, at that time induction motor generates emf is more then 25 KV. One more thing i want to add on we have connected a braking resistors to motor ckt so that the generated power can be dissipated. But what if we didn't connect the braking resistors or if the resistors is blolwn out. What will be the reaction in ckt. If possible please make a video on this or send the explanation to my mail id pushpakbhangale303@gmail.com

  • @reddypochasivasankara4745
    @reddypochasivasankara4745 2 ปีที่แล้ว

    HI Gaurav,
    Can you post some detailed videos on inductions motors and it controls

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว

      Sure. I’ll try

  • @SivaKumar-cq2wu
    @SivaKumar-cq2wu 3 ปีที่แล้ว +1

    I am requesting upload video on effects of faults on alternator.

  • @allsquire8362
    @allsquire8362 2 ปีที่แล้ว

    Sir please describe the different types of protective relay and zone...

  • @charlescoyle433
    @charlescoyle433 4 ปีที่แล้ว

    Thank you for good explanation of balanced 3 phase distribution. Have question, Using 3 phase 208 volt Y power at our church. 3-phase to large HVAC equipment, Using individual phase legs and neutral to provide 120 volts to utility outlets in building. When circuit breaker is shut of on one of the 208 volt legs we see a small voltage across the switched off leg and neutral. Interested to know what causes small voltage appearance and if it is drawing any power. When measuring small voltage, ~20 t0 40 volts, there is no load across wires. Any explanation will be appreciated.

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว

      It may be because of the capacitive charge which is present in the transmission line/cable. You can use disconnector with earth switch, using earth switch you can ground the charge.

  • @santhoshdhanajaya815
    @santhoshdhanajaya815 2 ปีที่แล้ว

    3 phase system has unbalanced load in my factory do we have any alternative to balance it ?

  • @10-madhumitamanikmahapatra73
    @10-madhumitamanikmahapatra73 3 ปีที่แล้ว +1

    Very well explanation sir🙏🙏,sir can you please make video on three phase transformer.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thanks. Sure I'll try ✌🏻 do share and subscribe to my channel ☺️

  • @cryora
    @cryora 10 หลายเดือนก่อน

    What software do you use to simulate?

  • @sampawar7674
    @sampawar7674 3 ปีที่แล้ว +2

    Please explain concept of floating neutral

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Hi.. here is the video on floating neutral
      th-cam.com/video/b9hDHGxaufM/w-d-xo.html

  • @rushabhpancholi890
    @rushabhpancholi890 5 ปีที่แล้ว

    Really great teacher....
    You teach the concept very well.....
    Thank you sir...

  • @sayankumardey8497
    @sayankumardey8497 3 ปีที่แล้ว

    Through which software you simulate the waveform...

  • @ronmar1able
    @ronmar1able ปีที่แล้ว

    You have illustration control for medium voltage switchgear?

  • @SSSS-ot8yk
    @SSSS-ot8yk 5 ปีที่แล้ว

    Please do video about..in transmission lines voltage is high but current is low..it is not satisfying ohms law how it is?

  • @MrShafeek4
    @MrShafeek4 3 ปีที่แล้ว

    My 3 phase generator producing a low voltage on one phase the other 2 phase gone high? What is the reason and how can I fix this issue?

  • @kishankumar5014
    @kishankumar5014 2 ปีที่แล้ว

    Sir Please make a video on this topic three-phase transformer connections from basic .......please please.

  • @Abcde-yk6qy
    @Abcde-yk6qy ปีที่แล้ว

    Hi sir can you please explain why 3 phase falt cable one conductor get different reading ?

  • @swarupmohanty3655
    @swarupmohanty3655 4 หลายเดือนก่อน

    Sir how cbct detects these unbalances in phases please make a video on it

  • @minasagun8718
    @minasagun8718 5 ปีที่แล้ว

    How about if phases and neutral cables have same amount of current? What is the cause?

  • @soumya2221
    @soumya2221 3 ปีที่แล้ว

    Can u just make a video on harmonics and effect of it in industry pls

  • @manojkumarsaddala8236
    @manojkumarsaddala8236 5 ปีที่แล้ว

    how to create phase unbalance, is it possible to create phase unbalance using VFDs? or we can also induce the phase unbalance for DOL connections?

  • @manssupar
    @manssupar 5 ปีที่แล้ว

    Can i make load balancing on 1 phase?

  • @ramesheee3209
    @ramesheee3209 3 ปีที่แล้ว

    Do video about harmonics in generated

  • @TheHITHUN
    @TheHITHUN 4 ปีที่แล้ว

    Hey. What was that software

  • @karimullashaik3245
    @karimullashaik3245 ปีที่แล้ว

    Sir can you please fully explain unbalanced distribution system

  • @anirudh7829
    @anirudh7829 3 ปีที่แล้ว

    plz explain what is per phase analysis ?

  • @dashok4749
    @dashok4749 6 หลายเดือนก่อน

    Sir,Why the neutral conductor size is half the size of phase wire, during unbalanced condition the neutral current may be equal to phase current?

  • @safnamehabin509
    @safnamehabin509 3 ปีที่แล้ว

    Sir please add the concepts of measuring instruments

  • @samrush3700
    @samrush3700 7 หลายเดือนก่อน

    Hey can you make a video on fault occur on balanced system and haw 2 phases increase √3times in faulty condition

  • @DSEE-ShashikumarHanagi
    @DSEE-ShashikumarHanagi 9 หลายเดือนก่อน

    will you please explain how grounding is compensate unbalanced system to balanced system.

  • @youssofasiry7233
    @youssofasiry7233 9 หลายเดือนก่อน

    Thanks for your easy explain.
    What is the allowed unbalance persent of current in three phase motor and if I connenct neutral wire will protect the motor from heating?

    • @GauravJ
      @GauravJ  9 หลายเดือนก่อน

      Hi. A three phase motor is a balanced load and hence no neutral is required.

  • @fardinulhoque5339
    @fardinulhoque5339 3 ปีที่แล้ว

    Brother what happens for 100 ohm, -100j ohm and 100j ohm can they make a balanced delta load